2008-02-04 16:20:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 2) PLEASE ADD THE JOB ADDRESS TO THE MECHANICAL PLAN,
 SEE 2004 WPB AMEND. 106.1.3.
  
 3) MODEL NUMBERS FOR A/C SYSTEMS 1 & 3 ON THE
 MECHANICAL PLAN COULD NOT BE FOUND ON THE ARI DIRECTORY
 WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI CERTIFICATE,
 SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 4) IF THE CORRECT MODEL NUMBER FOR CONDENSER UNIT #1 IS
 4TTR4030A THEN THE SYSTEM IS 13.75 SEER NOT 14 SEER
 (SEE ATTACHED ARI CERTIFICATE) IF SO PLEASE CORRECT
 MECHANICAL PLAN AND ENERGY CALCULATIONS, SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  