| 2008-02-16 11:56:05 | NOTE ADDED: |
| | |
| | PLEASE SEE UNITS WHICH CONTAIN A NOTE FOR AN EF-2 YET |
| | THE PLANS DO NOT SHOW ANY EF-IN UNITS. |
| 2008-02-14 19:17:57 | 2008-02-14 19:17:57 |
| | |
| | *** DENIED*** |
| | |
| | CANNES WEST PALM |
| | |
| | 1) NOTE: PLEASE KNOW THIS PROJECT WAS ONLY SUBMITTED |
| | FOR PLAN REVIEW AND NOT FOR PERMIT. ONCE ALL REVIEW |
| | COMMENTS ARE ADDRESSED PLANS WILL STILL REMAIN IN *F* |
| | STATUS UNTIL PERMIT HAS BEEN APPLIED FOR. |
| | ONCE PERMIT IS APPLIED FOR, REVIEW FOR ITEMS SUCH AS |
| | LICENSING ETC WILL BE DONE AT THAT TIME. |
| | |
| | 2) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES |
| | ARE STATED ON BOTH THE ELECTRICAL AS WELL AS THE |
| | ARCHITECTURAL COVER SHEETS. SOME OF THE FOLLOWING MAY |
| | ALREADY BE PRESENT HOWEVER SOME ARE NOT AT THIS TIME. |
| | 2004 FBC W/ 2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA72 |
| | 2002 NFPA-110 |
| | 2003 NFPA-20 |
| | |
| | ** SOME OF THESE ARE ALREADY SHOWN BUT NOT ALL AND NOT |
| | ON ELECTRICAL PLANS. |
| | |
| | 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | ARE NOT THE EDITION ADOPTED BY THE FBC 13-400.3.A. |
| | PLEASE SEE THE CALCULATIONS SUBMITTED DO NOT COMPLY |
| | WITH THE FBC. MOST IMPORTANTLY THE ELECTRICAL LIGHTING |
| | ON PLANS DOES NOT CORRELATE THE CALCULATIONS. FOR THE |
| | REMAINDER OF THIS COMMENT THE INPUT DATA REPORT WILL BE |
| | NOTED AT IDR. |
| | |
| | A) ** PLEASE SEE THE LIGHTING FOR INTERIOR LIGHTING ON |
| | PLANS DOES NOT COORDINATE WITH THE IDR FOR THE NUMBER |
| | OF FIXTURES, THE TYPES OF FIXTURES OR THE WATTAGES OF |
| | FIXTURES. FOR EXAMPLE: THE IDR FOR INTERIOR SHOWS A |
| | TOTAL OF 8 LIGHT FIXTURES ON THE INTERIOR OF THE |
| | BUILDING. HOW IS THIS POSSIBLE WHEN THE PLANS SHOWS |
| | HUNDREDS AND HUNDREDS OF LIGHTS?? |
| | |
| | B) ** PLEASE SEE THE IDR FOR EXTERIOR LIGHTING |
| | INFORMATION. THE IDR SHOWS ABSOLUTELY NO EXTERIOR |
| | LIGHTING FIGURED INTO THE CALCULATIONS. HOW IS THIS |
| | POSSIBLE WHEN THE PLANS SHOWS ONCE AGAIN HUNDREDS OF |
| | FIXTURES. |
| | |
| | THIS OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEAS BE SURE |
| | THAT ALL LIGHTING ON PLANS COORDINATES WITH THE |
| | LIGHTING IN THE IDR SUBMITTED. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, 13-415.2.ABC.1.3 |
| | ETC 13-415.1.A, 13-400.3.A ETC. |
| | PLEASE SEE METHOD SUBMITTED IS CURRENTLY IN QUESTION AS |
| | THE BUILDING CONTAINS *SHELL* PORTIONS WHICH ARE NOT |
| | KNOWN AT THIS TIME. |
| | PLEASE SEE 13-400.2.A.2 AS METHOD *A* MAY ONLY BE USED |
| | ONCE ALL ITEMS BEING INSTALLED ARE COMPLETED AND KNOWN. |
| | IF THERE ARE ITEMS NOT KNOWN BEING FUTURE, THEN THE |
| | ONLY OTHER CHOICE WOULD BE METHOD *B* FOR WHICH SECTION |
| | 13-415.1.B, 13-400.3.B APPLIES. |
| | PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY ALSO |
| | TOUCH ON THIS SAME TOPIC. |
| | |
| | 4) NOTE: PLEASE SUBMIT COMPLETE LIGHTING PLANS WITH |
| | MINIMUM REQUIRED CONTROLS FOR FBCCHAPTER 13, |
| | 13-415.1.ABC.1.1, .1.2 , .1.3 AND .1.4. |
| | PLEASE KNOW BASED ON PLANS WHICH ONLY SHOW STANDARD |
| | SWITCHES WHICH ARE WHAT THE SYMBOL LEGEND STATES AND |
| | SHOWS NO LIGHTING CONTROLS WHICH ARE REQUIRED ARE IN |
| | THE DESIGN FOR THE BUILDING AT THIS TIME. |
| | PLEASE SEE PLANS DO CONTAIN A NOTE FOR SOME KIND OF |
| | J-BOX IN STAIR WAYS FOR LIGHTING CONTROLS HOWEVER NO |
| | SYSTEM OR PROPOSED ITEMS FOR DESIGN COULD BE LOCATED. |
| | PLEASE BE SURE TO SEE NOT ONLY CHAPTER 10 OF THE FBC |
| | FOR OCCUPANCY SENSING DEVICES PERMITTED ON EMERGENCY |
| | EGRESS LIGHTS BUT NFPA-101 7.8.1.2.2 AUTOMATIC, MOTION |
| | SENSOR'"TYPE LIGHTING SWITCHES SHALL BE PERMITTED |
| | WITHIN THE MEANS OF EGRESS, PROVIDED THAT THE SWITCH |
| | CONTROLLERS ARE EQUIPPED FOR FAIL-SAFE OPERATION, THE |
| | ILLUMINATION TIMERS ARE SET FOR A MINIMUM 15-MINUTE |
| | DURATION, AND THE MOTION SENSOR IS ACTIVATED BY ANY |
| | OCCUPANT MOVEMENT IN THE AREA SERVED BY THE LIGHTING |
| | UNITS. PLEASE SEE NOTES BELOW WHICH WILL AFFECT EGRESS |
| | LIGHTING AS SHOWN.(FAIL SAFE ON) |
| | PLEASE KNOW AS THERE IS MUCH INFORMATION NOT SUBMITTED |
| | OR PART OF THE DESIGN, THERE MAY VERY WELL BE NEW |
| | COMMENTS ONCE PLANS ARE RESUBMITTED FOR THE NEXT |
| | REVIEW. |
| | |
| | 5) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS SHOWS |
| | 505 4TH STREET WHEN THE APPLIED LOCATIONS IS 510 4TH |
| | STREET. PLEASE BE SURE EACH BUILDING SET OF PLANS FOR |
| | EACH SEPARATE PERMIT CONTAINS THE CORRECT ADDRESS ON |
| | TITLE BLOCKS. |
| | FBC 106.5 ADMIN SECTION. |
| | FAC 61G1-16.004, FAC 61G15-23.002 |
| | |
| | 6) NOTE: PLEASE SEE HOUSE BILL 7121 FOR REQUIRED |
| | ON-SITE FUEL FOR BACK UP OF A GENERATOR IN A |
| | RESIDENTIAL HIGH-RISE BUILDING. |
| | PLEASE KNOW THAT BESIDES THE REQUIRED ITEMS PER NEW |
| | STATE STATUTES, PLEASE BE AWARE THAT IF THE BUILDING IS |
| | GOING TO BE OCCUPIED UNDER THE POWER OF THE GENERATOR |
| | ONLY, OTHER SYSTEMS SUCH AS VENTILATION ETC WILL NEED |
| | TO BE PART OF THE DESIGN OF FUEL CONSUMPTION ALONG WITH |
| | ALL OTHER LIFE SAFETY SYSTEMS. |
| | THIS WILL NEED TO BE GONE OVER ON THE PHONE OR IN |
| | PERSON TO CLARIFY WHAT IS REALLY NEEDED. |
| | |
| | 7) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE FOLLOWING ITEMS. THE GENERATOR, FUEL |
| | TANK(S), FIRE PUMP, FIRE PUMP CONTROLLER AND BOTH MTS |
| | AND ATS DEVICES. |
| | THERE ARE SEVERAL ITEMS WHICH COULD NOT BE REVIEWED FOR |
| | CODE COMPLIANCE AT THIS TIME. |
| | NEC 90.7, 110.3, NFPA-20, NFPA-110 ETC |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 8) NOTE: PLEASE SEE THE GENERATOR AS SHOWN ON PLANS |
| | DOES INDICATE THE PRIME-MOVER OR FUEL SOURCE? PLEASE |
| | SEE NFPA-110, NFPA-70 |
| | THERE ARE TOO MANY CODE SECTIONS TO LIST FOR REQUIRED |
| | ITEMS. |
| | PLEASE SEE NFPA-110 FOR LOCATION OF THE REQUIRED |
| | GENERATOR. |
| | PLEASE SEE THAT ALL ITEMS SHALL MEET ALL CHAPTERS |
| | HOWEVER MORE SPECIFIC PER THIS REVIEW CHAPTER 7. PLEASE |
| | SEE VENTILATION, LIGHTING LEVELS, LOCATION OF EQUIPMENT |
| | ETC. |
| | MAY NOT TAKE THE VENTILATION FROM ADJACENT ROOMS, MUST |
| | COME DIRECTLY FROM OUTSIDE. |
| | PLEASE KNOW THERE ARE TOO MANY CODE SECTIONS TO NOTE AT |
| | THIS TIME.7.1, 7.2, 7.3, 7.4, 7.5 ETC |
| | PLEASE SEE THAT THE MINIMUM LIGHTING LEVELS SHALL MEET |
| | 30FT CANDLES. THIS WILL BE NOTED IN NOTE BELOW FOR |
| | PHOTO-METRICS LEVELS. |
| | PLEASE SEE 700.12B (1), (3), 701.11B(1),(3) , ETC |
| | |
| | 9) NOTE: PLEASE SEE SOME A-SHEETS WHICH CONTAIN HAND |
| | DRAWN ITEMS WHICH CAN NOT BE MADE TO SIGNED AND SEALED |
| | PLANS. |
| | FS 481.221, 471.023 |
| | THIS COMMENT IS NOTED FOR ALL PLANS AND FOR ALL |
| | REVIEWS. |
| | |
| | 10) NOTE: PLEASE SEE MISSING RATED SEPARATION WHICH |
| | WILL BE A PART OF BUILDING SEPARATION. PLEASE ALSO KNOW |
| | THE ELECTRICAL SYSTEMS ON EACH SIDE OF THIS PROPOSED |
| | WALL AND FIRE RATED DOORS SHALL BE SEPARATED. PLEASE |
| | SEE THE LOCATION OF THE MAIN ELECTRICAL ROOM AS SHOWN |
| | IS NOT ACCEPTABLE TO THIS AHJ. THIS CREATES A MAJOR |
| | LIFE SAFETY HAZARD. EMERGENCY PERSONNEL DO NOT HAVE |
| | DIRECT AND IMMEDIATE ACCESS TO THE MAIN ELECTRICAL |
| | ROOM. THE LOCATION SHALL BE AT A NEAREST POINT OF |
| | ENTRANCE INTO THE BUILDING. . THE LOCATION WILL NEED TO |
| | BE DETERMINED BEFORE RESUBMITTED PLANS. SOME ITEMS WERE |
| | ALREADY GONE OVER WITH THE ELECTRICAL ENGINEER AFTER |
| | PLANS WERE SUBMITTED. |
| | 230.2, 230.70, 230.71, 230.72 ETC |
| | |
| | 11) NOTE: PLEASE SEE NEC 230.2 AND NFPA-110 FOR THE |
| | ACCEPTABLE LOCATION OF EPSS EQUIPMENT. |
| | PLEASE SEE NFPA-1107.2.2, 7.1.5, 7.2.1 ETC WHICH DOES |
| | NOT PERMIT THIS EQUIPMENT IN THE SAME ROOM AS THE |
| | NORMAL ELECTRICAL EQUIPMENT. PLEASE SEE 7.2.2.1 WHICH |
| | DOES ALLOW THE ATS/ TRANSFER EQUIPMENT IN THE SAME ROOM |
| | AS LONG AS TWICE THE DISTANCES FROM OTHER EQUIPMENT PER |
| | 110.26 IS PROVIDED. PLEASE SEE THE NEC WHICH STATES |
| | THIS EQUIPMENT SHALL BE SUFFICIENTLY REMOTE.NFPA-70 |
| | DOES NOT GIVE A DEFINITION FOR WHAT SUFFICIENTLY REMOTE |
| | IS HOWEVER NFPA-110 DOES PROVIDEDEFINITION OF LEVEL 1 |
| | OR LEVEL 2 SYSTEMS NOT TO BE LOCATE WITH IN THE SAME |
| | ROOM. |
| | PLEASE RE-LOCATE. |
| | |
| | 12) NOTE: PLEASE SEE MISSING INFORMATION FOR THE FIRE |
| | PUMP. PLEASE SEE NFPA-20CHAPTERS AND NFPA-70. MORE |
| | SPECIFIC PLEASE SEE CHAPTERS 9 AND 10 OF NFPA-20 AND |
| | NEC 695 FOR FIRE PUMPS. |
| | COULD NOT LOCATE INFORMATION ON REQUIRED LOCKED ROTOR |
| | CURRENT SETTINGS WHICH NEEDS TO BE SHOWN ON PLANS. |
| | COULD NOT LOCATE INFORMATION ON ISOLATION SWITCH(S), |
| | BY-PASS, ETC |
| | COULD NOT LOCATE THE MINIMUM REQUIRE ON-SITE FUEL FOR A |
| | MINIMUM OF 8HRS OF RUN TIME AT 100%. PLEASE BE SURE TO |
| | SEE NOTES ABOVE WITH RESPECT TO THE ALLOWANCE FOR HOUSE |
| | BILL 7121. IF BUILDING IS UNDER OCCUPANCY FOR THE |
| | PERIOD AS SPECIFIED THEN PLEASE SEE THAT THE FIRE PUMP |
| | SHALL HAVE THE REMAINDER OF ON-SITE FUEL FOR ANY GIVEN |
| | TIME DURING OCCUPANCY. |
| | |
| | 13) NOTE: PLEASE SEE NFPA-1107.1.5 AND NFPA-70 |
| | CHAPTERS 700 AND 701 WHICH DOES PERMIT OPTIONAL |
| | STAND-BY EQUIPMENT BEING FED FROM THE GENERATOR WHICH |
| | ALSO FEEDS LIFE SAFETY AND LEGALLY REQUIRED LOADS |
| | HOWEVER NO PROVISIONS FOR LOAD SHEDDING WAS INDICATED |
| | ON PLANS. |
| | PLEASE KNOW AT THIS TIME BASED ON THE PLANS, AND OTHER |
| | REQUIRED SYSTEMS THE GENERATOR IS NOT OF SUFFICIENT |
| | SIZE FOR ALL REQUIRED SYSTEMS. |
| | PLEASE ALSO PROVIDE LOAD SHEDDING DETAIL FOR THE UNITS |
| | MTS PANELS WHICH ARE FED FROM EU-2. |
| | PLEASE KNOW AS THERE ARE SEVERAL CHANGES NEEDED MANY |
| | ITEMS CAN NOT BE REVIEWED AT THIS TIME. |
| | |
| | 14) NOTE: PLEASE SEE GENERATOR ROOM WALL DETAIL ON |
| | EN-6.0 DOES NOT COORDINATE WITH OTHER SHEERS IN PLANS. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 15) NOTE: PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA |
| | DESIGNATIONS ON PLANS. PLEASE SEE FOR EXAMPLE: EN-2.0 , |
| | 2.1 ETC WHICH SHOW AREAS/ROOMS HOWEVER DO NOT INDICATE |
| | ANY DESIGNATIONS. |
| | THIS IS FOR MANY LOCATIONS ON PLANS HOWEVER NOT ALL ARE |
| | LISTED. |
| | PLEASE ALSO BE SURE TO COMPLETE THE SAME FOR UNITS. |
| | SOME OF THE UNITS IN THE BEGINNING OF UNIT PLANS DO |
| | INDICATE DESIGNATIONS HOWEVER AS THE UNIT SHEETS GO ON |
| | THE AREAS AND ROOMS WERE NOT ON SHEETS. |
| | PLEASE KNOW THAT ARE CODE SECTIONS WHICH APPLY TO UNITS |
| | WHICH CAN NOT BE CONFIRMED AT THIS TIME SUCH AS |
| | 210.52B1 FOR CIRCUITING OF ITEMS IN DINING AREAS. |
| | (COMMENTED BELOW). |
| | |
| | 16) NOTE: PLEASE SEE FAIR HOUSING ACT REGULATIONS 24 |
| | CFR, 100.205 AND FBC CHAPTER 11 FOR REQUIRED HEIGHTS |
| | AND LOCATIONS FOR DEVICES. |
| | PLEASE LIST ON PLANS. |
| | |
| | 17) NOTE: PLEASE BE SURE TO PROVIDE ANY INFORMATION FOR |
| | ANY ACCESS CONTROL SYSTEMS SUCH AS PARKING GARAGE GATE |
| | OPERATORS AND BATTERY BACK UP. |
| | PLEASE ALSO PROVIDE INFORMATION ON ANY ACCESS CONTROLS |
| | OF INGRESS OR EGRESS DOORS. PLEASE SEE NFPA-101 7.5.1, |
| | 7.5.2, 7.5.4. AT THIS TIME THERE IS NOT ENOUGH |
| | INFORMATION SHOWN. |
| | NO DEVICES ARE TO BE INSTALLED WHICH IN THE EVENT OF |
| | ANY EMERGENCY OR NON EMERGENCY WILL IMPEDE THE EGRESS |
| | OF OCCUPANTS OR FIRE DEPARTMENT PERSONNEL IN ANY WAY. |
| | PLEASE BE AWARE OF ANY POSSIBLE COMMENTS FROM FIRE |
| | MARSHAL. |
| | |
| | 18) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL |
| | EGRESS PATHS UNDER NORMAL AND EMERGENCY CONDITIONS. |
| | THIS IS INCLUSIVE OF STAIR WAYS ETC. |
| | PLEASE SEE NFPA-101 7.8.1.3 AND 7.9.2.2 WHICH REQUIRES |
| | A MINIMUM OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED |
| | DOWN TO 1FT CANDLE UNDER EMERGENCY. |
| | |
| | 19) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR THE GENERATOR |
| | ROOM AS NFPA-110 7.3.3 REQUIRES 30FT CANDLES MINIMUM. |
| | |
| | 20) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR ELEVATOR PITS |
| | FOR THE MINIMUM OF 5FT CANDLES REQUIRED PER ASME |
| | A17.1-2004, SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| | LEVELS ARE AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO |
| | BE EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE. |
| | |
| | 21) NOTE: PLEASE KNOW THAT BATTERY BACK UP LIGHTING |
| | FIXTURES WILL BE REQUIRED FOR ALL EGRESS PATHS |
| | INCLUDING STAIRS TO PROVIDE THE 1FT CANDLE MINIMUM. |
| | PLEASE ALSO INCLUDE BATTERY BACK UP FIXTURES IN THE |
| | FOLLOWING ROOMS. |
| | FIRE COMMAND ROOM |
| | MAIN ELECTRICAL ROOM (LOCATION YET TO BE DETERMINED) |
| | GENERATOR ROOM |
| | FIRE PUMP ROOM |
| | ALL ELEVATOR MACHINE ROOMS |
| | FUTURE RETAIL AREAS |
| | EPSS ROOM (TO BE SHOWN OR PART OF POSSIBLE DESIGN AS |
| | NOTED ABOVE). |
| | ** SOME OF THESE ARE ALREADY SHOWN ON PLANS BUT NOT |
| | ALL. |
| | NFPA-700.12F, 700.16, NFPA-7.8 AND 7.9. |
| | |
| | 22) NOTE: PLEASE LIST ALL ITEMS IN FIRE COMMAND ROOM AS |
| | REQUIRED PER NFPA-101 11.8.5. PLEASE INDICATE NOTES FOR |
| | MAPPING OF BUILDINGS ELECTRICAL SYSTEM AND EMERGENCY |
| | SYSTEMS LOCATIONS. |
| | 230.2E, 700.8, 701.9 ETC |
| | |
| | 23) NOTE: PLEASE SEE AREAS SUCH AS FUTURE RETAIL AREAS |
| | SHALL INCLUDE LIGHTING CONTROLS PER 13-415.1.ABC.1.1, |
| | .1.2. |
| | |
| | 24) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTORS AFTER THE FIRST MEANS OF DISCONNECT AT MANY |
| | LOCATIONS. PLEASE SEE RETAIL METERS FROM GUTTER FOR |
| | EXAMPLE WHICH IS AFTER THE FIRST MEANS OF DISCONNECT. |
| | PLEASE INDICATE ON THE RISER FLOATING NEUTRAL KITS |
| | WHICH WILL BE REQUIRED. |
| | PLEASE SEE 250.6, 250.24, 250.110, 250.122 |
| | |
| | 25) NOTE: PLEASE SEE ALL OTHER CONDUITS SHALL CONTAIN |
| | AN EQUIPMENT GROUNDING CONDUCTORS IN CONDUITS AFTER THE |
| | FIRST MEANS OF DISCONNECT. THE PLANS DO CONTAIN NOTES |
| | FOR SOME BUT NOT FOR ALL. PLANS ALSO MENTIONS ONLY IF |
| | PVC. |
| | PLEASE KNOW ANY METALLIC CONDUIT PATHS SHALL USE |
| | CONNECTORS WHICH ARE LISTED AS AN APPROVED *EQUIPMENT |
| | GROUNDING PATH*. THESE CONNECTORS, COUPLINGS ETC SHALL |
| | CONTAIN A LISTED APPROVED FOR SUCH USE BY A NRTL. |
| | (NATIONALLY RECOGNIZED TESTING LABORATORY. |
| | 110.3, 250.110, 250.122. |
| | |
| | 26) NOTE: PLEASE PROVIDE THROUGH FLOOR CURBING DETAILS |
| | FOR BUS-DUCT PER 368.10 ( C ) ALL. |
| | |
| | 27). PLEASE PROVIDE WALL AND FLOOR FIRE RATED |
| | PENETRATION DETAILS ON ELECTRICAL PLANS PER NEC 300.21 |
| | AND NFPA 221, SECTION 4.2, PENETRATION SEALS, STATES |
| | THE FOLLOWING: |
| | ALL THROUGH-PENETRATION PROTECTION SYSTEMS SHALL BE |
| | TESTED AND RATED IN ACCORDANCE WITH ASTM E 814, |
| | STANDARD TEST METHOD FOR FIRE TESTS OF |
| | THROUGH-PENETRATION FIRE STOPS, OR ANSI/UL 1479, FIRE |
| | TEST OF THROUGH-PENETRATION FIRE STOPS. THE POSITIVE |
| | PRESSURE DIFFERENCE BETWEEN THE EXPOSED AND UNEXPOSED |
| | SURFACES OF THE TEST ASSEMBLY SHALL NOT BE LESS THAN |
| | 0.01 IN. (2.5 PA) WATER GAUGE. A THROUGH-PENETRATION |
| | PROTECTION SYSTEM SHALL HAVE AN F RATING NOT LESS THAN |
| | THE REQUIRED FIRE RESISTANCE RATING OF THE FIRE WALL OR |
| | FIRE BARRIER WALL. ANSI/UL 1479 /ASTM E 814-02. |
| | |
| | 28) NOTE: PLEASE SEE PLANS AS SOME SHEETS CONTAINS |
| | NOTES WHICH ARE TOO SMALL TO READ. PLEASE SEE SHEETS |
| | EN-2.2 AND 2.3 FOR EXAMPLE. THERE ARE OTHER SHEETS ALSO |
| | HOWEVER ONLY A COUPLE IS NOTED. |
| | |
| | 29) NOTE: PLEASE SEE MISSING GROUND LEVEL |
| | PHOTO-METRICS. |
| | PLEASE ALSO SUBMIT COMPLETED PHOTO-METRICS FOR POOL |
| | AREA FOR ANY PROPOSED AFTER DUSK TO DAWN SWIMMING. |
| | PLEASE KNOW THAT ANY PHOTO-METRICS FOR ANY PROPOSED |
| | AFTER DUSK AND BEFORE DAWN SWIMMING WILL BE REQUIRED TO |
| | BE STAMPED BY THE PALM BEACH COUNTY HEALTH DEPARTMENT. |
| | POOL WILL BE UNDER A SEPARATE PERMIT AND REGULAR PLANS |
| | FOR ACTUAL POOL WILL ALSO HAVE PLANS STAMPED AT A LATER |
| | DATE. |
| | AS LIGHTING FOR POOL AREAS ARE UNDER THIS REVIEW THIS |
| | WOULD BE NEEDED AT THIS TIME. |
| | |
| | 30) NOTE: PLEASE PLACE DISTANCES/NOTES ON PLANS FOR |
| | REQUIRED CLEARANCES OF LIGHT FIXTURES AROUND POOL AREA. |
| | PLEASE SEE 680.22/23 AND MOST IMPORTANTLY 411.4B WHICH |
| | REQUIRES 10FT MINIMUM. |
| | |
| | 31) NOTE: PLEASE PLACE NOTE ON ROOF TOP PLANS. ANY |
| | PROPOSED LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED |
| | PER NFPA-780. OR WORDS TO THAT AFFECT. |
| | PLEASE BE AWARE THAT NON-ACCEPTABLE SYSTEMS SUCH AS |
| | ESE, CTSARE NOT PERMITTED. |
| | |
| | 32) NOTE: PLEASE KNOW THE MANUFACTURES SPECS/CUT SHEETS |
| | FOR THE PROPOSED SAUNA WILL BE NEEDED TO BE SUBMITTED |
| | FOR REVIEW. |
| | PLEASE BE AWARE UNIT IS REQUIRED TO BE LISTED BY A |
| | NRTL. |
| | 110.3 |
| | |
| | 33) NOTE: PLEASE CORRELATE THE ELECTRICAL PLANS WITH |
| | THE PLUMBING PLANS FOR THE PROPOSED INSTA-HOT WATER |
| | HEATER UNITS. |
| | PLEASE SEE THE MINIMUM OVER CURRENT PROTECTION, BRANCH |
| | CIRCUIT, WIRING ETC SHALL MEET 422.11. IF STORAGE TYPE, |
| | 422.13. |
| | PLEASE SEE UNIT PANEL SCHEDULES AS THE OVER CURRENT |
| | PROTECTION AND BRANCH CIRCUITS EXCEED THE RATING OF THE |
| | BRANCH CIRCUIT PROVIDED. |
| | PLEASE SE LOAD IS SHOWN AT 8300 VA AND THE CIRCUIT IS |
| | ONLY 30AMPS WITH #10 AWG. |
| | PLEASE BE SURE TO SEE THE MINIMUM AND MAXIMUM RATINGS |
| | PER THE MANUFACTURES RECOMMENDATIONS STATED ON SPECS |
| | PRINTED ON PLUMBING SHEETS. |
| | 240.4, 310.16, 110.3, 90.7 ETC |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 34) NOTE: PLANS SHOWS THE LOCATION OF THIS HEATING UNIT |
| | FOR HOT WATER BEING LOCATED UNDER THE SINK AND IN CLOSE |
| | PROXIMITY OF STORAGE OF COMBUSTIBLES WHICH IS NOT |
| | PERMITTED PER 422.17. |
| | |
| | 35) NOTE: PLEASE ALSO KNOW THAT ANY PROPOSED DISCONNECT |
| | WHICH CONTAINS OVER CURRENT PROTECTION SHALL MEET |
| | 110.26 FOR MINIMUM CLEARANCES. (INCLUDING WATER HEATING |
| | UNIT). |
| | |
| | 36) NOTE: PLEASE SEE PLANS WHICH SHOWS SMOKE DETECTORS |
| | INSTEAD OF SMOKE ALARMS. PLEASE SEE NFPA-72 DEFINITIONS |
| | AS A SMOKE DETECTOR ONLY DETECTS AND DOES NOT SOUND AN |
| | ALARM WHEREAS A SMOKE ALARM NOT ONLY DETECTS BUT ALSO |
| | SOUNDS AN ALARM. |
| | IF THESE ARE INDEED SMOKE DETECTORS PLEASE COMPLETE |
| | PLANS WITH FIRE ALARM PANEL, SYSTEM AND HORN DEVICES IN |
| | EACH UNIT. IF THESE ARE SMOKE ALARMS PLEAS ADJUST ALL |
| | DESIGNATIONS ON PLANS. |
| | |
| | 37) NOTE: PLEASE SEE NFPA-72 11.5.1.1.1 AND 11.8.3 |
| | WHICH REQUIRES THESE SMOKE DETECTION DEVICES TO BE |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | PLEASE SEE THE SECTION ABOVE FOR INSTALLATION LOCATIONS |
| | AS THIS REQUIRES A MINIMUM OF 3FT FROM BATH ROOM DOORS. |
| | THIS SAME SECTION ALSO REQUIRES 20FT FROM COOKING |
| | APPLIANCES UNLESS MEETING EXCEPTIONS OF A PARTICULAR |
| | UNIT. |
| | PLEASE NOT ONLY ADJUST MANY LOCATIONS ON PLANS, BUT |
| | ALSO ADD SOME MISSING AND ADJUST SPECIFIED DEVICES FOR |
| | DEVICES LOCATED WITHIN 20FT. |
| | PLEASE SEE SOME UNITS NOTED FOR EXAMPLE: UNIT M AND |
| | OTHERS ALSO. |
| | |
| | 38) NOTE: PLEASE GO OVER PLANS AND RISER FOR |
| | COORDINATION OF THE SIZING OF PANELS. |
| | PLEASE SEE SOME WHICH ARE IN NEED OF ADJUSTING. FOR |
| | EXAMPLE: RISER SHOWS PANELS *M* AS 125AMP AND PANEL *M* |
| | IS SHOWN AS 150AMP ON SCHEDULE. |
| | FBC 106.1.23 FOR COORDINATION. |
| | |
| | 39) NOTE: PLEASE SEE 210.52C1 FOR KITCHEN COUNTER |
| | SPACES FOR 12INCHES OR MORE OF COUNTER. |
| | PLEASE SEE MANY UNITS APPEAR TO SCALE 12INCHES OR MORE |
| | AND SOME ARE IN QUESTION. |
| | PLEASE SEE UNITS FOR EXAMPLE: B, C, D, A ETC PLEASE BE |
| | SURE TO SEE 210.8A6 FOR ANY REQUIRED GFI PROTECTION. |
| | |
| | 40) NOTE: PLEASE COORDINATE ALL CIRCUITING IN UNITS |
| | WITH PANEL SCHEDULES. FOR EXAMPLE: PLEASE SEE UNIT *B* |
| | WHICH SHOWS CIRCUIT #16 TO MASTER BEDROOM HOWEVER |
| | ACTUALLY SHOWS FEEDING OTHER BEDROOM ON PLANS. PLEASE |
| | SEE FOR EXAMPLE: COMPLETE CIRCUITING FOR ALL IS |
| | REQUIRED INCLUDING ITEMS SUCH AS LIGHTING IN BEDROOM IN |
| | UNIT B WHICH IS MISSING CIRCUIT. |
| | UNIT K, AND OTHERS. |
| | FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION. |
| | |
| | 41) NOTE: PLEASE SEE THERE ARE SEVERAL LOCATIONS IN |
| | UNITS WHICH THE DINING, BREAKFAST AREAS AND AREAS OF |
| | THE LIKE CONTAIN CIRCUITS TO RECEPTACLES WHICH ARE NOT |
| | APART OF THE ONE OR MORE SMALL APPLIANCE CIRCUITS AS |
| | REQUIRED PER 210.52B1, 210.11C1, 220.52. |
| | PLEASE SEE UNIT K, UNIT M FOR A COUPLE OF EXAMPLES; |
| | THESE ARE NOT ALL. |
| | ** PLEASE SEE SOME OF THE RECEPTACLES IN THESE AREAS |
| | ARE BEING SHOWN ON THE GENERAL LIGHTING CIRCUIT |
| | PROVIDED BY THE MTS PANEL WHICH IS NOT PERMITTED UNLESS |
| | IT BECOMES ONE OF THE SMALL APPLIANCE CIRCUITS. THIS |
| | WOULD REQUIRE 1500VA PER CIRCUIT ETC. |
| | |
| | 42) NOTE: PLEASE SEE DINING AREA WHICH CONTAINS A |
| | LAUNDRY ROOM RECEPTACLE AND CIRCUIT. PLEASE SEE |
| | 210.11C2 WHICH DOES NOT PERMIT THIS. |
| | PLEASE SEE UNIT Q FOR ONE EXAMPLE. |
| | |
| | 43) NOTE: PLEASE SEE 210.52 FOR SOME RECEPTACLES |
| | MISSING FOR 2FT OF WALL SPACE. MOST RECEPTACLES MEET |
| | 210.52 AND THERE ARE ONLY A FEW MISSING. |
| | PLEASE SEE UNIT P FOR EXAMPLE AT DOOR. (REDLINED ON |
| | PLANS). |
| | |
| | 44) NOTE: PLEASE SEE THE BRANCH CIRCUIT ON MTS PANEL |
| | WHICH IN SOME UNITS IS SHOWN FEEDING LIGHTING OUTLETS |
| | OR OTHER DEVICES IN SLEEPING AREAS ARE REQUIRED TO ARC |
| | FAULT PER 210.12. |
| | FOR EXAMPLE: UNIT M. |
| | |
| | 45) NOTE: PLEASE SEE LOAD ON E2 IS MORE THAN THE RATED |
| | LOAD OF GENERATOR. |
| | PLEASE SEE SIZING OF EQUIPMENT PER 220. |
| | |
| | 46) NOTE: PLEASE SEE NOTE ON ELECTRICAL RISER 8TH LEVEL |
| | WEST RISER WHICH SHOWS 1-125AMP AND 2-150AMP? WHAT ARE |
| | THESE FOR ? |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 47) NOTE: PLEASE CONFIRM THE NUMBER OF CIRCUITS SHOWN |
| | ON UNIT PANELS WHICH SHOWS THESE AS 32 CIRCUIT PANELS. |
| | PLEASE SUBMIT SPEC/CUT SHEET FOR PANELS. |
| | 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 48) NOTE:PLEASE BE SURE TO SPECIFY FOOTER STEEL AS |
| | PART OF THE GROUNDING ELECTRODE SYSTEM PER 250.50 |
| | |
| | 49) NOTE: PLEASE SEE PANEL H2 IS NOT ON RISER AT |
| | MEZZANINE AS LISTED ON PANEL SCHEDULE. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 50) NOTE: PLEASE SEE RISER SHOWS 400AMP OVER CURRENT |
| | PROTECTION AND RISER UP TO EE AN EW PANELS YET NO |
| | INFORMATION WAS SHOWN ON HOW THESE WILL BE TAPPED OR |
| | CONNECTED. |
| | PLEASE SEE 240.4, 310.16, 240.21 AS THE TAPPED |
| | CONDUCTORS AS SHOWN ON FEEDER LEGEND AS #3 ARE NOT |
| | RATED FOR THE 125AMP BREAKER AT TERMINATION. |
| | |
| | 51) NOTE: PLEASE KNOW IT HAS COME TO OUR ATTENTION THAT |
| | THE PROPOSED PROJECT IS GOING FOR A LEED |
| | CERTIFICATION. |
| | PLEASE BE SURE TO PROVIDE INFORMATION AND ALL NOTES |
| | ABOVE WITH RESPECT TO FBC AND CHAPTER 13. |
| | |
| | 52) NOTE: PLEASE KNOW ONE SET OF ELECTRICAL PLANS |
| | CONTAINS MANY OF THE ABOVE ITEMS REDLINED HOWEVER NOT |
| | ALL. |
| | PLEASE ALSO KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| | SUBMITTED FOR REVIEW AND DUE TO THE FACT THERE WILL BE |
| | CHANGES TO PLANS THERE MAY VERY WELL BE NEW COMMENTS ON |
| | THE NEXT REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | 53) NOTE: PLEASE KNOW AS THIS A THRESHOLD PROJECT, |
| | THREE SETS OF PLANS, AND ALL SUPPORTING DOCUMENTS ARE |
| | REQUIRED TO BE SUBMITTED FOR REVIEW AND STAMPING. |
| | |
| | ** |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-02-13 11:33:17 | |
| | |
| | ONE ROLL IN ELECTRIC FOR REVIEW. |