| Notes |
| Date |
Text |
| 2008-02-14 18:26:59 | | | | | | | DENIED | | | | | | 1)PRODUCT APPROVALS FOR THE PGT SINGLE HUNG WINDOWS | | | DO NOT HAVE THE MIAMI-DADE REPORT THAT SHOWS COMPLIANCE | | | WITH THE 2004 BUILDING CODE. | | | | | | PLEASE NOTE THAT IF THE SH 4000 MODEL IS THE NON-IMPACT | | | WITH STANDARD MEETING RAIL SEE THAT THE MIN 1/8" | | | ANNEALED GLAZING IN THE NOA WILL NOT MEET THE DESIGN | | | PRESSURES NEEDED FOR THE "A" SIZE WINDOWS (53.125 X 63) | | | IF 1/8" TEMPERED GLASS OR 3/16" ANNEALED IS USED | | | PRESSURES WILL MEET THE REQUIRED PRESSURES. | | | | | | 2)VERIFY SWING FOR SUNBURST GLAZED DOOR, DRAWING | | | SHOWS OUTSWING AND PRODUCT APPROVALS ARE FOR INSWING | | | DOORS ALSO THE DESIGN PRESSURE OF THIS DOOR IS +35/-35 | | | AND THE PRESSURE IS REQUIRED TO MEET OR EXCEED | | | +35.3/-36.7 PER FBC | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|