| Plan Review Notes For Permit 08020051 |
| Permit Number |
08020051 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-04 14:16:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.PLEASE MAKE SECONDARY WATER BARRIER CLEAR | | | FS553.844(5)(A).I WAS UNABLE TO RESOLVE THIS ISSUE | | | WITH THE CONTRACTOR OVER THE TELEPHONE.TO AVOID FIELD | | | ISSUES, PLEASE PROVIDE THIS INFORMATION IN WRITING; | | | FLAT DECK AND PITCHED ROOF. | | | | | | 2.A PRODUCT APPROVAL WAS INCLUDED FOR POLYGLASS.IF | | | USING THIS AS AN UNDERLAYMENT, PROVIDE ASSOCIATED | | | DOCUMENTATION (EVALUATION REPORT AND INSTALLATION | | | INSTRUCTIONS) ALONG WITH THE FLORIDA STATE PRODUCT | | | APPROVAL COVER SHEET.ALSO NOTE METHOD OF INSTALLATION | | | (NOTE THAT DIRECT DECK/TILE DOES NOT MEET SECONDARY | | | WATER BARRIER REQUIREMENTS). | | | |
|