Plan Review Notes
Plan Review Notes For Permit 08020032
Permit Number 08020032
Review Stop B
Sequence Number 1
Notes
Date Text
2008-02-08 16:58:51NEW SINGLE FAMILY RESIDENCE, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE. MAY BE DONE AT TIME OF PERMIT PICK
 UP.
  
 2- PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT. MAY BE DONE AT TIME OF PERMIT PICK
 UP.
  
 3- DESIGN PARAMETERS.WIND EXPOSURE CLASSIFICATION
 NEED TO BE CHANGED FROM "B" TO "C" AS REQUIRED BY SEC.
 R301.2.1.4(3)OF 2004 FLORIDA RESIDENTIALCODE.MORE
 THAN 600 FEET OF OPEN LAND ON ONE QUADRANT MAKES IT AN
 EXPOSURE "C".
 ALSO, NEED TO REVISE ALL THE DESIGN PRESSURES AS
 REQUIRED.
  
 NOTE: THIS NEEDS TO BE REVISED ONLOT 26 TOO.
  
 4-A) SOIL TEST REPORT NEEDS TO HAVE THE FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 B) SOIL TEST REPORT NEEDS TO REFER TO FBC 2004, NOT
 2001. REVISE AS REQUIRED.
  
 5- ENERGY CALCULATIONS:
 A) REVISE NAME OF BUILDER.
  
 B) REVISE UNDER ATTIC AREA AS REQUIRED BY SEC.
 13-604.1.A.1 FBC 2004.
  
 C) REVISE OVERHANG LENGTH AND HEIGHT TO MATCH ACTUAL
 FLOOR PLANS. AND ELEVATIONS.
  
 D) REVISE BUILDING ORIENTATION TO MATCH ACTUAL
 BUILDING ORIENTATION AND SHOW ALL OPENINGS. THERE ARE
 SOME OPENINGS THAT ARE MISSING.EG: THERE ARE NOT
 OPENINGS SHOWN FOR NORTH WALLS.SEE SURVEY FOR CORRECT
 BUILDING ORIENTATION AND REVISE AS REQUIRED.
  
 6- ARCHITECT TO DATE DRAWINGS AS REQUIRED BY SEC.
 61G1-16.004 OF FLORIDA ADMINISTRATIVE CODE.1/2008 IS
 NOT A COMPLETE DATE.
  
 7- NEED TO PROVIDE ONE BATHROOMWITH DOOR THAT ALLOWS
 MIN. 29" CLEAR OPENING. SEC. 11-11.1 FBC 2004.
  
 8-A) SPECIFY AREA OF PORCH ADJACENT TO THE LIVING
 ROOM TO PROPERLY ADJUST THE VALUATION AND RADON FEES.
  
 B) RECALCULATE ALL AREA ON SHEET A4 AND REVISE AS
 REQUIRED TO MATCH ACTUAL AREAS. EG: LANAI AREA IS
 INCORRECT.
  
 9- PROVIDE COMPLETE DETAILS/SECTIONS AND SPECIFICATIONS
 FOR CONSTRUCTION OF ROOF CUPOLAS TO VERIFY COMPLIANCE
 WITH SEC. R301.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 10- PROVIDE MANUFACTURER SPECIFICATIONS AND DETAILS FOR
 CONSTRUCTION OF ROOF COVER OVER CHIMNEY.CHIMNEY CAPS
 MAY INTERFERE WITH PROPER FIREPLACE FUNCTION AND MAY
 AFFECT MANUFACTURER WARRANTIES.
  
 11- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING(NOT SIGNING AND SEALING) BY THE
 ARCHITECTAS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004.
  
 12- PROVIDE PRODUCT APPROVALAS REQUIRED BY DCA RULE
 9B-72FOR WINDOW AND DOORS MULLIONS. AND, CLEARLY
 SPECIFY SIZE AND FASTENING TO VERIFY COMPLIANCE WITH
 THE CALCULATED DESIGN PRESSURES.
  
 13- SHEET A3:
 A) PROVIDE COMPLETE DETAILS/SPECS FORSCREEN
 ENCLOSURE AS REQUIRED BY SEC. R301.1 2004 FLORIDA
 RESIDENTIAL CODE.
  
 B) PROVIDE COMPLETE SPECS FOR TYPE OF COLUMNS AT THE
 ENDS OF LIVING ROOM WINDOWS,FAMILY ROOM BY THE FRENCH
 DOORSAND BY THE ENTRY PORCH. THERE ARE NO SPECS ON
 THE COLUMN LEGEND.
  
 C) PROVIDE COMPLETE DETAIL/SPECS FOR STEEL COLUMNS
 BETWEEN LIVING ROOM WINDOWS. NEED TO SPECIFY TOP AND
 BOTTOM CONNECTIONS. TO VERIFY COMPLIANCE WITH SEC.
 R301.1.
  
 D) PROVIDE COMPLETE DETAILS/SPECS FOR INSTALLATION
 OF STRUCTURALBUCKS IN STEEL COLUMNS AND ATTACHMENT OF
 WINDOWSIN LIVING ROOM AREA TO VERIFY COMPLIANCE WITH
 SEC. R301.1.
  
 14- SHEET A4:
 A) DOOR AND WINDOW BUCK DETAILS NEED TO BE
 COORDINATEDWITH DETAILS SHOWN ON SHEET A7. ALSO,
 PROVIDE DETAILS THAT COMPLY WITH SEC. R613.6.BUCK
 NEEDSTO PROVIDE FULL SUPPORT TO DOOR AND WINDOW.
  
 B) REVISE SIZE OF FIXED WINDOW IN MASTER BEDROOM.
 6060 FIXED WINDOW WAS DIVIDED INTO TWO TO SATISFY
 PRODUCT APPROVAL SIZE.
  
 15- SHEET A5: THERE ARE MANYTRUSSES THAT ARE MISSING
 THE CONNECTORS.SPECIFY CONNECTORS FOR ALL TRUSSES TO
 VERIFY COMPLIANCE WITH CALCULATED UPLIFT LOADS OF SEC.
 R301.1
 ALSO, THERE ARE SOME CONNECTORS THAT NEED TO BE
 COORDINATED FOR PROPER INSTALLATION. EG: CHECK
 CONNECTORS SPECIFIED ON GIRDER TRUSS ABOVE FAMILY ROOM
 AREA.REVIEWAND COORDINATE ALL SPECIFIED CONNECTORS
 TO MATCH PROPOSED INSTALLATION.
  
 16- SHEET A7:TYPICAL WALL SECTION:A) REVISE TILE
 INSTALLATION.20.0 UPLIFT RESISTANCE IS NOT ADEQUATE.
 SEE PRODUCT APPROVAL.
  
 B) INFORMATION FOR FOOTING DIMENSIONS ABOVE AND
 BELOW GRADEIS OVERLAPPING. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712