| Plan Review Notes For Permit 08010729 |
| Permit Number |
08010729 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-07-30 15:36:46 | REVISION: "OK" ADDED GAS PIPING TO FIRE PIT & VALUE | | | INCREASED. | | | | | | ****************PROVISO**************** | | | A} IF DRYER ROOM IS A CONFINED SPACE, OPENINGS | | | REQUIRED PER SECTION 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | | | B} IF WATER HEATER ROOM IS A CONFINED SPACE, OPENINGS | | | REQUIRED PER SECTION 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. MINIMUM 3,850 CUBIC FEET REQUIRED. | | | | | | C} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR | | | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | | | | |
|