Plan Review Notes
Plan Review Notes For Permit 08020032
Permit Number 08020032
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-04 12:54:06** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON ELECTRICAL PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE PLANS ARE CALLING FOR SD AND LEGEND
 INDICATES SMOKE DETECTORS. PLEASE SEE NFPA-72
 DEFINITIONS AS SMOKE DETECTORS ARE ONLY DEVICES WHICH
 DETECT AND DO NOT SOUND AN ALARM.IF THESE ARE INDEED
 SMOKE DETECTORS, PLEASE SHOW THE FIRE ALARM PANEL,
 HORN/SOUNDING DEVICES ALONG WITH HORN LOCATIONS.
 IF THESE ARE INDEED SMOKE ALARMS WHICH DETECT AND SOUND
 AND ALARM, PLEASE ADJUST DESIGNATIONS AND SYMBOL
 LEGEND.
 PLEASE SEE 11.5.1.1, 11.8.3 AND FBC R313.
  
 3) NOTE: PLEASE CORRELATE RISER AND PANELS. PLEASE SEE
 THE PANELS ARE BOTH SHOWN AS MCB, (MAIN CIRCUIT
 BREAKERS) YET THE RISER SHOWS BOTH OF THESE AS MLO
 (MAIN LUG ONLY).
 FBC 106.1.2 ADMIN SECTION FOR COORDINATION.
 230, 215, 240, ETC
  
 4) NOTE: PLEASE SEE 2005 NEC FOR REQUIRED GFI
 PROTECTION OF ALL 15/20AMP RECEPTACLES/CIRCUITS LOCATED
 WITHIN 6FT OF LAUNDRY ROOM SINKS.
 PLEASE KNOW EVEN DEDICATED WASHER, DRYER RECEPTACLES
 ARE REQUIRED TO BE GFI PROTECTED. ** NOTE** AS THESE
 ARE REQUIRED TO BE SINGLE POINT OF USE, PLEASE BE SURE
 TO LIST BREAKER IN PANEL AS WELL.
 210.8A7** THIS WAS A CHANGE IN THE 2005 NEC.
  
 5) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS
 DINING ROOM, BREAKFAST AREA, BAR AREA AND AREAS OF THE
 LIKE REQUIRES RECEPTACLES TO BE ON ONE OR MORE OF THE
 SMALL APPLIANCE CIRCUITS. THIS WOULD MEANS *DINING ROOM
 RECETPS* 20A, #12, 1500 VA IN ADDITION TO THE TWO
 MINIMUM SMALL APPLIANCE CIRCUITS FOR SEPARATE OR
 ADDITIONAL CIRCUITS.
  
 6) NOTE: PLEASE BE SURE TO INCLUDE DESIGNATION FOR
 REQUIRED RECESSED LIGHTS PER 13-606.1.ABC.1.2.4
  
 7) NOTE: PLEASE INCLUDE LOADS FOR RECESSED LIGHTING PER
 220.14D.
 PLEASE SEE THE PLANS SHOW MORE THAN 60 RECESSED LIGHT
 FIXTURES. THESE ARE SHOWN ABOVE NORMAL GENERAL
 LIGHTING.
  
 8) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING
 REQUIRED.
 PLEASE SEE BEDROOM #4 FOR EXAMPLE AS THE SPACING WITHIN
 6FT OF DOORWAYS IN THREE LOCATIONS DO NOT MEET CODE.
  
 9) NOTE: PLEASE SEE MISSING THE MINIMUM CONDUCTOR SIZE
 FOR BATH GFI PER 210.11C3
 MUST BE #12 MINIMUM.
  
 10) NOTE: PLEASE SEE THERE ARE SEVERAL CONDUCTOR SIZES
 ON PANELS FOR BRANCH CIRCUITS WHICH NEED TO BE
 COMPLETED, CORRECTED AND COORDINATED. SOME EXAMPLES:
 PLEASE SEE THERE ARE BRANCH CIRCUIT CONDUCTORS MISSING
 AS NOTED FOR BATH ABOVE ALONG WITH COOK-TOP ETC.
 PLEASE SEE THERE ARE 20AMP BREAKERS ON #14AWG WHICH
 EXCEEDS THE RATING OF THE CONDUCTOR, SEE JACUZZI.
 PLEASE SEE THERE ARE NUMEROUS CIRCUITS WHERE THE
 CONDUCTORS ARE SHOWN EXCEEDING THE CIRCUIT SIZE. LARGER
 CONDUCTORS ARE NOT IN VIOLATION HOWEVER PLEASE SEE
 CIRCUITS SUCH AS WET BAR GFI WHICH SHOWS #6 FOR
 CIRCUIT. PLEASE SEE MICROWAVE WITH #8, REFRIGERATOR,
 SMALL APPLIANCES, GARAGE DOOR OPENERS ETC ALL WITH
 #10.
 PLEASE KNOW SOME OF THESE DEVICES AND BREAKERS ARE
 RATED TO THE #10, HOWEVER #6 WILL NOT WORK IN A GFI.
 THIS WOULD CREATE LISTING ISSUES WITH SEVERAL ITEMS.
 PLEASE COORDINATE ALL BRANCH CIRCUITS, PANEL SCHEDULES
 AND BREAKERS.
 240.4, 408.4, 310.16, 110.3, ETC
 FBC106.1.2, 106.3.5.4 ADMIN SECTION. COORDINATION.
  
 11) NOTE: PLEASE SEE PANEL SCHEDULE *B* LOAD
 CALCULATIONS AS THE AIR HANDLER HEAT LOAD IS SHOWN AT
 100 % WHICH IS NOTED AS 8.8 KW. HOW IS THIS POSSIBLE
 WHEN THE LOAD ON THE PANEL SCHEDULE ALSO INDICATES THIS
 AS 10KW?
 PLEASE COORDINATED.
 240.4, 310.16, 220, 408.4
 FBC 106.1.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  