| 2008-04-16 18:14:10 | *****DENIED***** |
| | |
| | |
| | 01.THE ADDRESS SHOWN IN THE TITLE BLOCK OF EACH PLAN |
| | SHEET OF 505 4TH STREET DOES NOT CORRELATE WITH THE |
| | ADDRESS OF 510 4TH STREET WHICH REGISTERS IN THE |
| | COMMUNITY PLUS SYSTEM.VERIFY/CONFIRM/AMEND WITH A |
| | PERMIT SPECIALIST TO MAKE SURE THE CORRECT PROJECT SITE |
| | ADDRESS IS APPLIED. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER |
| | EMERGENCY RESPONSE ACCESS TO THE SURROUNDING PROPERTIES |
| | OR VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE |
| | LANES) . |
| | |
| | 04.STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION. |
| | |
| | 05.ALL CUTTING AND WELDING OPERATIONS SHALL COMPLY |
| | WITH NFPA 51B. |
| | |
| | 06. TEMPORARY STANDPIPE SYSTEM REQUIRED WHEN THE |
| | BUILDING REACHES THREE STORIES OR THIRTY FEET IN |
| | HEIGHT. |
| | |
| | 07.ON SHEET G-1.3, THEREARE SEVERAL REFERENCES TO |
| | THE CITY OF MIAMI;PLEASE BE ADVISED THAT THE |
| | AUTHORITY HAVING JURISDICTION (AHJ) IS THE CITY OF WEST |
| | PALM BEACH. |
| | |
| | 08.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| | 4TH STREET, DISPLAY/SHOW THE ACTUAL NUMERICAL ADDRESS |
| | ON THE BUILDING.AS PER WEST PALM BEACH CODE, NUMBERS |
| | SHALL BE A MINUMUM OF 6" IN HEIGHT AND A MINUMUM OF 1" |
| | IN WIDTH. |
| | |
| | 09.KNOX-BOXES WILL BE REQUIRED FOR THE BUILDING. SHOW |
| | THE LOCATION OF THE KNOX BOX.FOR AN APPLICATION, |
| | CONTACT WEST PALM BEACH FIRE PREVENTION AT |
| | 561-804-4724. |
| | |
| | 10.STAIRWELL IDENTIFICATION SIGNS ARE REQUIRED |
| | IDENTIFYING FLOOR LEVEL, STAIR IDENTITY, AND TERMINUS |
| | TOP AND BOTTOM. |
| | |
| | 11.ELEVATOR WARNING SIGNS " IN CASE OF FIRE, DO NOT |
| | USE THE ELEVATORS "ARE REQUIRED. |
| | |
| | 12.ALL TRASH CHUTES ARE TO COMPLY WITH NFPA 82. |
| | |
| | 13.FIRE DOORS AND FIRE WINDOWS ARE TO COMPLY WITH |
| | NFPA 80. |
| | |
| | 14.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE |
| | EXITS, EXIT ACCESS CORRIDORS, AND OTHER AREAS IN TERMS |
| | OF CLASS A, CLASS B, OR CLASS C.LIKEWISE, SPECIFY THE |
| | INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II |
| | FOR THESE AREAS. |
| | |
| | 15.ON SHEET LSN-1.1, THE FIRE EXTINGUISHER IN THE |
| | RESIDENT BICYCLE STORAGE AREA APPEARS TO BE LOCATED IN |
| | THE BIKE RACKS.(SEE APPROXIMATE AREA C-4) |
| | |
| | 16.ON SHEET LSN-1.2 AND LSN-1.3, THE PATH OF EGRESS |
| | (TRAVEL DISTANCE ROUTE) IS SHOWN TO PASS THROUGH A |
| | VEHICLE PARKING STALL. THE PATH OF TRAVEL SHALL NOT BE |
| | THROUGH AN OBSTRUCTION OR POSSIBLE OBSTRUCTION. |
| | |
| | 17.ON PLAN SHEETS EN-2.3 THRU EN-2.7, LIST THE UNIT |
| | TYPE SO THAT THE PLANS EXAMINER AND/OR FIELD INSPECTOR |
| | CAN IDENTIFY WHICH LAYOUTIS BEING REFERENCED ON |
| | EN-3.0 THRU EN-3.6 SHEETS. |
| | |
| | 18.ON SHEET EN2.7, WORDING IN THE NOTE NOT CLEAR. |
| | (SEE APPROXIMATE AREA C.5 / 3.5) |
| | |
| | 19.SMOKE DETECTORS (SD) ARE SHOWN IN THE RESIDENTIAL |
| | UNITS ON SHEETS EN-3.0 THRU EN-3.6;AMEND THESE DEVICE |
| | TO SMOKE ALARMS (SA).PLEASE BE ADVISED THAT SD'S ARE |
| | TIED INTO THE BUILDING'S FIRE ALARM SYSTEM WHEREAS SA'S |
| | ALERT THE OCCUPANT(S) OF THE DWELLING UNIT ONLY. |
| | |
| | 20.CORRELATE THE INFORMATION IN THE INDEX OF DRAWING. |
| | SHEET G1.0 LISTS LSN-1.5 AS LIFE SAFETY PLAN (4TH TO |
| | 6TH LEVEL) ;WHEREAS IT IS TITLED ON SHEET LSN-1.5 AS |
| | LIFE SAFETY PLAN (3 - 6 LEVEL) . |
| | |
| | 21.COULD NOT FIND SHEET LSN-1.8 AND LSN-1.9 AS |
| | INDICATED IN THE INDEX OF DRAWING (SHEET G1.0) . |
| | |
| | 22.IN THE SEQUENCE OF OPERATIONS FOR THE FIRE ALARM |
| | SYSTEM (SHEET FAN-1.0) , AMEND TO SHOW AS PER LOCAL |
| | CODES THAT "DUCT SMOKE DETECTORS SHALL INITIATE A |
| | GENERAL FIRE ALARM" . |
| | |
| | 23.FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL |
| | LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION |
| | SERVICE. |
| | |
| | 24.ARE HEAT DETECTORS SLATED FOR THE KITCHEN AREA IN |
| | THE DWELLING UNITS? |
| | |
| | 25.SHEET FAN-2.7 IS INCORRECTLY TITLED AS ELECTRICAL |
| | PLAN (8TH FLOOR);SHOULD BE FIRE ALARM PLAN (8TH |
| | FLOOR) AS INDICATED IN THE INDEX OF DRAWINGS (SHEET |
| | G-1.0) . |
| | |
| | 26.THE INDEX OF DRAWINGS (SHEET G-1.0) LISTS FAN-2.8 |
| | AS FIRE ALARM PLAN (3RD FLOOR) WHEREAS THE SHEET ITSELF |
| | IS TITLED AS FIRE ALARM PLAN (ROOF LEVEL) . |
| | |
| | 27.CORRELATE SHEET FAN-2.9 IN THE INDEX OF DRAWING |
| | WITH THE INFORMATION ON THE ACTUAL SHEET. |
| | |
| | 28.ELECTRONIC SWITCHES, CHAIN AND LOCK REQUIRED ON |
| | FIRE LINE BACKFLOW DEVICE. |
| | |
| | 29.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR |
| | BOTH THE FIRE ALARM AND THE FIRE SPRINKLER SYSTEMS AND |
| | ANY ACCESS CONTROL SYSTEMS. |
| | |
| | 30.NFPA 13 - 2002 EDITION - SHALL BE REFERENCED FOR |
| | THE INSTALLATION OF THE BUILDING'S FIRE SPRINKLER |
| | SYSTEM.IT WAS INDICATED IN ONE OF THE PLAN SHEET THAT |
| | NFPA 13R WOULD BE REFERENCED;PLEASE BE ADVISED THAT |
| | NFPA 13R IS THE STANDARD FOR THE INSTALLATION OF |
| | SPRINKLER SYSTEM IN RESIDENTIAL OCCUPANCIES UP TO AND |
| | INCLUDING 4 STORIES IN HEIGHT. |
| | |
| | 31.ON SHEET FPN-0.0, AMEND NOTE #14 THAT "WATER FLOW |
| | DEVICES SHALL INITIATE A GENERAL FIRE ALARM. |
| | |
| | 32.FIRE SPRINKLER SYSTEM WILL BE MONITORED. |
| | |
| | 33.EXPLAIN TERMINOLOGY (AND PURPOSE) OF FLOOR CONTROL |
| | RIG (FCR);FCR IS NOT SHOWN IN THE ABBREVIATIONS SND |
| | SYMBOLS LEGEND ON THE FPN-0.0 SHEET. |
| | |
| | 34.KNOX LOCKING CAPS REQUIRED FOR THE FIRE DEPARTMENT |
| | CONNECTIONS (FDC).CONTACT WEST PALM BEACH FIRE |
| | PREVENTION AT 561-804-4724 FOR AN APPLICATION. |
| | |
| | 35.ON PLAN SHEETS FPN-2.3 THRU FPN-2.7, LIST THE UNIT |
| | TYPE SO THAT THE PLAN REVIEWER AND/OR FIELD INSPECTOR |
| | CAN IDENTIFY WHICH FIRE SPRINKLER LAYOUT IS BEING |
| | REFERENCED ON FPN-3.00 THRU FPN-3.02 SHEETS. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET |
| | EACH ITEM WAS ADDRESSED |
| | |
| | |