| Plan Review Notes For Permit 08020014 |
| Permit Number |
08020014 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-04 15:00:29 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PER 230.2 NUMBER OF SERVICES: | | | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED | | | BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A) | | | THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 | | | ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND | | | LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED | | | TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER | | | AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING | | | ONE SERVICE.PLEASE INDICATE UNDER WHICH EXCEPTION THE | | | SECOND SERVICE WOULD MEET. | | | | | | 2}PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED IF | | | THE SERVICE IS ALLOWED. WE ARE SPECIFICALLY CONCERNED | | | WITH GROUPING ISSUES PER 230.72. | | | | | | 3} PER 110.9 AND 110.10 PROVIDE THE AIC CALCULATION AND | | | THE RATING OF THE EQUIPMENT TO BE INSTALLED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | | | | |
|