| 2008-02-01 14:57:44 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} 13-415.1.ABC.1.2 SPACE CONTROL. |
| | EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL |
| | HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY |
| | CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH |
| | MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED |
| | SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. A. A |
| | CONTROL DEVICE SHALL BE INSTALLED THAT AUTOMATICALLY |
| | TURNS LIGHTING OFF WITHIN 30 MINUTES OF ALL OCCUPANTS |
| | LEAVING A SPACE, EXCEPT SPACES WITH MULTISCENE CONTROL, |
| | IN THE FOLLOWING: 1. CLASSROOMS (NOT INCLUDING SHOP |
| | CLASSROOMS, LABORATORY CLASSROOMS, AND PRESCHOOL |
| | THROUGH 12TH GRADE CLASSROOMS). |
| | 2. CONFERENCE/MEETING ROOMS. |
| | 3. EMPLOYEE LUNCH AND BREAK ROOMS. |
| | INDICATE SAME OM PLANS. |
| | |
| | 2} THE CALCULATED LOAD (SHEET E-3) FOR THE A/C |
| | EQUIPMENT DOES NOT MATCH THE MECHANICAL SPECS ON SHEET |
| | M-1, CORRELATE SAME. |
| | |
| | NOTE:PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL |
| | BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE |
| | ARTICLE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |