2008-02-15 10:24:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1) SHEET 2, PIPING SCHEMATIC: THE HEAT PUMP IS MISSING
 FROM THE PIPING SCHEMATIC. AT A MINIMUM THE PIPING
 SCHEMATIC SHALL REFECT THE POOL DATA & EQUIPMENT DETAIL
 OF SHEET 1. PER CITY OF WPB AMENDMENTS TO CHAPTER 1,
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 AND SECTION 106.1.2 ADDITIONAL DATA.
  
 2) FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.(DETAIL
 REQUIRED FOR THE CLEANING LINE WITH THE MAKE AND MODEL
 NUMBER OR SUBMIT MANUFACTURE SPECIFICATION SHEET)
  
 3) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED CLEARLY INDICATING THE MAKE, MODEL
 NUMBER AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY, PLEASE SUBMIT)
  
 4) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 END OF COMMENTS:
  