Plan Review Notes
Plan Review Notes For Permit 08010603
Permit Number 08010603
Review Stop B
Sequence Number 2
Notes
Date Text
2008-02-14 18:26:59 
  
 DENIED
  
 1)PRODUCT APPROVALS FOR THE PGT SINGLE HUNG WINDOWS
 DO NOT HAVE THE MIAMI-DADE REPORT THAT SHOWS COMPLIANCE
 WITH THE 2004 BUILDING CODE.
  
 PLEASE NOTE THAT IF THE SH 4000 MODEL IS THE NON-IMPACT
 WITH STANDARD MEETING RAIL SEE THAT THE MIN 1/8"
 ANNEALED GLAZING IN THE NOA WILL NOT MEET THE DESIGN
 PRESSURES NEEDED FOR THE "A" SIZE WINDOWS (53.125 X 63)
 IF 1/8" TEMPERED GLASS OR 3/16" ANNEALED IS USED
 PRESSURES WILL MEET THE REQUIRED PRESSURES.
  
 2)VERIFY SWING FOR SUNBURST GLAZED DOOR, DRAWING
 SHOWS OUTSWING AND PRODUCT APPROVALS ARE FOR INSWING
 DOORS ALSO THE DESIGN PRESSURE OF THIS DOOR IS +35/-35
 AND THE PRESSURE IS REQUIRED TO MEET OR EXCEED
 +35.3/-36.7 PER FBC
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716