| 2008-04-11 11:00:22 | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS AS WELL AS |
| | THE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | NEW COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS |
| | PLUMBING REVIEW COMMENTS. |
| | |
| | 1. **OK** COMMENT ADDRESSED, LETTERS HAVE BEEN |
| | FORWARDED TO KEN CONRAD CHIEF BUILDING INSPECTOR. |
| | |
| | 2. SHEET S1 IS INDICATING A BATHROOM WITH A WATER |
| | CLOSET AND LAVATORY AND SHEET S-1 IS INDICATING A 4" |
| | SLAB-ON-GRADE. IS IT THE INTENTOF THIS FOUNDATION |
| | PERMIT TO POUR THE SLAB ON GRADE WITHOUT THE |
| | UNDERGROUND PLUMBIMG BEING INSTALLED. PLEASE CLARIFY |
| | PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION |
| | 106.1.2 ADDITIONAL DATA REQUIRED. |
| | **RESONSE NOTED AND REVIEW OF THE NEW ATTACHED |
| | PLUMBING SHEETS WILL BE UNDER NEW COMMENTS. |
| | |
| | 3. **PLUMBING PROVISO** PER CITY OF WPB AMENDMENTS TO |
| | CHAPTER 1, SECTION *105.13 PHASED PERMIT APPROVAL. |
| | AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION |
| | DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE |
| | A PERMIT FOR THE CONSTRUCTION OF THE FOUNDATIONS. THE |
| | HOLDER OF SUCH PERMIT FOR THE FOUNDATION SHALL PROCEED |
| | AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION |
| | AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| | STRUCTURE WILL BE GRANTED. CORRECTIONS MAY REQUIRED TO |
| | MEET THE REQUIREMENTS OF THE TECHNICAL CODE. |
| | **RESPONSE NOTED. |
| | |
| | THE FOLLOWING ARE NEW COMMENTS. |
| | |
| | 4. SHEET C1 USE AND OCCUPANCY CLASSIFICATION IS |
| | INDICATING ON THE FIRST AND SECOND LEVEL THAT MODERATE |
| | HAZARD STORAGE IS IN GROUP S-1. WHAT TYPES AND QUANTITY |
| | OF HAZARDOUS MATERIALS ARE GOING TO BE STORED? PER |
| | (W.P.B.) SECTION 106.1.2 ADDITIONAL DATA AND FBC |
| | PLUMBING SECTION 411 EMERGENCY SHOWER AND EYEWASH |
| | STATIONS MAY BE REQUIRED. |
| | |
| | 5. SHEET P1.1 INDICATES FOUR SEPERATE RETAIL SPACES. |
| | PLEASE CLARIFY IF THE RETAIL SPACES HAVE ONE OWNER OR |
| | IF THERE ARE FOUR SEPERATE OWNERS. PER FBC PLUMBING |
| | SECTION 403.6 PUBLIC FACILITIES.CUSTOMERS, PATRONS AND |
| | VISITORS SHALL BE PROVIDED WITH PUBLIC TOILET |
| | FACILITIES IN STRUCTURES AND TENANT SPACES INTENDED FOR |
| | PUBLIC UTILIZATION. PUBLIC TOILET FACILITIES SHALL BE |
| | LOCATED NOT MORE THAN ONE STORY ABOVE OR BELOW THE |
| | SPACE REQUIRED TO BE PROVIDED WITH PUBLIC TOILET |
| | FACILITIES AND THE PATH OF TRAVEL TO SUCH FACILITIES |
| | SHALL NOT EXCEED A DISTANCE OF 500 FEET (152 M). |
| | |
| | 6. SHEET P1.1 THE STORM DRAIN REQUIRES A TWO-WAY |
| | CLEANOUT OUTSIDE OF THE BUILDING. PER FBC PLUMBING |
| | SECTION 1101.8 CLEANOUTS REQUIRED (SECTION 708.3.5 ). |
| | |
| | 7. SHEET P3.1 PLEASE CLARIFY IF THERE ARE PARAPET |
| | WALLS AND IF SO WHAT ARE THE CALCULATIONS? PER FBC |
| | PLUMING SECTION 1106.4 VERTICAL WALLS. |
| | |
| | 8. SHEET P3.2 THE SQUARE FOOTAGE FOR RD-1 AND RD-2 |
| | APPEARS LOW. MY CALCULATIONS COME TO 2517.5 SQ. FT. FOR |
| | RD-1 AND 2052 SQ. FT. FOR RD-2 AND THATS NOT |
| | CALCULATING IF THERE ARE PARAPET WALLS. PER FBC |
| | PLUMBING SECTION 1101.1 SCOPE AND 1106.4 VERTICAL |
| | WALLS. |
| | |
| | 9. SHEET P4.1 PLUMBING SPECIFICATIONS (2) CODES AND |
| | STANDARDS (A) THE CODE STANDARDS REFERENCED ARE NOT |
| | COMPLIANT PLEASE DELETE THOSE CODE REFERENCE STANDARDS |
| | AND ADD IN ITS PLACE "FBC-2004 WITH 2007 REVISIONS". |
| | |
| | 7. SHEET P4.1 PLUMBING SPECIFICATIONS (5) MATERIALS |
| | (F) AIR CHAMBERS ARE NOT APPROVED BY FBC PLUMBING |
| | SECTION 604.9 WATER HAMMER. HOWEVER IF IT IS THE INTENT |
| | TO USE AIR CHAMBERS THEY SHALL BE INSTALLED PER |
| | "STANDARD PDI-WH 201 RECHARGEABLE TYPE AIR CHAMBER. A |
| | DETAIL OF THIS TYPE OF AIR CHAMBER IS REQUIRED ON PLANS |
| | OR DELETE AIR CHAMBERS ON THE RESUBMITTAL. |
| | |
| | 8. SHEET P4.1 SANITARY RISER A CLEANOUT IS REQUIRED AT |
| | THE BASE OF THE STACK ON RISER S-1, PER FBC PLUMBING |
| | SECTION 708.3.4 AND A TWO-WAY CLEANOUT IS REQUIRED AT |
| | THE JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER, |
| | PER FBC PLUMBING SECTION 708.3.5. |
| | |
| | 9. SHEET P4.2 STORM RISERS CLEANOUTS ARE REQUIRED AT |
| | THE BASE OF THE VERTICAL STORM LEADERS, PER 1101.8 |
| | (708.3.4) AND A TWO-WAY CLEANOUT IS REQUIRED ON THE |
| | HORIZONTAL STORM DRAINAGE PIPE OUTSIDE OF THE BUILDING, |
| | PER FBC PLUMBING 1101.8 (708.3.5). |
| | |
| | 10. SHEET P4.2 STORM RISERS: THE STORM RISERS WERE |
| | REVIEWED PER MINIMUM REQUIREMENTS PER FBC PLUMBING |
| | TABLE 1106.3 SLOPE OF 1/8 INCH PER FOOT (1-PERCENT). IF |
| | IT IS THE INTENT OF THE DESIGNER TO USE OTHER SLOPE |
| | REQUIREMENTS IT MUST BE CLEARLY INDICATED ON THE PLANS. |
| | PLEASE CORRECT ALL MAIN UNDERGROUND HORIZONTAL STORM |
| | DRAINAGE PIPING SIZES FOR THE ROOF DRAINS. PLEASE |
| | CORRECT THE FOLLOWING BRANCHES TO THE ABOVE GROUND |
| | HORIZONTAL STORM DRAINAGE PIPE TO RD-1, RD-2, RD-3, AND |
| | RD-5. PLEASE CORRECT ALL MAIN ABOVE GROUND HORIZONTAL |
| | STORM DRAINAGE PIPE SIZES FOR THE EMERGENCY DRAINS. |
| | PLEASE CORRECT THE FOLLOWING BRANCHES TO THE ABOVE |
| | GROUND HORIZONTAL STORM DRAINAGE PIPE TO ED-3, AND |
| | ED-5. PER FBC PLUMBING TABLE 1106.3 (1-PERCENT SLOPE). |
| | |
| | |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |