| 2008-03-11 08:24:54 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) TWO COPIES OF THE ENERGY CALCULATIONS AND COOLING |
| | LOAD CALCULATIONS NEED TO BE SUBMITTED PER 2004 WPB |
| | AMEND. 106.1. |
| | |
| | 2) COOLING LOAD CALCULATIONS ARE CALLING FOR 97,985 |
| | TOTAL COOLING BTU'S OR 8.17 TONS, THE MECHANICAL PLAN |
| | EQUIPMENT SCHEDULE IS SHOWING 42,000 TOTAL COOLING |
| | BTU'S. PER 2004 FBC 13-407.1.ABC.1.1,HVAC SYSTEMS AND |
| | EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN THE |
| | SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE WITH |
| | SECTION 407.1.ABC.1 . A SINGLE PIECE OF EQUIPMENT |
| | PROVIDING BOTH COOLING AND HEATING SHALL SATISFY THIS |
| | PROVISION WHEN THE COOLING FUNCTION MEETS THE |
| | PROVISIONS OF SECTION 407.1.ABC.1 , AND THE HEATING |
| | FUNCTION IS SIZED AS SMALL AS POSSIBLE TO MEET THE LOAD |
| | WITHIN AVAILABLE EQUIPMENT OPTIONS. PLEASE CORRECT |
| | COOLING LOAD CALCULATIONS. |
| | |
| | 3) NOT NOTICED IN LAST REVIEW MECHANICAL PLAN OUTSIDE |
| | AIR CALCULATIONS ARE REFERENCING 2007 ASHRAE 62, THE |
| | CITY OF W.P.B. HAS NOT ADOPTED THE 2007 ASHRAE 62 BUT |
| | IS USING THE 2004 ASHRAE 62, PLEASE CORRECT. |
| | |
| | 4) NOT NOTICED IN LAST REVIEW MECHANICAL PLAN OUTSIDE |
| | AIR CALCULATIONS ARE REFERENCING SECTION 6.1.3.4 OF |
| | ASHRAE 62 PLEASE BE AWARE I COULD NOT FIND ANY SUCH |
| | SECTION IN ASHRAE 62. PLEASE SEE SECTION 6.2.6.1 OF |
| | 2004 ASHRAE 62 FOR VARIABLE LOAD CONDITIONS. PLEASE |
| | CORRECT. |
| | |