2008-04-16 18:14:10*****DENIED*****
  
  
 01.THE ADDRESS SHOWN IN THE TITLE BLOCK OF EACH PLAN
 SHEET OF 505 4TH STREET DOES NOT CORRELATE WITH THE
 ADDRESS OF 510 4TH STREET WHICH REGISTERS IN THE
 COMMUNITY PLUS SYSTEM.VERIFY/CONFIRM/AMEND WITH A
 PERMIT SPECIALIST TO MAKE SURE THE CORRECT PROJECT SITE
 ADDRESS IS APPLIED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SURROUNDING PROPERTIES
 OR VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES) .
  
 04.STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
  
 05.ALL CUTTING AND WELDING OPERATIONS SHALL COMPLY
 WITH NFPA 51B.
  
 06. TEMPORARY STANDPIPE SYSTEM REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 07.ON SHEET G-1.3, THEREARE SEVERAL REFERENCES TO
 THE CITY OF MIAMI;PLEASE BE ADVISED THAT THE
 AUTHORITY HAVING JURISDICTION (AHJ) IS THE CITY OF WEST
 PALM BEACH.
  
 08.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 4TH STREET, DISPLAY/SHOW THE ACTUAL NUMERICAL ADDRESS
 ON THE BUILDING.AS PER WEST PALM BEACH CODE, NUMBERS
 SHALL BE A MINUMUM OF 6" IN HEIGHT AND A MINUMUM OF 1"
 IN WIDTH.
  
 09.KNOX-BOXES WILL BE REQUIRED FOR THE BUILDING. SHOW
 THE LOCATION OF THE KNOX BOX.FOR AN APPLICATION,
 CONTACT WEST PALM BEACH FIRE PREVENTION AT
 561-804-4724.
  
 10.STAIRWELL IDENTIFICATION SIGNS ARE REQUIRED
 IDENTIFYING FLOOR LEVEL, STAIR IDENTITY, AND TERMINUS
 TOP AND BOTTOM.
  
 11.ELEVATOR WARNING SIGNS " IN CASE OF FIRE, DO NOT
 USE THE ELEVATORS "ARE REQUIRED.
  
 12.ALL TRASH CHUTES ARE TO COMPLY WITH NFPA 82.
  
 13.FIRE DOORS AND FIRE WINDOWS ARE TO COMPLY WITH
 NFPA 80.
  
 14.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE
 EXITS, EXIT ACCESS CORRIDORS, AND OTHER AREAS IN TERMS
 OF CLASS A, CLASS B, OR CLASS C.LIKEWISE, SPECIFY THE
 INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II
 FOR THESE AREAS.
  
 15.ON SHEET LSN-1.1, THE FIRE EXTINGUISHER IN THE
 RESIDENT BICYCLE STORAGE AREA APPEARS TO BE LOCATED IN
 THE BIKE RACKS.(SEE APPROXIMATE AREA C-4)
  
 16.ON SHEET LSN-1.2 AND LSN-1.3, THE PATH OF EGRESS
 (TRAVEL DISTANCE ROUTE) IS SHOWN TO PASS THROUGH A
 VEHICLE PARKING STALL. THE PATH OF TRAVEL SHALL NOT BE
 THROUGH AN OBSTRUCTION OR POSSIBLE OBSTRUCTION.
  
 17.ON PLAN SHEETS EN-2.3 THRU EN-2.7, LIST THE UNIT
 TYPE SO THAT THE PLANS EXAMINER AND/OR FIELD INSPECTOR
 CAN IDENTIFY WHICH LAYOUTIS BEING REFERENCED ON
 EN-3.0 THRU EN-3.6 SHEETS.
  
 18.ON SHEET EN2.7, WORDING IN THE NOTE NOT CLEAR.
 (SEE APPROXIMATE AREA C.5 / 3.5)
  
 19.SMOKE DETECTORS (SD) ARE SHOWN IN THE RESIDENTIAL
 UNITS ON SHEETS EN-3.0 THRU EN-3.6;AMEND THESE DEVICE
 TO SMOKE ALARMS (SA).PLEASE BE ADVISED THAT SD'S ARE
 TIED INTO THE BUILDING'S FIRE ALARM SYSTEM WHEREAS SA'S
 ALERT THE OCCUPANT(S) OF THE DWELLING UNIT ONLY.
  
 20.CORRELATE THE INFORMATION IN THE INDEX OF DRAWING.
 SHEET G1.0 LISTS LSN-1.5 AS LIFE SAFETY PLAN (4TH TO
 6TH LEVEL) ;WHEREAS IT IS TITLED ON SHEET LSN-1.5 AS
 LIFE SAFETY PLAN (3 - 6 LEVEL) .
  
 21.COULD NOT FIND SHEET LSN-1.8 AND LSN-1.9 AS
 INDICATED IN THE INDEX OF DRAWING (SHEET G1.0) .
  
 22.IN THE SEQUENCE OF OPERATIONS FOR THE FIRE ALARM
 SYSTEM (SHEET FAN-1.0) , AMEND TO SHOW AS PER LOCAL
 CODES THAT "DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM" .
  
 23.FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL
 LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 24.ARE HEAT DETECTORS SLATED FOR THE KITCHEN AREA IN
 THE DWELLING UNITS?
  
 25.SHEET FAN-2.7 IS INCORRECTLY TITLED AS ELECTRICAL
 PLAN (8TH FLOOR);SHOULD BE FIRE ALARM PLAN (8TH
 FLOOR) AS INDICATED IN THE INDEX OF DRAWINGS (SHEET
 G-1.0) .
  
 26.THE INDEX OF DRAWINGS (SHEET G-1.0) LISTS FAN-2.8
 AS FIRE ALARM PLAN (3RD FLOOR) WHEREAS THE SHEET ITSELF
 IS TITLED AS FIRE ALARM PLAN (ROOF LEVEL) .
  
 27.CORRELATE SHEET FAN-2.9 IN THE INDEX OF DRAWING
 WITH THE INFORMATION ON THE ACTUAL SHEET.
  
 28.ELECTRONIC SWITCHES, CHAIN AND LOCK REQUIRED ON
 FIRE LINE BACKFLOW DEVICE.
  
 29.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR
 BOTH THE FIRE ALARM AND THE FIRE SPRINKLER SYSTEMS AND
 ANY ACCESS CONTROL SYSTEMS.
  
 30.NFPA 13 - 2002 EDITION - SHALL BE REFERENCED FOR
 THE INSTALLATION OF THE BUILDING'S FIRE SPRINKLER
 SYSTEM.IT WAS INDICATED IN ONE OF THE PLAN SHEET THAT
 NFPA 13R WOULD BE REFERENCED;PLEASE BE ADVISED THAT
 NFPA 13R IS THE STANDARD FOR THE INSTALLATION OF
 SPRINKLER SYSTEM IN RESIDENTIAL OCCUPANCIES UP TO AND
 INCLUDING 4 STORIES IN HEIGHT.
  
 31.ON SHEET FPN-0.0, AMEND NOTE #14 THAT "WATER FLOW
 DEVICES SHALL INITIATE A GENERAL FIRE ALARM.
  
 32.FIRE SPRINKLER SYSTEM WILL BE MONITORED.
  
 33.EXPLAIN TERMINOLOGY (AND PURPOSE) OF FLOOR CONTROL
 RIG (FCR);FCR IS NOT SHOWN IN THE ABBREVIATIONS SND
 SYMBOLS LEGEND ON THE FPN-0.0 SHEET.
  
 34.KNOX LOCKING CAPS REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTIONS (FDC).CONTACT WEST PALM BEACH FIRE
 PREVENTION AT 561-804-4724 FOR AN APPLICATION.
  
 35.ON PLAN SHEETS FPN-2.3 THRU FPN-2.7, LIST THE UNIT
 TYPE SO THAT THE PLAN REVIEWER AND/OR FIELD INSPECTOR
 CAN IDENTIFY WHICH FIRE SPRINKLER LAYOUT IS BEING
 REFERENCED ON FPN-3.00 THRU FPN-3.02 SHEETS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW