Plan Review Notes
Plan Review Notes For Permit 08010673
Permit Number 08010673
Review Stop M
Sequence Number 2
Notes
Date Text
2008-03-11 08:24:54PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) TWO COPIES OF THE ENERGY CALCULATIONS AND COOLING
 LOAD CALCULATIONS NEED TO BE SUBMITTED PER 2004 WPB
 AMEND. 106.1.
  
 2) COOLING LOAD CALCULATIONS ARE CALLING FOR 97,985
 TOTAL COOLING BTU'S OR 8.17 TONS, THE MECHANICAL PLAN
 EQUIPMENT SCHEDULE IS SHOWING 42,000 TOTAL COOLING
 BTU'S. PER 2004 FBC 13-407.1.ABC.1.1,HVAC SYSTEMS AND
 EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN THE
 SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE WITH
 SECTION 407.1.ABC.1 . A SINGLE PIECE OF EQUIPMENT
 PROVIDING BOTH COOLING AND HEATING SHALL SATISFY THIS
 PROVISION WHEN THE COOLING FUNCTION MEETS THE
 PROVISIONS OF SECTION 407.1.ABC.1 , AND THE HEATING
 FUNCTION IS SIZED AS SMALL AS POSSIBLE TO MEET THE LOAD
 WITHIN AVAILABLE EQUIPMENT OPTIONS. PLEASE CORRECT
 COOLING LOAD CALCULATIONS.
  
 3) NOT NOTICED IN LAST REVIEW MECHANICAL PLAN OUTSIDE
 AIR CALCULATIONS ARE REFERENCING 2007 ASHRAE 62, THE
 CITY OF W.P.B. HAS NOT ADOPTED THE 2007 ASHRAE 62 BUT
 IS USING THE 2004 ASHRAE 62, PLEASE CORRECT.
  
 4) NOT NOTICED IN LAST REVIEW MECHANICAL PLAN OUTSIDE
 AIR CALCULATIONS ARE REFERENCING SECTION 6.1.3.4 OF
 ASHRAE 62 PLEASE BE AWARE I COULD NOT FIND ANY SUCH
 SECTION IN ASHRAE 62. PLEASE SEE SECTION 6.2.6.1 OF
 2004 ASHRAE 62 FOR VARIABLE LOAD CONDITIONS. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]