| Plan Review Notes For Permit 08010762 |
| Permit Number |
08010762 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-02-27 14:37:52 | COMMERCIAL ROOFING BUILDING REVIEW SECOND CHECKLIST: | | | | | | 1-FLAT ROOF SYSTEM NOA05-0830.10 SUBMITTED AND | | | ENGINEER'S RAS 117 CALCULATIONS ARE FOR TWO DIFFERENT | | | PRODUCTS.NOA 05-0830.10 IS A PRODUCT FROM FIRESTONE | | | BUILDING PRODUCTS COMPANY, WHILE NOA 06-0410.06 | | | REFERENCED BY THE ENGINEER IS A PRODUCT FROM POLYGLASS | | | USA.NEED INFORMATION THAT MATCHES TO EACH OTHER. | | | | | | 2-ONLY TWO SETS OF ENGINEER CALCULATIONS WERE | | | PROVIDED.THREE SETS OF EVERYTHING IS REQUIRED IN THIS | | | JOB BECAUSE THERE IS A THRESHOLD INSPECTOR IN THIS | | | JOB. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|