2008-08-22 11:13:46 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 REVISION DENIED
  
 1} THE LOCATION OF THE SERVICE IS IN VIOLATION OF
 110.26.
  
 2} THERE IS NO INDICATION OF THE SCOPE OF THIS
 REVISION. INDICATE BY CLOUDS AND DELTA'S OR ANOTHER
 METHOD DEEMED ACCEPTABLE BY THE PROFESSION, THE CHANGES
 TO BE REVIEWED FOR THIS REVISION. 106.1.3FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  