| 2008-02-05 09:29:07 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A03 IS INDICATING IS INDICATING PRIMARY AND |
| | SECONDARY ROOF DRAINAGE, PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION FOR THESE REQUIRED DRAINS. |
| | |
| | A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF |
| | AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS |
| | AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004 |
| | PLUMBING, SECTION 1106. |
| | B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004 |
| | PLUMBING, SECTION 1106.2 |
| | C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION |
| | 1106.4 |
| | D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING, |
| | SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004 |
| | PLUMBING, TABLE 1106.7. |
| | E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004 |
| | PLUMBING, SECTION 1107. |
| | A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING, |
| | SECTION 1107.1. |
| | B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING, |
| | SECTION 1107.2. |
| | |
| | 2. SHEET A05 SAITARY ISOMETRIC THE FOLLOWING |
| | CORRECTIONS ARE REQUIRED. |
| | |
| | (A) FBC-PLUMBING SECTION *406.3 WASTE CONNECTIONS.THE |
| | TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | (B) FBC-PLUMBING SECTION *802.4 STANDPIPES.STANDPIPES |
| | SHALL BE INDIVIDUALLY TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. |
| | **INDICATE THE REQUIRED STANDPIPE FOR THE WASHING |
| | MACHINE. |
| | |
| | (C) FBC-PLUMBING SECTION *708.3.5 BUILDING DRAIN AND |
| | BUILDING |
| | SEWER JUNCTION. THERE SHALL BE A TWO-WAY |
| | CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. |
| | |
| | (D) FBC-PLUMBING SECTION *708.7 MINIMUM SIZE. |
| | CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM). |
| | **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3". |
| | |
| | (E) FBC-PLUMBING SECTION *708.9 ACCESS. ACCESS SHALL |
| | BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED AT |
| | 4' A.F.F. |
| | |
| | (F) FBC-PLUMBING SECTION *1002.3 (5) PROHIBITED TRAPS. |
| | THE "S" TRAP BEING INDICATED FOR THE SINK IS PROHIBITED |
| | AND A VENT IS REQUIRED FOR THE SINK PER FBC-PLUMBING |
| | SECTION *901.2.1 VENTING REQUIRED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |