| 2008-02-08 16:58:51 | NEW SINGLE FAMILY RESIDENCE, BUILDING REVIEW |
| | CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. MAY BE DONE AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 2- PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY |
| | OF PAID RECEIPT. MAY BE DONE AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 3- DESIGN PARAMETERS.WIND EXPOSURE CLASSIFICATION |
| | NEED TO BE CHANGED FROM "B" TO "C" AS REQUIRED BY SEC. |
| | R301.2.1.4(3)OF 2004 FLORIDA RESIDENTIALCODE.MORE |
| | THAN 600 FEET OF OPEN LAND ON ONE QUADRANT MAKES IT AN |
| | EXPOSURE "C". |
| | ALSO, NEED TO REVISE ALL THE DESIGN PRESSURES AS |
| | REQUIRED. |
| | |
| | NOTE: THIS NEEDS TO BE REVISED ONLOT 26 TOO. |
| | |
| | 4-A) SOIL TEST REPORT NEEDS TO HAVE THE FIRM |
| | CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY SEC. |
| | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | B) SOIL TEST REPORT NEEDS TO REFER TO FBC 2004, NOT |
| | 2001. REVISE AS REQUIRED. |
| | |
| | 5- ENERGY CALCULATIONS: |
| | A) REVISE NAME OF BUILDER. |
| | |
| | B) REVISE UNDER ATTIC AREA AS REQUIRED BY SEC. |
| | 13-604.1.A.1 FBC 2004. |
| | |
| | C) REVISE OVERHANG LENGTH AND HEIGHT TO MATCH ACTUAL |
| | FLOOR PLANS. AND ELEVATIONS. |
| | |
| | D) REVISE BUILDING ORIENTATION TO MATCH ACTUAL |
| | BUILDING ORIENTATION AND SHOW ALL OPENINGS. THERE ARE |
| | SOME OPENINGS THAT ARE MISSING.EG: THERE ARE NOT |
| | OPENINGS SHOWN FOR NORTH WALLS.SEE SURVEY FOR CORRECT |
| | BUILDING ORIENTATION AND REVISE AS REQUIRED. |
| | |
| | 6- ARCHITECT TO DATE DRAWINGS AS REQUIRED BY SEC. |
| | 61G1-16.004 OF FLORIDA ADMINISTRATIVE CODE.1/2008 IS |
| | NOT A COMPLETE DATE. |
| | |
| | 7- NEED TO PROVIDE ONE BATHROOMWITH DOOR THAT ALLOWS |
| | MIN. 29" CLEAR OPENING. SEC. 11-11.1 FBC 2004. |
| | |
| | 8-A) SPECIFY AREA OF PORCH ADJACENT TO THE LIVING |
| | ROOM TO PROPERLY ADJUST THE VALUATION AND RADON FEES. |
| | |
| | B) RECALCULATE ALL AREA ON SHEET A4 AND REVISE AS |
| | REQUIRED TO MATCH ACTUAL AREAS. EG: LANAI AREA IS |
| | INCORRECT. |
| | |
| | 9- PROVIDE COMPLETE DETAILS/SECTIONS AND SPECIFICATIONS |
| | FOR CONSTRUCTION OF ROOF CUPOLAS TO VERIFY COMPLIANCE |
| | WITH SEC. R301.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 10- PROVIDE MANUFACTURER SPECIFICATIONS AND DETAILS FOR |
| | CONSTRUCTION OF ROOF COVER OVER CHIMNEY.CHIMNEY CAPS |
| | MAY INTERFERE WITH PROPER FIREPLACE FUNCTION AND MAY |
| | AFFECT MANUFACTURER WARRANTIES. |
| | |
| | 11- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND |
| | APPROVED IN WRITING(NOT SIGNING AND SEALING) BY THE |
| | ARCHITECTAS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 12- PROVIDE PRODUCT APPROVALAS REQUIRED BY DCA RULE |
| | 9B-72FOR WINDOW AND DOORS MULLIONS. AND, CLEARLY |
| | SPECIFY SIZE AND FASTENING TO VERIFY COMPLIANCE WITH |
| | THE CALCULATED DESIGN PRESSURES. |
| | |
| | 13- SHEET A3: |
| | A) PROVIDE COMPLETE DETAILS/SPECS FORSCREEN |
| | ENCLOSURE AS REQUIRED BY SEC. R301.1 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | B) PROVIDE COMPLETE SPECS FOR TYPE OF COLUMNS AT THE |
| | ENDS OF LIVING ROOM WINDOWS,FAMILY ROOM BY THE FRENCH |
| | DOORSAND BY THE ENTRY PORCH. THERE ARE NO SPECS ON |
| | THE COLUMN LEGEND. |
| | |
| | C) PROVIDE COMPLETE DETAIL/SPECS FOR STEEL COLUMNS |
| | BETWEEN LIVING ROOM WINDOWS. NEED TO SPECIFY TOP AND |
| | BOTTOM CONNECTIONS. TO VERIFY COMPLIANCE WITH SEC. |
| | R301.1. |
| | |
| | D) PROVIDE COMPLETE DETAILS/SPECS FOR INSTALLATION |
| | OF STRUCTURALBUCKS IN STEEL COLUMNS AND ATTACHMENT OF |
| | WINDOWSIN LIVING ROOM AREA TO VERIFY COMPLIANCE WITH |
| | SEC. R301.1. |
| | |
| | 14- SHEET A4: |
| | A) DOOR AND WINDOW BUCK DETAILS NEED TO BE |
| | COORDINATEDWITH DETAILS SHOWN ON SHEET A7. ALSO, |
| | PROVIDE DETAILS THAT COMPLY WITH SEC. R613.6.BUCK |
| | NEEDSTO PROVIDE FULL SUPPORT TO DOOR AND WINDOW. |
| | |
| | B) REVISE SIZE OF FIXED WINDOW IN MASTER BEDROOM. |
| | 6060 FIXED WINDOW WAS DIVIDED INTO TWO TO SATISFY |
| | PRODUCT APPROVAL SIZE. |
| | |
| | 15- SHEET A5: THERE ARE MANYTRUSSES THAT ARE MISSING |
| | THE CONNECTORS.SPECIFY CONNECTORS FOR ALL TRUSSES TO |
| | VERIFY COMPLIANCE WITH CALCULATED UPLIFT LOADS OF SEC. |
| | R301.1 |
| | ALSO, THERE ARE SOME CONNECTORS THAT NEED TO BE |
| | COORDINATED FOR PROPER INSTALLATION. EG: CHECK |
| | CONNECTORS SPECIFIED ON GIRDER TRUSS ABOVE FAMILY ROOM |
| | AREA.REVIEWAND COORDINATE ALL SPECIFIED CONNECTORS |
| | TO MATCH PROPOSED INSTALLATION. |
| | |
| | 16- SHEET A7:TYPICAL WALL SECTION:A) REVISE TILE |
| | INSTALLATION.20.0 UPLIFT RESISTANCE IS NOT ADEQUATE. |
| | SEE PRODUCT APPROVAL. |
| | |
| | B) INFORMATION FOR FOOTING DIMENSIONS ABOVE AND |
| | BELOW GRADEIS OVERLAPPING. REVISE AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |