Plan Review Notes
Plan Review Notes For Permit 08010673
Permit Number 08010673
Review Stop M
Sequence Number 1
Notes
Date Text
2008-01-30 11:45:57PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS FORM A MAY NOT BE USE FOR A
 RENOVATION, SEE 2004 FBC 13-101.1.3. PLEASE SUBMIT FORM
 C OR B.
  
 2)PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 3) PLEASE PROVIDE WIND LOAD CALCULATIONS FOR A/C
 CONDENSED UNIT AND STAND ON PAGE M-1, SEE 2004 FBC/M
 301.13.
  
 4) A/C SYSTEM LISTED ON A/C EQUIPMENT SCHEDULE COULD
 NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE
 CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 FBC
 13-407.1.ABC.3.1.1.
  
 5) A/C EQUIPMENT SCHEDULE ON PLAN M-1 SHOWS KW HEAT AS
 88 KW, PLEASE CORRECT.
  
 6) PLEASE STATE WHERE THE CONDENSATE LINE WILL DISPOSE
 TO, SEE 2004 FBC/M 307.2.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]