 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 13-415.1.ABC.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. A. A
 CONTROL DEVICE SHALL BE INSTALLED THAT AUTOMATICALLY
 TURNS LIGHTING OFF WITHIN 30 MINUTES OF ALL OCCUPANTS
 LEAVING A SPACE, EXCEPT SPACES WITH MULTISCENE CONTROL,
 IN THE FOLLOWING: 1. CLASSROOMS (NOT INCLUDING SHOP
 CLASSROOMS, LABORATORY CLASSROOMS, AND PRESCHOOL
 THROUGH 12TH GRADE CLASSROOMS).
 2. CONFERENCE/MEETING ROOMS.
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
 INDICATE SAME OM PLANS.
  
 2} THE CALCULATED LOAD (SHEET E-3) FOR THE A/C
 EQUIPMENT DOES NOT MATCH THE MECHANICAL SPECS ON SHEET
 M-1, CORRELATE SAME.
  
 NOTE:PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL
 BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.
  