2008-04-07 14:47:51** DENIED 2ND REVIEW **
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW ARE STILL IN
 NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SUBMIT ELECTRICAL PLANS/DETAIL FOR THE
 REQUESTED FOUNDATION PERMIT SCOPE OF WORK.
 PLEASE SEE 250.50 AS THE FOOTER STEEL IS REQUIRED TO BE
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 RESPONSE LETTER FROM ARCHITECT MENTIONS TO SEE PLANS
 WHICH WILL PART OF THE MAIN BUILDING PERMIT HOWEVER THE
 FOUNDATION STEEL IS PART OF THE SCOPE OF WORK FOR THIS
 PERMIT AND ELECTRICAL PLANS/DETAILS ARE REQUIRED.
 PLEASE SEE THE LETTER FROM THE ENGINEERING FIRM TEELE
 AND ASSOCIATES DOES NOT PROVIDE THE REQUIRED PLANS.
 THIS LETTER MAKES REFERENCE TO THE NEC AND 250.66B AND
 250.70 WITHOUT ACTUALLY SUBMITTING ANY PLANS. THE
 SHEETS ATTACHED TO THE LETTER ARE NOT FROM THE NEC/
 NFPA-70 2005.
 PLEASE ALSO KNOW THE CODE SECTION AS REFERENCE IN
 LETTER ONLY APPLIES IN CERTAIN CIRCUMSTANCES. THE
 SIZING OF THE GROUNDING ELECTRODE CONDUCTOR IS STILL
 REQUIRED TO MEET 250.66.
 PLEASE SUBMIT MINIMUM PLANS AS PREVIOUSLY NOTED.
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: *** IMPORTANT ***
 PLEASE KEEP IN MIND AS SLAB WORK APPEARS TO BE PART OF
 THE PROPOSED FOUNDATION, ANY SLAB CONDUITS FOR
 ELECTRICAL WOULD NEED TO BE SHOWN ALSO AT THIS TIME. IF
 SLAB WORK WILL NOT CONTAIN ANY SLAB CONDUITS FOR ITEMS
 SUCH AS FLOOR BOXES, FEEDERS ETC THEN THIS WILL NOT BE
 NEEDED.
 ***
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  