Plan Review Notes
Plan Review Notes For Permit 08010592
Permit Number 08010592
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-16 11:56:05NOTE ADDED:
  
 PLEASE SEE UNITS WHICH CONTAIN A NOTE FOR AN EF-2 YET
 THE PLANS DO NOT SHOW ANY EF-IN UNITS.
2008-02-14 19:17:572008-02-14 19:17:57
  
 *** DENIED***
  
 CANNES WEST PALM
  
 1) NOTE: PLEASE KNOW THIS PROJECT WAS ONLY SUBMITTED
 FOR PLAN REVIEW AND NOT FOR PERMIT. ONCE ALL REVIEW
 COMMENTS ARE ADDRESSED PLANS WILL STILL REMAIN IN *F*
 STATUS UNTIL PERMIT HAS BEEN APPLIED FOR.
 ONCE PERMIT IS APPLIED FOR, REVIEW FOR ITEMS SUCH AS
 LICENSING ETC WILL BE DONE AT THAT TIME.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON BOTH THE ELECTRICAL AS WELL AS THE
 ARCHITECTURAL COVER SHEETS. SOME OF THE FOLLOWING MAY
 ALREADY BE PRESENT HOWEVER SOME ARE NOT AT THIS TIME.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA72
 2002 NFPA-110
 2003 NFPA-20
  
 ** SOME OF THESE ARE ALREADY SHOWN BUT NOT ALL AND NOT
 ON ELECTRICAL PLANS.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ARE NOT THE EDITION ADOPTED BY THE FBC 13-400.3.A.
 PLEASE SEE THE CALCULATIONS SUBMITTED DO NOT COMPLY
 WITH THE FBC. MOST IMPORTANTLY THE ELECTRICAL LIGHTING
 ON PLANS DOES NOT CORRELATE THE CALCULATIONS. FOR THE
 REMAINDER OF THIS COMMENT THE INPUT DATA REPORT WILL BE
 NOTED AT IDR.
  
 A) ** PLEASE SEE THE LIGHTING FOR INTERIOR LIGHTING ON
 PLANS DOES NOT COORDINATE WITH THE IDR FOR THE NUMBER
 OF FIXTURES, THE TYPES OF FIXTURES OR THE WATTAGES OF
 FIXTURES. FOR EXAMPLE: THE IDR FOR INTERIOR SHOWS A
 TOTAL OF 8 LIGHT FIXTURES ON THE INTERIOR OF THE
 BUILDING. HOW IS THIS POSSIBLE WHEN THE PLANS SHOWS
 HUNDREDS AND HUNDREDS OF LIGHTS??
  
 B) ** PLEASE SEE THE IDR FOR EXTERIOR LIGHTING
 INFORMATION. THE IDR SHOWS ABSOLUTELY NO EXTERIOR
 LIGHTING FIGURED INTO THE CALCULATIONS. HOW IS THIS
 POSSIBLE WHEN THE PLANS SHOWS ONCE AGAIN HUNDREDS OF
 FIXTURES.
  
 THIS OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEAS BE SURE
 THAT ALL LIGHTING ON PLANS COORDINATES WITH THE
 LIGHTING IN THE IDR SUBMITTED.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, 13-415.2.ABC.1.3
 ETC 13-415.1.A, 13-400.3.A ETC.
 PLEASE SEE METHOD SUBMITTED IS CURRENTLY IN QUESTION AS
 THE BUILDING CONTAINS *SHELL* PORTIONS WHICH ARE NOT
 KNOWN AT THIS TIME.
 PLEASE SEE 13-400.2.A.2 AS METHOD *A* MAY ONLY BE USED
 ONCE ALL ITEMS BEING INSTALLED ARE COMPLETED AND KNOWN.
 IF THERE ARE ITEMS NOT KNOWN BEING FUTURE, THEN THE
 ONLY OTHER CHOICE WOULD BE METHOD *B* FOR WHICH SECTION
 13-415.1.B, 13-400.3.B APPLIES.
 PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY ALSO
 TOUCH ON THIS SAME TOPIC.
  
 4) NOTE: PLEASE SUBMIT COMPLETE LIGHTING PLANS WITH
 MINIMUM REQUIRED CONTROLS FOR FBCCHAPTER 13,
 13-415.1.ABC.1.1, .1.2 , .1.3 AND .1.4.
 PLEASE KNOW BASED ON PLANS WHICH ONLY SHOW STANDARD
 SWITCHES WHICH ARE WHAT THE SYMBOL LEGEND STATES AND
 SHOWS NO LIGHTING CONTROLS WHICH ARE REQUIRED ARE IN
 THE DESIGN FOR THE BUILDING AT THIS TIME.
 PLEASE SEE PLANS DO CONTAIN A NOTE FOR SOME KIND OF
 J-BOX IN STAIR WAYS FOR LIGHTING CONTROLS HOWEVER NO
 SYSTEM OR PROPOSED ITEMS FOR DESIGN COULD BE LOCATED.
 PLEASE BE SURE TO SEE NOT ONLY CHAPTER 10 OF THE FBC
 FOR OCCUPANCY SENSING DEVICES PERMITTED ON EMERGENCY
 EGRESS LIGHTS BUT NFPA-101 7.8.1.2.2 AUTOMATIC, MOTION
 SENSOR'"TYPE LIGHTING SWITCHES SHALL BE PERMITTED
 WITHIN THE MEANS OF EGRESS, PROVIDED THAT THE SWITCH
 CONTROLLERS ARE EQUIPPED FOR FAIL-SAFE OPERATION, THE
 ILLUMINATION TIMERS ARE SET FOR A MINIMUM 15-MINUTE
 DURATION, AND THE MOTION SENSOR IS ACTIVATED BY ANY
 OCCUPANT MOVEMENT IN THE AREA SERVED BY THE LIGHTING
 UNITS. PLEASE SEE NOTES BELOW WHICH WILL AFFECT EGRESS
 LIGHTING AS SHOWN.(FAIL SAFE ON)
 PLEASE KNOW AS THERE IS MUCH INFORMATION NOT SUBMITTED
 OR PART OF THE DESIGN, THERE MAY VERY WELL BE NEW
 COMMENTS ONCE PLANS ARE RESUBMITTED FOR THE NEXT
 REVIEW.
  
 5) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS SHOWS
 505 4TH STREET WHEN THE APPLIED LOCATIONS IS 510 4TH
 STREET. PLEASE BE SURE EACH BUILDING SET OF PLANS FOR
 EACH SEPARATE PERMIT CONTAINS THE CORRECT ADDRESS ON
 TITLE BLOCKS.
 FBC 106.5 ADMIN SECTION.
 FAC 61G1-16.004, FAC 61G15-23.002
  
 6) NOTE: PLEASE SEE HOUSE BILL 7121 FOR REQUIRED
 ON-SITE FUEL FOR BACK UP OF A GENERATOR IN A
 RESIDENTIAL HIGH-RISE BUILDING.
 PLEASE KNOW THAT BESIDES THE REQUIRED ITEMS PER NEW
 STATE STATUTES, PLEASE BE AWARE THAT IF THE BUILDING IS
 GOING TO BE OCCUPIED UNDER THE POWER OF THE GENERATOR
 ONLY, OTHER SYSTEMS SUCH AS VENTILATION ETC WILL NEED
 TO BE PART OF THE DESIGN OF FUEL CONSUMPTION ALONG WITH
 ALL OTHER LIFE SAFETY SYSTEMS.
 THIS WILL NEED TO BE GONE OVER ON THE PHONE OR IN
 PERSON TO CLARIFY WHAT IS REALLY NEEDED.
  
 7) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FOLLOWING ITEMS. THE GENERATOR, FUEL
 TANK(S), FIRE PUMP, FIRE PUMP CONTROLLER AND BOTH MTS
 AND ATS DEVICES.
 THERE ARE SEVERAL ITEMS WHICH COULD NOT BE REVIEWED FOR
 CODE COMPLIANCE AT THIS TIME.
 NEC 90.7, 110.3, NFPA-20, NFPA-110 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 8) NOTE: PLEASE SEE THE GENERATOR AS SHOWN ON PLANS
 DOES INDICATE THE PRIME-MOVER OR FUEL SOURCE? PLEASE
 SEE NFPA-110, NFPA-70
 THERE ARE TOO MANY CODE SECTIONS TO LIST FOR REQUIRED
 ITEMS.
 PLEASE SEE NFPA-110 FOR LOCATION OF THE REQUIRED
 GENERATOR.
 PLEASE SEE THAT ALL ITEMS SHALL MEET ALL CHAPTERS
 HOWEVER MORE SPECIFIC PER THIS REVIEW CHAPTER 7. PLEASE
 SEE VENTILATION, LIGHTING LEVELS, LOCATION OF EQUIPMENT
 ETC.
 MAY NOT TAKE THE VENTILATION FROM ADJACENT ROOMS, MUST
 COME DIRECTLY FROM OUTSIDE.
 PLEASE KNOW THERE ARE TOO MANY CODE SECTIONS TO NOTE AT
 THIS TIME.7.1, 7.2, 7.3, 7.4, 7.5 ETC
 PLEASE SEE THAT THE MINIMUM LIGHTING LEVELS SHALL MEET
 30FT CANDLES. THIS WILL BE NOTED IN NOTE BELOW FOR
 PHOTO-METRICS LEVELS.
 PLEASE SEE 700.12B (1), (3), 701.11B(1),(3) , ETC
  
 9) NOTE: PLEASE SEE SOME A-SHEETS WHICH CONTAIN HAND
 DRAWN ITEMS WHICH CAN NOT BE MADE TO SIGNED AND SEALED
 PLANS.
 FS 481.221, 471.023
 THIS COMMENT IS NOTED FOR ALL PLANS AND FOR ALL
 REVIEWS.
  
 10) NOTE: PLEASE SEE MISSING RATED SEPARATION WHICH
 WILL BE A PART OF BUILDING SEPARATION. PLEASE ALSO KNOW
 THE ELECTRICAL SYSTEMS ON EACH SIDE OF THIS PROPOSED
 WALL AND FIRE RATED DOORS SHALL BE SEPARATED. PLEASE
 SEE THE LOCATION OF THE MAIN ELECTRICAL ROOM AS SHOWN
 IS NOT ACCEPTABLE TO THIS AHJ. THIS CREATES A MAJOR
 LIFE SAFETY HAZARD. EMERGENCY PERSONNEL DO NOT HAVE
 DIRECT AND IMMEDIATE ACCESS TO THE MAIN ELECTRICAL
 ROOM. THE LOCATION SHALL BE AT A NEAREST POINT OF
 ENTRANCE INTO THE BUILDING. . THE LOCATION WILL NEED TO
 BE DETERMINED BEFORE RESUBMITTED PLANS. SOME ITEMS WERE
 ALREADY GONE OVER WITH THE ELECTRICAL ENGINEER AFTER
 PLANS WERE SUBMITTED.
 230.2, 230.70, 230.71, 230.72 ETC
  
 11) NOTE: PLEASE SEE NEC 230.2 AND NFPA-110 FOR THE
 ACCEPTABLE LOCATION OF EPSS EQUIPMENT.
 PLEASE SEE NFPA-1107.2.2, 7.1.5, 7.2.1 ETC WHICH DOES
 NOT PERMIT THIS EQUIPMENT IN THE SAME ROOM AS THE
 NORMAL ELECTRICAL EQUIPMENT. PLEASE SEE 7.2.2.1 WHICH
 DOES ALLOW THE ATS/ TRANSFER EQUIPMENT IN THE SAME ROOM
 AS LONG AS TWICE THE DISTANCES FROM OTHER EQUIPMENT PER
 110.26 IS PROVIDED. PLEASE SEE THE NEC WHICH STATES
 THIS EQUIPMENT SHALL BE SUFFICIENTLY REMOTE.NFPA-70
 DOES NOT GIVE A DEFINITION FOR WHAT SUFFICIENTLY REMOTE
 IS HOWEVER NFPA-110 DOES PROVIDEDEFINITION OF LEVEL 1
 OR LEVEL 2 SYSTEMS NOT TO BE LOCATE WITH IN THE SAME
 ROOM.
 PLEASE RE-LOCATE.
  
 12) NOTE: PLEASE SEE MISSING INFORMATION FOR THE FIRE
 PUMP. PLEASE SEE NFPA-20CHAPTERS AND NFPA-70. MORE
 SPECIFIC PLEASE SEE CHAPTERS 9 AND 10 OF NFPA-20 AND
 NEC 695 FOR FIRE PUMPS.
 COULD NOT LOCATE INFORMATION ON REQUIRED LOCKED ROTOR
 CURRENT SETTINGS WHICH NEEDS TO BE SHOWN ON PLANS.
 COULD NOT LOCATE INFORMATION ON ISOLATION SWITCH(S),
 BY-PASS, ETC
 COULD NOT LOCATE THE MINIMUM REQUIRE ON-SITE FUEL FOR A
 MINIMUM OF 8HRS OF RUN TIME AT 100%. PLEASE BE SURE TO
 SEE NOTES ABOVE WITH RESPECT TO THE ALLOWANCE FOR HOUSE
 BILL 7121. IF BUILDING IS UNDER OCCUPANCY FOR THE
 PERIOD AS SPECIFIED THEN PLEASE SEE THAT THE FIRE PUMP
 SHALL HAVE THE REMAINDER OF ON-SITE FUEL FOR ANY GIVEN
 TIME DURING OCCUPANCY.
  
 13) NOTE: PLEASE SEE NFPA-1107.1.5 AND NFPA-70
 CHAPTERS 700 AND 701 WHICH DOES PERMIT OPTIONAL
 STAND-BY EQUIPMENT BEING FED FROM THE GENERATOR WHICH
 ALSO FEEDS LIFE SAFETY AND LEGALLY REQUIRED LOADS
 HOWEVER NO PROVISIONS FOR LOAD SHEDDING WAS INDICATED
 ON PLANS.
 PLEASE KNOW AT THIS TIME BASED ON THE PLANS, AND OTHER
 REQUIRED SYSTEMS THE GENERATOR IS NOT OF SUFFICIENT
 SIZE FOR ALL REQUIRED SYSTEMS.
 PLEASE ALSO PROVIDE LOAD SHEDDING DETAIL FOR THE UNITS
 MTS PANELS WHICH ARE FED FROM EU-2.
 PLEASE KNOW AS THERE ARE SEVERAL CHANGES NEEDED MANY
 ITEMS CAN NOT BE REVIEWED AT THIS TIME.
  
 14) NOTE: PLEASE SEE GENERATOR ROOM WALL DETAIL ON
 EN-6.0 DOES NOT COORDINATE WITH OTHER SHEERS IN PLANS.
 FBC 106.1.2 FOR COORDINATION.
  
 15) NOTE: PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE SEE FOR EXAMPLE: EN-2.0 ,
 2.1 ETC WHICH SHOW AREAS/ROOMS HOWEVER DO NOT INDICATE
 ANY DESIGNATIONS.
 THIS IS FOR MANY LOCATIONS ON PLANS HOWEVER NOT ALL ARE
 LISTED.
 PLEASE ALSO BE SURE TO COMPLETE THE SAME FOR UNITS.
 SOME OF THE UNITS IN THE BEGINNING OF UNIT PLANS DO
 INDICATE DESIGNATIONS HOWEVER AS THE UNIT SHEETS GO ON
 THE AREAS AND ROOMS WERE NOT ON SHEETS.
 PLEASE KNOW THAT ARE CODE SECTIONS WHICH APPLY TO UNITS
 WHICH CAN NOT BE CONFIRMED AT THIS TIME SUCH AS
 210.52B1 FOR CIRCUITING OF ITEMS IN DINING AREAS.
 (COMMENTED BELOW).
  
 16) NOTE: PLEASE SEE FAIR HOUSING ACT REGULATIONS 24
 CFR, 100.205 AND FBC CHAPTER 11 FOR REQUIRED HEIGHTS
 AND LOCATIONS FOR DEVICES.
 PLEASE LIST ON PLANS.
  
 17) NOTE: PLEASE BE SURE TO PROVIDE ANY INFORMATION FOR
 ANY ACCESS CONTROL SYSTEMS SUCH AS PARKING GARAGE GATE
 OPERATORS AND BATTERY BACK UP.
 PLEASE ALSO PROVIDE INFORMATION ON ANY ACCESS CONTROLS
 OF INGRESS OR EGRESS DOORS. PLEASE SEE NFPA-101 7.5.1,
 7.5.2, 7.5.4. AT THIS TIME THERE IS NOT ENOUGH
 INFORMATION SHOWN.
 NO DEVICES ARE TO BE INSTALLED WHICH IN THE EVENT OF
 ANY EMERGENCY OR NON EMERGENCY WILL IMPEDE THE EGRESS
 OF OCCUPANTS OR FIRE DEPARTMENT PERSONNEL IN ANY WAY.
 PLEASE BE AWARE OF ANY POSSIBLE COMMENTS FROM FIRE
 MARSHAL.
  
 18) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS UNDER NORMAL AND EMERGENCY CONDITIONS.
 THIS IS INCLUSIVE OF STAIR WAYS ETC.
 PLEASE SEE NFPA-101 7.8.1.3 AND 7.9.2.2 WHICH REQUIRES
 A MINIMUM OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED
 DOWN TO 1FT CANDLE UNDER EMERGENCY.
  
 19) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR THE GENERATOR
 ROOM AS NFPA-110 7.3.3 REQUIRES 30FT CANDLES MINIMUM.
  
 20) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR ELEVATOR PITS
 FOR THE MINIMUM OF 5FT CANDLES REQUIRED PER ASME
 A17.1-2004, SAFETY CODE FOR ELEVATORS AND ESCALATORS.
 LEVELS ARE AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO
 BE EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.
  
 21) NOTE: PLEASE KNOW THAT BATTERY BACK UP LIGHTING
 FIXTURES WILL BE REQUIRED FOR ALL EGRESS PATHS
 INCLUDING STAIRS TO PROVIDE THE 1FT CANDLE MINIMUM.
 PLEASE ALSO INCLUDE BATTERY BACK UP FIXTURES IN THE
 FOLLOWING ROOMS.
 FIRE COMMAND ROOM
 MAIN ELECTRICAL ROOM (LOCATION YET TO BE DETERMINED)
 GENERATOR ROOM
 FIRE PUMP ROOM
 ALL ELEVATOR MACHINE ROOMS
 FUTURE RETAIL AREAS
 EPSS ROOM (TO BE SHOWN OR PART OF POSSIBLE DESIGN AS
 NOTED ABOVE).
 ** SOME OF THESE ARE ALREADY SHOWN ON PLANS BUT NOT
 ALL.
 NFPA-700.12F, 700.16, NFPA-7.8 AND 7.9.
  
 22) NOTE: PLEASE LIST ALL ITEMS IN FIRE COMMAND ROOM AS
 REQUIRED PER NFPA-101 11.8.5. PLEASE INDICATE NOTES FOR
 MAPPING OF BUILDINGS ELECTRICAL SYSTEM AND EMERGENCY
 SYSTEMS LOCATIONS.
 230.2E, 700.8, 701.9 ETC
  
 23) NOTE: PLEASE SEE AREAS SUCH AS FUTURE RETAIL AREAS
 SHALL INCLUDE LIGHTING CONTROLS PER 13-415.1.ABC.1.1,
 .1.2.
  
 24) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS AFTER THE FIRST MEANS OF DISCONNECT AT MANY
 LOCATIONS. PLEASE SEE RETAIL METERS FROM GUTTER FOR
 EXAMPLE WHICH IS AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE INDICATE ON THE RISER FLOATING NEUTRAL KITS
 WHICH WILL BE REQUIRED.
 PLEASE SEE 250.6, 250.24, 250.110, 250.122
  
 25) NOTE: PLEASE SEE ALL OTHER CONDUITS SHALL CONTAIN
 AN EQUIPMENT GROUNDING CONDUCTORS IN CONDUITS AFTER THE
 FIRST MEANS OF DISCONNECT. THE PLANS DO CONTAIN NOTES
 FOR SOME BUT NOT FOR ALL. PLANS ALSO MENTIONS ONLY IF
 PVC.
 PLEASE KNOW ANY METALLIC CONDUIT PATHS SHALL USE
 CONNECTORS WHICH ARE LISTED AS AN APPROVED *EQUIPMENT
 GROUNDING PATH*. THESE CONNECTORS, COUPLINGS ETC SHALL
 CONTAIN A LISTED APPROVED FOR SUCH USE BY A NRTL.
 (NATIONALLY RECOGNIZED TESTING LABORATORY.
 110.3, 250.110, 250.122.
  
 26) NOTE: PLEASE PROVIDE THROUGH FLOOR CURBING DETAILS
 FOR BUS-DUCT PER 368.10 ( C ) ALL.
  
 27). PLEASE PROVIDE WALL AND FLOOR FIRE RATED
 PENETRATION DETAILS ON ELECTRICAL PLANS PER NEC 300.21
 AND NFPA 221, SECTION 4.2, PENETRATION SEALS, STATES
 THE FOLLOWING:
 ALL THROUGH-PENETRATION PROTECTION SYSTEMS SHALL BE
 TESTED AND RATED IN ACCORDANCE WITH ASTM E 814,
 STANDARD TEST METHOD FOR FIRE TESTS OF
 THROUGH-PENETRATION FIRE STOPS, OR ANSI/UL 1479, FIRE
 TEST OF THROUGH-PENETRATION FIRE STOPS. THE POSITIVE
 PRESSURE DIFFERENCE BETWEEN THE EXPOSED AND UNEXPOSED
 SURFACES OF THE TEST ASSEMBLY SHALL NOT BE LESS THAN
 0.01 IN. (2.5 PA) WATER GAUGE. A THROUGH-PENETRATION
 PROTECTION SYSTEM SHALL HAVE AN F RATING NOT LESS THAN
 THE REQUIRED FIRE RESISTANCE RATING OF THE FIRE WALL OR
 FIRE BARRIER WALL. ANSI/UL 1479 /ASTM E 814-02.
  
 28) NOTE: PLEASE SEE PLANS AS SOME SHEETS CONTAINS
 NOTES WHICH ARE TOO SMALL TO READ. PLEASE SEE SHEETS
 EN-2.2 AND 2.3 FOR EXAMPLE. THERE ARE OTHER SHEETS ALSO
 HOWEVER ONLY A COUPLE IS NOTED.
  
 29) NOTE: PLEASE SEE MISSING GROUND LEVEL
 PHOTO-METRICS.
 PLEASE ALSO SUBMIT COMPLETED PHOTO-METRICS FOR POOL
 AREA FOR ANY PROPOSED AFTER DUSK TO DAWN SWIMMING.
 PLEASE KNOW THAT ANY PHOTO-METRICS FOR ANY PROPOSED
 AFTER DUSK AND BEFORE DAWN SWIMMING WILL BE REQUIRED TO
 BE STAMPED BY THE PALM BEACH COUNTY HEALTH DEPARTMENT.
 POOL WILL BE UNDER A SEPARATE PERMIT AND REGULAR PLANS
 FOR ACTUAL POOL WILL ALSO HAVE PLANS STAMPED AT A LATER
 DATE.
 AS LIGHTING FOR POOL AREAS ARE UNDER THIS REVIEW THIS
 WOULD BE NEEDED AT THIS TIME.
  
 30) NOTE: PLEASE PLACE DISTANCES/NOTES ON PLANS FOR
 REQUIRED CLEARANCES OF LIGHT FIXTURES AROUND POOL AREA.
 PLEASE SEE 680.22/23 AND MOST IMPORTANTLY 411.4B WHICH
 REQUIRES 10FT MINIMUM.
  
 31) NOTE: PLEASE PLACE NOTE ON ROOF TOP PLANS. ANY
 PROPOSED LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED
 PER NFPA-780. OR WORDS TO THAT AFFECT.
 PLEASE BE AWARE THAT NON-ACCEPTABLE SYSTEMS SUCH AS
 ESE, CTSARE NOT PERMITTED.
  
 32) NOTE: PLEASE KNOW THE MANUFACTURES SPECS/CUT SHEETS
 FOR THE PROPOSED SAUNA WILL BE NEEDED TO BE SUBMITTED
 FOR REVIEW.
 PLEASE BE AWARE UNIT IS REQUIRED TO BE LISTED BY A
 NRTL.
 110.3
  
 33) NOTE: PLEASE CORRELATE THE ELECTRICAL PLANS WITH
 THE PLUMBING PLANS FOR THE PROPOSED INSTA-HOT WATER
 HEATER UNITS.
 PLEASE SEE THE MINIMUM OVER CURRENT PROTECTION, BRANCH
 CIRCUIT, WIRING ETC SHALL MEET 422.11. IF STORAGE TYPE,
 422.13.
 PLEASE SEE UNIT PANEL SCHEDULES AS THE OVER CURRENT
 PROTECTION AND BRANCH CIRCUITS EXCEED THE RATING OF THE
 BRANCH CIRCUIT PROVIDED.
 PLEASE SE LOAD IS SHOWN AT 8300 VA AND THE CIRCUIT IS
 ONLY 30AMPS WITH #10 AWG.
 PLEASE BE SURE TO SEE THE MINIMUM AND MAXIMUM RATINGS
 PER THE MANUFACTURES RECOMMENDATIONS STATED ON SPECS
 PRINTED ON PLUMBING SHEETS.
 240.4, 310.16, 110.3, 90.7 ETC
 FBC 106.1.2 FOR COORDINATION.
  
 34) NOTE: PLANS SHOWS THE LOCATION OF THIS HEATING UNIT
 FOR HOT WATER BEING LOCATED UNDER THE SINK AND IN CLOSE
 PROXIMITY OF STORAGE OF COMBUSTIBLES WHICH IS NOT
 PERMITTED PER 422.17.
  
 35) NOTE: PLEASE ALSO KNOW THAT ANY PROPOSED DISCONNECT
 WHICH CONTAINS OVER CURRENT PROTECTION SHALL MEET
 110.26 FOR MINIMUM CLEARANCES. (INCLUDING WATER HEATING
 UNIT).
  
 36) NOTE: PLEASE SEE PLANS WHICH SHOWS SMOKE DETECTORS
 INSTEAD OF SMOKE ALARMS. PLEASE SEE NFPA-72 DEFINITIONS
 AS A SMOKE DETECTOR ONLY DETECTS AND DOES NOT SOUND AN
 ALARM WHEREAS A SMOKE ALARM NOT ONLY DETECTS BUT ALSO
 SOUNDS AN ALARM.
 IF THESE ARE INDEED SMOKE DETECTORS PLEASE COMPLETE
 PLANS WITH FIRE ALARM PANEL, SYSTEM AND HORN DEVICES IN
 EACH UNIT. IF THESE ARE SMOKE ALARMS PLEAS ADJUST ALL
 DESIGNATIONS ON PLANS.
  
 37) NOTE: PLEASE SEE NFPA-72 11.5.1.1.1 AND 11.8.3
 WHICH REQUIRES THESE SMOKE DETECTION DEVICES TO BE
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PLEASE SEE THE SECTION ABOVE FOR INSTALLATION LOCATIONS
 AS THIS REQUIRES A MINIMUM OF 3FT FROM BATH ROOM DOORS.
 THIS SAME SECTION ALSO REQUIRES 20FT FROM COOKING
 APPLIANCES UNLESS MEETING EXCEPTIONS OF A PARTICULAR
 UNIT.
 PLEASE NOT ONLY ADJUST MANY LOCATIONS ON PLANS, BUT
 ALSO ADD SOME MISSING AND ADJUST SPECIFIED DEVICES FOR
 DEVICES LOCATED WITHIN 20FT.
 PLEASE SEE SOME UNITS NOTED FOR EXAMPLE: UNIT M AND
 OTHERS ALSO.
  
 38) NOTE: PLEASE GO OVER PLANS AND RISER FOR
 COORDINATION OF THE SIZING OF PANELS.
 PLEASE SEE SOME WHICH ARE IN NEED OF ADJUSTING. FOR
 EXAMPLE: RISER SHOWS PANELS *M* AS 125AMP AND PANEL *M*
 IS SHOWN AS 150AMP ON SCHEDULE.
 FBC 106.1.23 FOR COORDINATION.
  
 39) NOTE: PLEASE SEE 210.52C1 FOR KITCHEN COUNTER
 SPACES FOR 12INCHES OR MORE OF COUNTER.
 PLEASE SEE MANY UNITS APPEAR TO SCALE 12INCHES OR MORE
 AND SOME ARE IN QUESTION.
 PLEASE SEE UNITS FOR EXAMPLE: B, C, D, A ETC PLEASE BE
 SURE TO SEE 210.8A6 FOR ANY REQUIRED GFI PROTECTION.
  
 40) NOTE: PLEASE COORDINATE ALL CIRCUITING IN UNITS
 WITH PANEL SCHEDULES. FOR EXAMPLE: PLEASE SEE UNIT *B*
 WHICH SHOWS CIRCUIT #16 TO MASTER BEDROOM HOWEVER
 ACTUALLY SHOWS FEEDING OTHER BEDROOM ON PLANS. PLEASE
 SEE FOR EXAMPLE: COMPLETE CIRCUITING FOR ALL IS
 REQUIRED INCLUDING ITEMS SUCH AS LIGHTING IN BEDROOM IN
 UNIT B WHICH IS MISSING CIRCUIT.
 UNIT K, AND OTHERS.
 FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION.
  
 41) NOTE: PLEASE SEE THERE ARE SEVERAL LOCATIONS IN
 UNITS WHICH THE DINING, BREAKFAST AREAS AND AREAS OF
 THE LIKE CONTAIN CIRCUITS TO RECEPTACLES WHICH ARE NOT
 APART OF THE ONE OR MORE SMALL APPLIANCE CIRCUITS AS
 REQUIRED PER 210.52B1, 210.11C1, 220.52.
 PLEASE SEE UNIT K, UNIT M FOR A COUPLE OF EXAMPLES;
 THESE ARE NOT ALL.
 ** PLEASE SEE SOME OF THE RECEPTACLES IN THESE AREAS
 ARE BEING SHOWN ON THE GENERAL LIGHTING CIRCUIT
 PROVIDED BY THE MTS PANEL WHICH IS NOT PERMITTED UNLESS
 IT BECOMES ONE OF THE SMALL APPLIANCE CIRCUITS. THIS
 WOULD REQUIRE 1500VA PER CIRCUIT ETC.
  
 42) NOTE: PLEASE SEE DINING AREA WHICH CONTAINS A
 LAUNDRY ROOM RECEPTACLE AND CIRCUIT. PLEASE SEE
 210.11C2 WHICH DOES NOT PERMIT THIS.
 PLEASE SEE UNIT Q FOR ONE EXAMPLE.
  
 43) NOTE: PLEASE SEE 210.52 FOR SOME RECEPTACLES
 MISSING FOR 2FT OF WALL SPACE. MOST RECEPTACLES MEET
 210.52 AND THERE ARE ONLY A FEW MISSING.
 PLEASE SEE UNIT P FOR EXAMPLE AT DOOR. (REDLINED ON
 PLANS).
  
 44) NOTE: PLEASE SEE THE BRANCH CIRCUIT ON MTS PANEL
 WHICH IN SOME UNITS IS SHOWN FEEDING LIGHTING OUTLETS
 OR OTHER DEVICES IN SLEEPING AREAS ARE REQUIRED TO ARC
 FAULT PER 210.12.
 FOR EXAMPLE: UNIT M.
  
 45) NOTE: PLEASE SEE LOAD ON E2 IS MORE THAN THE RATED
 LOAD OF GENERATOR.
 PLEASE SEE SIZING OF EQUIPMENT PER 220.
  
 46) NOTE: PLEASE SEE NOTE ON ELECTRICAL RISER 8TH LEVEL
 WEST RISER WHICH SHOWS 1-125AMP AND 2-150AMP? WHAT ARE
 THESE FOR ?
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 47) NOTE: PLEASE CONFIRM THE NUMBER OF CIRCUITS SHOWN
 ON UNIT PANELS WHICH SHOWS THESE AS 32 CIRCUIT PANELS.
 PLEASE SUBMIT SPEC/CUT SHEET FOR PANELS.
 110.3, 90.7
 FBC 106.1.2
  
 48) NOTE:PLEASE BE SURE TO SPECIFY FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM PER 250.50
  
 49) NOTE: PLEASE SEE PANEL H2 IS NOT ON RISER AT
 MEZZANINE AS LISTED ON PANEL SCHEDULE.
 FBC 106.1.2 FOR COORDINATION.
  
 50) NOTE: PLEASE SEE RISER SHOWS 400AMP OVER CURRENT
 PROTECTION AND RISER UP TO EE AN EW PANELS YET NO
 INFORMATION WAS SHOWN ON HOW THESE WILL BE TAPPED OR
 CONNECTED.
 PLEASE SEE 240.4, 310.16, 240.21 AS THE TAPPED
 CONDUCTORS AS SHOWN ON FEEDER LEGEND AS #3 ARE NOT
 RATED FOR THE 125AMP BREAKER AT TERMINATION.
  
 51) NOTE: PLEASE KNOW IT HAS COME TO OUR ATTENTION THAT
 THE PROPOSED PROJECT IS GOING FOR A LEED
 CERTIFICATION.
 PLEASE BE SURE TO PROVIDE INFORMATION AND ALL NOTES
 ABOVE WITH RESPECT TO FBC AND CHAPTER 13.
  
 52) NOTE: PLEASE KNOW ONE SET OF ELECTRICAL PLANS
 CONTAINS MANY OF THE ABOVE ITEMS REDLINED HOWEVER NOT
 ALL.
 PLEASE ALSO KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED FOR REVIEW AND DUE TO THE FACT THERE WILL BE
 CHANGES TO PLANS THERE MAY VERY WELL BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 53) NOTE: PLEASE KNOW AS THIS A THRESHOLD PROJECT,
 THREE SETS OF PLANS, AND ALL SUPPORTING DOCUMENTS ARE
 REQUIRED TO BE SUBMITTED FOR REVIEW AND STAMPING.
  
 **
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-02-13 11:33:17 
  
 ONE ROLL IN ELECTRIC FOR REVIEW.