Plan Review Notes
Plan Review Notes For Permit 08010592
Permit Number 08010592
Review Stop P
Sequence Number 1
Notes
Date Text
2008-03-24 15:56:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. PLANS ARE INCOMPLETE AT THIS TIME AND MORE COMMENTS
 MAY BE FORTHCOMING WHEN ALL REQUIRED PLANS ARE
 SUBMITTED. SECTION 106.1.2.
  
 2. SHT G-1.0 THE INDEX OF DRAWING DOES NOT REFLECT THE
 SHEETS SUBMITTED. MANY SHEETS SHOWN ON THE INDEX WERE
 NOT SUBMITTED AND MANY SHEETS SUBMITTED WERE NOT
 INDICATED ON THE INDEX OF DRAWINGS. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 3. ALL ARCHITECTURAL SHEETS. THE SIGNATURE OF THE
 ARCHITECT IS REQUIRED ON EACH SHEET. IT APPEARS THAT
 INITIALS HAVE BEEN USED TO SIGN THE PLANS. IF INDEED
 THIS IS THE ARCHITECTS LEGAL SIGNATURE, THEN A SIGNED,
 SEALED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE
 OF THE ARCHITECT. FAC 61G1-16.003, 61G1-16.004(5) & FS
 481.2055.
  
 4. SHT AN-2.1 MEN'S & WOMEN'S BATHROOM & CHANGING ROOM
 SHALL BE ACCESSIBLE. PLEASE SUBMIT DETAILS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
  
 5. SHT AN-2.1 THE GREASE INTERCEPTORS SHALL BE SIZED BY
 THE UTILITY DEPT. PLEASE CONTACT RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE AT (561) 644-1821, BY FAX
 (561) 822-2287, OR BY E-MAIL [email protected]. A WRITTEN
 DETERMINATION SHALL BE SUBMITTING INDICATING THE
 REQUIRED GREASE INTERCEPTOR SIZE. ARTICLE III SECTION
 90-124(7)(A THRU G).
  
 6. SHT AN-2.1 THE MINIMUM FACILITIES CALCULATIONS ARE
 UNCLEAR. THE FIXTURES FOR THE ASSEMBLY ARE INDICATED ON
 THE FLOOR PLAN. ALSO THE TOILET FACILITIES FOR THE
 MEETING ROOM ARE SHOWN ALL EXCEPT THE DRINKING
 FOUNTAINS, (ONLY 1 SERVICE SINK REQUIRED FOR THE
 BUILDING IF ACCESSIBLE TO ALL RETAIL SPACES). BUT NO
 FIXTURES ARE SHOWN FOR THE TETAIL SPACES. WILL THESE BE
 INDICATED AT THE BUILD-OUT OF THE RETAIL SPACES? ALSO 3
 DRINKING FOUNTAINS ARE REQUIRED BUT ONLY 2 DRINKING
 FOUNTAINS ARE SHOWN. TABLE 403.1.
  
 7. SHT AN-2.1 SHOWS FLAT FLOOR DRAINS AT THE PLAZA ON
 THE WEST SIDE OF THE MAIN LOBBY/DROP OFF AREA BUT NOT
 ON THE LEFT SIDE. PLEASE CLARIFY. ALSO THERE ARE 10
 OTHER FLAT FLOOR DRAINS SHOWN AT THE DRIVE THRU/DROP
 OFF AREA. IF THESE ARE FOR STORM DRAINAGE THEN THE
 CORRECT RECEPTICLE FOR DRAINING THE STORM WATER IS AREA
 DRAINS. SECTION 202.
  
 8. SHT AN-2.3 MANY UNIT TYPES ARE NOT LEGIBLE. THERE IS
 OTHER INFORMATION PRINTED OVER THE TOP OF THE UNIT
 TYPE. SECTION 106.1.1.
  
 9. SHT AN-2.4 MORE INFORMATION IS REQUIRED. WILL THE
 PRIVATE TERRACES FOR UNITS "D" & "F" HAVE STORM
 DRAINAGE? PLEASE CLARIFY. SECTIONS 106.1.2, 1106 &
 1107.
  
 10. SUBMIT CALCULATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS AT EACH DECK, TERRACES, PRIVATE TERRACES, POOL
 DECK AND ROOF ELEVATIONS PER SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS AND TABLES. WHERE REQUIRED SHOW ALL
 SECONDARY DRAINS/SCUPPERS. SHOW THE AREA PLUS 1/2 THE
 VERTICAL WALL CONTRIBUTION INCLUDING PARAPETS AS WELL
 AS ALL ROOF AREAS THAT DRAIN ON TO THE AREA FROM ABOVE
 FOR EACH DRAIN IN THE CALCULATIONS SUBMITTED.
  
 11. SHT AN-8.1 SHOW COMPLIANCE WITH SECTION 1210.2 FOR
 COMMON AREA TOILET ROOMS AND BATHROOMS.
  
 12. SUBMIT RISER DESIGNATION NUMBERS FOR EACH RISER SO
 THEY CAN BE TRACKED THRU THE BUILDING FROM THE
 UNDERGROUND THRU THE VENT THRU ROOF. (EXAMPLES SAN-1,
 SAN-2, SAN-3, RWL-1, RWL-2, RWL-3 ETC.) (SEE CONDENSATE
 RISER DESIGNATION NUMBERS).--RISER #1 AS SHOWN DOES
 NOT RELFECT ALL RISERS DESIGNATED AS RISER #1. RISER #1
 SHOWS KITCHEN SINKS ON THE 2ND THRU 8TH FLOORS (14
 DFU), BUT SOME RISER #1 DO NOT HAVE A KITCHEN SINK ON
 THE 2ND FLOOR AS SHOWN ON THE FLOOR PLAN. THOSE RISER
 #1 CAN BE TYPICAL OF MANY RISERS AND CAN BE INDICATED
 AS RISER #1 TYPICAL OF SAN-1, SAN-5, SAN-7 ETC FOR
 EXAMPLE AS RISERS THAT ARE THE SAME AS RISER #1. FOR
 RISERS THAT ARE DIFFERENT BUT IN THE SAME CATAGORY
 THOSE RISERS CAN BE TYPICAL OF ANOTHER RISER NUMBER.
 EACH TYPICAL RISER SHALL INDICATE THE OFFSETS SHOWN ON
 THE FLOOR PLAN.THIS IS REQUIRED FOR EACH RWL OR STORM
 RISER ALSO.
  
 13. SUBMIT A COMPLETE STORM RISER ISOMETRIC RISER
 DIAGRAM FOR THE BUILDING STORM HORIZONTAL DRAINAGE
 SYSTEM. SHOW ALL PIPE SIZES, RISERS FROM THE BUILDING
 STORM DRAIN THRU TO THE DECK DRAINS, TERRACE DRAINS,
 ROOF DRAINS ETC, CLEANOUTS, OFFSETS & INDICATE SQUARE
 FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. INDICATE THE
 RISERS DESIGNATION NUMBERS FOR EACH RISER TO TRACK
 PIPING THRU THE BUILDING. SECTIONS 106.3.5.1.3, 1101.1,
 1101.8, 1106 & 1107 WITH ALL SUBSECTIOS & TABLES.
  
 14. SUBMIT STORM RISER DIAGRAMS. SHOW ALL PIPE SIZES,
 OFFSETS ETC. AND INDICATE THE RISER DESIGNATION NUMBER
 FOR EACH RISER SO IT CAN BE TRACKED FROM THE STORM
 BUILDING HORIZONTAL DRAIN THRU THE DECK DRAINS,
 TERRACES, ROOF DRAINS ETC. SECTIONS 106.3.5.1.3, 1106,
 & 1107 WITH ALL SUBSECTIONS & TABLES.
  
 15. SUBMIT A COMPLETS SANITARY ISOMETRIC HORIZONTAL
 RISER DIAGRAM FOR THE BUILDING SANITARY DRAIN INCLUDING
 ALL PIPING NOT SHOWN ON VERTICAL RISER DIAGRAMS. SHOW
 ALL PIPE SIZES, CLEANOUTS, TRAPS, VENTS ETC. SECTIONS
 106.3.5.1.3, 701.1, 704, 708, 901 & 1001.1.
  
 16. SUBMIT A COMPLETE CONDENSATE HORIZONTAL ISOMETRIC
 RISER DIAGRAM AND VERTICAL RISER DIAGRAMS IN ISOMETRIC
 FORM. SHOW ALL PIPE SIZES, OFFSETS ETC. SECTION
 106.3.5.1.3.
  
 17. SUBMIT A COMPLETE POTABLE HORIZONTAL WATER
 ISOMETRIC RISER DIAGRAM AND VERTICAL RISER DIAGRAMS
 SHOWING ALL PIPE SIZES, VALVES & WATER HAMMER
 ARRESTORS. SECTIONS 106.3.5.1.3, 601.1, 603, 604, 606,
 607, & 608 WITH ALL SUBSECTIONS AND TABLES.
  
 18. SHT PN-201 AREA DRAIN NEAR COL. LINE 8 BETWEEN
 COLS. N & O SHOWS 4" AD BUT ALSO SHOWS 6" AD(3907SF)
 WITH 4" DOWNSTREAM. PLEASE CLARIFY. TABLE 1106.3. (6"
 PIPE REQD FOR 3907SF @ 1/8"/FT.
  
 19. SHT PN-2.01 CD/18 - CD/19 - CD/20 - CD/21 SHOWS
 1-2/2" CD DRAIN. PLEASE CLARIFY. SECTION 106.1.1.
  
 20. SHT PN-2.01 INFORMATION NEAR COL. LINE 8/I IS NOT
 LEGIBLE. PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.2.
  
 21. SHT PN-2.01 ALL CONDENSATE LINES, RWL LINES & STORM
 LINES ARE SHOWN WITHOUT PIPING. PLEASE INDICATE WHERE
 THESE LINES CONNECT TO THE HORIZONTAL CONDENSATE AND
 STORM DRAINS. SECTIONS 106.1.1, 106.1.2, 1101.1, TABLES
 1106.2, 1106.3.
  
 22. SHT PN-2.01 SHOW THE REQUIRED CLEANOUTS FOR ALL
 SYSTEMS PER SECTIONS 708, & 1101.8.
  
 23. SHT PN-2.02ALL CONDENSATE LINES, RWL LINES &
 STORM LINES ARE SHOWN WITHOUT PIPING. PLEASE INDICATE
 WHERE THESE LINES CONNECT TO THE HORIZONTAL CONDENSATE
 AND STORM DRAINS. SECTIONS 106.1.1, 106.1.2, 1101.1,
 TABLES 1106.2, 1106.3.
  
 24. SHT PN-2.02 INFORMATION BY CONDENSATE RISERS 30,31
 & 33 THRU 35 IS NOT LEGIBLE. SECTION 106.1.1. PLEASE
 CLARIFY.
  
 25. SHT PN-2.02 SHOWS 4" AD BUT ALSO SHOWS 6" AD
 (3707SF) WITH 4" DOWNSTREAM. PLEASE CLARIFY. TABLE
 1106.3. (6" PIPE REQD FOR 3707SF @ 1/8"/FT.
  
 26. SHT PN-2.02 SHOWS 4" FD (955 SF) AT COL. LINE
 14/F.2. IF THIS IS STORM, THE RECEPTICAL SHALL BE
 DESIGNATED AS AN AREA DRAIN OR ROOF DRAIN. SECTION
 202.1.
  
 27. SHT PN-2.02 SHOWS TWO 12" STORM SEWER PIPES AT THE
 CEILING BUT DOES NOT INDICATE THE PIPES CONNECTING TO
 ANY BUILDING STORM DRAIN OR STORM RISERS. PLEASE
 CLARIFY. SECTIONS 106.1.1, 106.1.2 & 1106.
  
 28. SHT PN-2.02 NOTES AT EAST SIDE OF BLDG ARE
 INCOMPLETE. SECTIONS 106.1.1 & 106.1.2. PLEASE SUBMIT
 COMPLETE INFORMATION.
  
 29. SHT PN-2.02 SHOW REQUIRED CLEANOUTS REQUIRED FOR
 THE SANITARY AND STORM SYSTEMS PER SECTIONS 708 &
 1101.8.
  
 30. SHT PN-2.02 SHOWS24" ROUND BY 24" DEEP SUMP PIT
 AND AN 18"X18"X18" SUMP PIT BUT THERE IS NO PIPING
 EXITING THE PITS. PLEASE SHOW THE SUMP DISCHARGE PIPING
 ON THE FLOOR PLAN AND SUBMIT A RISER DIAGRAM FOR THE
 PIPING SHOWING ALL PIPE SIZES, CLEANOUTS. VALVES &
 CHECK VALVES AS WELL AS THE TERMINATION POINT FOR THE
 DISCHARGE LINES. SECTIONS 106.1.2 & 712.
  
 31. SHT PN-2.03 DETAIL #3 PLAN VIEW SHOWS A 6" SAN
 STACK BUT THE RISER DIAGRAM AND THE FLOOR PLAN SHOW A
 4" SAN STACK. PLEASE CORRELATE. SECTION 106.1.1 &
 TABLES 710.1(1) & 710.1(2).
  
 32. SHT PN-2.03 DETAIL #3 RISER ISOMETRIC RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN AT THE DRINKING
 FOUNTAINS. PLEASE CORRELATE. SECTION 106.1.1.
  
 33. SHT PN-2.03 6" RWL OFFSET AT COL. LINE 8/M-N
 INDICATED DOWN AT BOTH ENDS OF THE OFFSET. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 34. SHT PN-2.03 VENT SHOWN IN THE FLOOR BY THE TURNING
 AREA. PLEASE CLARIFY. SECTION 106.1.1.
  
 35. SHT PN-2.04 THE 6" RWL OFFSET AT COL. LINE 11 SHOWS
 DOWN AT BOTH ENDS OF THE OFFSET. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 36. SHT PN-2.04 A RELIEF VENT IS REQUIRED FOR THE 2"
 AAV. SECTION 917.3.2.
  
 37. SHT PN-2.04 COL. LINE 14 INDICATES A 4" FD (955
 SF). IF THE SYSTEM IS FOR STORM WATER, THE RECEPTICAL
 SHALL BE DESIGNATED AS A ROOF DRAIN OR AREA DRAIN.
 SECTION 202.
  
 38. SHT PN-2.05A RELIEF VENT IS REQUIRED FOR THE 3"
 AAV. SECTION 917.3.2.
  
 39. SHT PN-2.05 SHOWS 4" SAN. DOWN FOR RISER 168FU & 6"
 DOWN 424FU ON THE SAME BRANCH/DRAIN LINE. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 40. SHT PN-2.05 SHOWS A TWO INCH VENT AT THE CEILING
 SPACE, BUT DOES NOT WHOW WHERE THE VENT IS LOCATED.
 PLEASE CLARIFY. SECTION 106.1.2.
  
 41. SHT PN-2.05 INDICATES A 4" SAN DOWN FOR RISERS 1 &
 2 AT THE UPPER END OF THE DRAIN LINE. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 42. SHT PN-2.05 INDICATES A 4" SAN DOWN FOR RISERS 2 &
 3 AT THE UPPER END OF THE DRAIN LINE. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 43. SHT PN-2.05 INDICATES A 3" VENT DOWN BY COL. LINE
 4/J-K. VENT TO TERMINATE OUTSIDE OF BUILDING. PLEASE
 CLARIFY. SECTION 903.3.
  
 44. SHT PN-2.06 SHOWS 4" FLOOR DRAIN (955 SF) & 4"
 FLOOR DRAIN (303 SF). IF THE SYSTEM IS FOR STORM WATER,
 THE RECEPTICAL SHALL BE DESIGNATED AS A ROOF DRAIN OR
 AREA DRAIN. SECTION 202.
  
 45. SHT PN-2.06 A RELIEF VENT IS REQUIRED FOR THE 3"
 AAV. SECTION 917.3.2.
  
 46. SHT PN2.06 SHOWS A 3" SD FROM BELOW (294 SF), BUT
 THE RISER SEEMS TO BE AT THE HIGH END OF THE DRAIN
 LINE. PLEASE CLARIFY. SECTION 106.1.1.
  
 47. SHT PN-2.07 INFORMATION SOUTH OF CD RISERS 60 & 61
 NOT LEGIBLE. INDICATE THE LOCATION OF THE STORM DRAINS.
 SECTIONS 106.1.1 & 106.1.2.
  
 48. SHT PN-2.07 A RELIEF VENT IS REQUIRED FOR THE 3"
 AAV. SECTION 917.3.2.
  
 49. SHT PN-2.07 SHOWS A 4" FLOOR DRAIN (900 SF).IF
 THE SYSTEM IS FOR STORM WATER, THE RECEPTICAL SHALL BE
 DESIGNATED AS A ROOF DRAIN OR AREA DRAIN. SECTION 202.
  
 50. SHT PN-2.08 INFORMATION BY CD/48 NOT LEGIBLE.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 51. SHT PN-2.08 SHOWS 4" FLOOR DRAIN (955 SF) & 4"
 FLOOR DRAIN (303 SF). IF THE SYSTEM IS FOR STORM WATER,
 THE RECEPTICAL SHALL BE DESIGNATED AS A ROOF DRAIN OR
 AREA DRAIN. SECTION 202.
  
 52. SHT PN-2.09 INDICATES CD/17A RISER THAT IS NOT
 SHOWN ON THE PREVIOUS LEVELS/ PLEASE CLARIFY. SECTIONS
 106.1.1 & 106.1.2.
  
 53. SHT PN-2.09 NOTE BY COL. LINE 9/P NOT LEGIBLE.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 54. SHT PN-2.10 SHOWS FOUR 4" FLOOR DRAINS, (303 SF)
 (955 SF) (993 SF) (404 SF). IF THE SYSTEM IS FOR STORM
 WATER, THE RECEPTICAL SHALL BE DESIGNATED AS A ROOF
 DRAIN OR AREA DRAIN. SECTION 202.
  
 55. SHT PN-2.10 SANITARY RISER #1 NEAR N.1/K.1 - 15/16
 COL LINE IS INDICATED AS RISER 1B ON THE 2ND FLOOR.
 PLEASE CORRELATE. SECTION 106.1.1 & TABLE 710.1(2).
  
 56. PLUMBING FLOOR PLANS FOR THE 4TH THRU 8 TH FLOORS,
 ROOF PLANS & POOL DECK HAVE NOT BEEN SUBMITTED. PLEASE
 SUBMIT ALL FLOOR PLANS. SECTION 106.1.2.
  
 57. SHT PN-3.0 DETAIL #3 SANITARY RISER #1 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 58. SHT PN-3.2 RISER I2 DOES NOT REFLECT THE FLOOR PLAN
 AT THE LAV. PLEASE CORRELATE. SECTION 106.1.1.
  
 59. SHT PN-3.2 RISER G1 VENT REQUIRED FOR BOTH LAVS.
 SECTION 901.2.1.
  
 60. SHT PN-3.3 DETAIL #3 UNIT M SHOW PIPING TO W/C 2ND
 BATH. SECTION 106.1.2.
  
 61. SHT PN-3.3 RISER K1 DOES NOT REFLECT THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 62. SHT PN-3.4 RISER P6 VENT FOR LAV DOES NOT RELFECT
 THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 63. SHT PN-4.0 RISER FOR UNIT C DETAIL #3 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 64. SHT PN-4.1 RISER FOR UNIT K1 DETAIL 1 DOES NOT
 REFLECT THE FLOOR PLAN AT THE WATER HEATER BETWEEN REF
 & KITCHEN SINK & 3/4" TO W/M ON FLOOR PLAN, 1/2" ON
 RISER. PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 65. SHT PN-4.1 RISER FOR UNIT E DETAIL 2 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS
 106.1.1 & 601.1. (SHOWS 1" PAST LAV IN 2ND BATH).
  
 66. SHT PN-4.2 RISER FOR UNIT I DETAIL 3 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS
 106.1.1 & 601.1. (WATER SUPPLY LINE TO W/H AND OUT OF
 THE W/H).
  
 67. SHT PN-4.4 UNIT P RISER AND FLOOR PLAN. SHOW THE
 PIPE SIZE FOR THE COLD WATER FROM THE UNIT SHUT OFF
 VALVE TO PAST 1ST LAV. (1/2" INDICATED). SECTIONS
 106.1.2 & 601.1.
  
 68. SHT PN-4.4 UNIT O SHOWS 3/4" COLD WATER TO BATHROOM
 ON FLOOR PLAN, BUT INDICATES BOTH 3/4" AND 1/2" COLD
 WATER PAST KITCHEN SINK ON RISER DIAGRAM. PLEASE
 CLARIFY AND CORRELATE. SECTIONS 106.1.1, 106.1.2, 601.1
 & 604.
  
 69. SHT PN-4.5 INDICATES 1/2" HOT WATER TO REF IN UNIT
 T RISER. COLD WATER SUPPLY REQUIRED. SECTIONS 106.1.1 &
 601.1.
  
 70. SHT PN-5.0 UNABLE TO VERIFY SANITARY RISER TO SEE
 IF THEY REFLECT THE FLOOR PLANS AS THE 4TH THRU 8TH
 FLOORS & POOL DECK HAVE NOT BEEN SUBMITTED.SOME
 RISERS ARE NOT TYPICAL. SOME FLOOR PLANS SHOW OFFSETS
 NOT TYPICAL OF OTHER RISERS WITH THE SAME NUMBER. EACH
 RISER SHALL BE INDIVIDUALLY NUMBERED SO THEY CAN BE
 TRACKED THRU THE BUILDING.
  
 71. SHT PN-5.1 RISER DIAGRAM SUBMITTED IS NOT COMPLETE.
 SUBMIT AN ISOMETRIC RISER DIAGRAM THAT REFLECT THE
 COMPLETE SANITARY BUILDING HORIZONTAL DRAIN WITH RISER
 CONNECTIONS THAT REFLECTS THE FLOOR PLAN. SHOW ALL PIPE
 SIZES, TRAPS, VENTS, AND DFU'S AS THEY ACCUMULATE TIN
 THE SYSTEM. SECTIONS 106.3.5.1.2, 701.1 704, 706, 708,
 709, 710 & 711.
  
 72. SHT PN-6.01 NON-POTABLE WATER TREATMENT ISOMETRIC
 RISER DIAGRAM. PLEASE SHOW ALL PIPE SIZES. SUBMIT A
 WATER RISER DIAGRAM FOR THE COMPLETE SYSTEM FROM THE
 PUMP, CHLORINATOR & FILTER AREA TO THE PUBLIC TOILETS,
 AND TO THE POINT OF IRRIGATION CONNECTION. SHOW THE
 LOCATION OF THE PUMP, CHLORINATOR & FILTER AREA ON THE
 FLOOR PLAN AS WELL AS THE PIPING TO THE TOILET ROOMS
 AND FIXTURES AND THE POINT OF CONNECTION FOR THE
 IRRIGATION. SECTIONS 106.1.2 & 601.1.
  
 ***FHA/ACCESSIBILITY NOTES***
  
 73. SHTS AN-2.4, AN-2.3, AN-2.6 & AN-2.7 UNIT TYPE "E"
 SHOW THE W/C ADJACENT TO THE WALL IN ONE BATHROOM. NO
 BACKING DETAIL HAS BEEN SUBMITTED FOR THE W/C NEXT TO A
 WALL ON SHT AN-7.2. PLEASE SUBMIT BACKING DETAIL AS
 INDICATED ON PAGES 6.4 & 6.5.
  
 74. SHT AN-7.2 DETAIL 5 THE OPENING FOR THE WATER
 CLOSET BETWEEN THE LAV AND TUB SHALL SHOW A MINIMUM
 33". (18" - 15"). SEE PAGES 7.43 THRU 7.45.
  
 75. SHT AN-7.2 DETAIL 6 ELEVATION. SHOW THE BOTTOM OF
 THE BACKING FOR THE TUB TO BE 6" MAX OFF THE TUB PER
 PAGE 6.9.
  
 76. SPECIFICATION "A" OR "B" SHALL BE INDICATED FOR
 EACH UNIT AS REQUIRED ON PAGES 7.34 & 7.35. PLEASE
 INDICATE ON PLANS.
  
 77. SHOW THE CLEAR FLOOR SPACE ON THE FLOOR PLANS FOR
 THE WATER CLOSETS IN ALL ACCESSIBLE BATHROOMS. PAGE
 7.43.
  
 78. SHT AN-7.5 DETAILS 2 AND 6 SHOWER CONTROLS LOCATION
 AND HEIGHT NOT INDICATED PER SECTIONS 11-4.21.3 &
 11-4.21.5.--NOTE AT EACH DETAIL STATES, "FOR NUM.
 DIMENSIONS & SPECS. (ADA) SEE SHEET A-7.?. PLEASE
 CLARIFY. SECTIONS 106.1.1 & 106.1.2.
  
 79. SHT AN-7.6 DETAIL #1 WATER CLOSET STALLS SHALL
 COMPLY WITH SECTION 11-4.17.3 & FIG. 11-30E. A LAV IS
 REQUIRED IN THE ACCESSIBLE STALL.--SHOWERS SHALL
 COMPLY WITH SECTION 11-4.21.2 FOR SIZE. PLEASE SHOW
 COMPLIANCE.
  
 80. SHT AN-7.6 PLEASE SHOW COMPLIANCE WITH SECTIONS
 11-5.16, 11-4.19, 11-4.21 & 11-4.22 WITH ALL
 SUBSECTIONS. FOR BATHROOMS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  