| 2008-01-31 14:09:57 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SUBMIT THE LIGHTING PERFORMANCE LEVELS |
| | FOR DINING SPACE/AREA PER 13-415.2 |
| | PLEASE LIST THE FIXTURES BEING USED. |
| | |
| | 2) NOTE: PLEASE INDICATE THE LOCATIONS OF NEW OR |
| | EXISTING EXIT AND EMERGENCY LIGHTING PER NFPA-101 7.8, |
| | 7.9 |
| | |
| | 3) NOTE: PLEASE LIST THE FOLLOWING CODES ON PLANS FOR |
| | ELECTRICAL. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 4) NOTE: PLEASE KNOW ONLY TWO SETS OF SIGNED, SEALED |
| | DATED PLANS ARE NEEDED. PLEASE SEE 5 SETS WERE |
| | SUBMITTED. UP TO THREE SETS SIGNED AND SEALED MAY BE |
| | SUBMITTED FOR REVIEW AND STAMPING IF EXTRA COPY IS |
| | DESIRED BY CONTRACTOR HOWEVER AS STATED ONLY TOW ARE |
| | NEEDED. |
| | THIS IS FOR INFORMATION ONLY AS TWO SETS WERE SIGNED |
| | AND SEALED. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |