Plan Review Notes
Plan Review Notes For Permit 08010592
Permit Number 08010592
Review Stop B
Sequence Number 1
Notes
Date Text
2008-03-17 12:37:10BUILDING PLAN REVIEW
 PERMIT: 08010592
 ADD: 510 4TH STREET
 CONT:TRENTO CONSTRUCTION CO
 TEL: (786)631-5616
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW ?PLAN REVIEW?
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3) PLEASE PROVIDE A COPY OF THE UNITY OF TITLE FOR
 BLOCK 16 OF PLAT CLOWS ADDITION, AND THE NORTHERN HALF
 OF 4TH STREET.THE UNITY OF TITLE SUBMITTED IS FOR
 BLOCK 27 OR THE SOUTH TOWER. NOTE, THE LANGUAGE IN THE
 UNITY OF TITLE FOR THE SOUTH BLOCK 27 THERE IS A TRUE
 PROPERTY LINE BETWEEN BLOCK 27 AND BLOCK 16 WHICH THIS
 BUILDING WILL BE BUILT UPON.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF OF TITLE' DOCUMENT SO
 THAT FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE
 DEEMED NOT APPLICABLE.
  
 4) THIS BUILDING IS TO BE CLASSIFIED AS A ?THRESHOLD
 BUILDING? BY FLORIDA STATUTE 553.71
 ANDREQUIRING 3 SETS OF ALL DOCUMENTS TO BE SUBMITTED
 TO THE BUILDING DEPARTMENT, PLANS ,REPORTS, PRODUCT
 APPROVALS AND SUBMITTALS. 109.3.6.*
  
 5)INFORMATIONAL: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) INFORMATIONAL: 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 7) SHEET AN-1.0:110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED. NOTE IF A BUILDING PERMIT IS NOT APPLIED FOR
 BEFORE OCT.1 2008 THE 2007 FLORIDA BUILDING CODE WILL
 BE ADOPTED AND ENACTED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 THIS BUILDING IS CLASSIFIED AS A MIXED USE OCCUPANCY,
 MISSING THE RETAIL ON THE FIRST FLOOR.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.COMPLIED.
 D) THE OCCUPANT LOAD, SEE 1004.
 E. ) NUMBER OF UNITS
 F ) NUMBER OF FLOORS
 G ) NUMBER OF BEDROOMS
 H ) NUMBER OF ROOMS
 I ) NUMBER OF BEDROOMS
 J ) SQ. FT. LIV SPACE/ FL
 K) SQ. FT. FOOTPRINT
 L ) TOTAL SQUARE FOOT WITHIN BUILDING
  
 7C) PLANS INDICATE THAT A SEPARATE PERMIT WILL BE
 REQUIRED FOR. NOTE THIS STRUCTURE IS DESIGNED AS AN
 ENCLOSED STRUCTURE WITH A INTERNAL PRESSURE COEFFICIENT
 OF +/-0.18 REQUIRING
 GLAZED OPENING PROTECTION TO COMPLETE THE ENVELOPE OF
 THE BUILDING, REQUIRING THE EXTERIOR WINDOWS AND DOORS
 AS PART OF THIS PERMIT PACKAGE, 106.3.5.1.1(8) BEFORE
 THE BUILDING PERMIT WILL BE ISSUED.
  
 8)SHEET AN-2.0:
 8A) GRIDLINE A & A.1 WHICH IS THE SOUTH BASEMENT WALL,
 NO WALL IDENTIFICATION TAGS.
  
 8B) NOTE, THERE CAN BE NO OPENINGS THROUGH TO THE SOUTH
 GARAGE, THIS IS A TRUE PROPERTY LINE, THERE IS NO
 LONGERA PUBLIC ACCESS RIGHT OF WAY, (PUBLIC STREET)
 SEE TABLE 704.8.
  
 8C) STAIRWELL# 1 PLEASE PROVIDE WALL IDENTIFICATION
 TAGS, 106.1.2 & 707.4.
  
 8D) STAIRWELL DOORS LISTED ON SHEET AN-8.0DOOR # 3 ARE
 INDICATED AS A ?B? LABEL DOOR REFLECTING THE AMBIENT
 TEMPERATURE RISE BUT THE DOOR SCHEDULE FAILS TO
 IDENTIFY IN HOURS THE ASSEMBLY RATING, PLEASE SEE TABLE
 715.3.
  
 8E) THE ELEVATOR DOORS LISTED ON SHEET AN-8.0 DOOR # 12
 ARE LISTED AS A ?B? LABEL DOOR BUT THE HOUR RATING IS
 NOT PROVIDED.
  
 8F) REFERENCE ** PLEASE CORRECT FROM THE SFBC AND
 SECTION TO THE CURRENT CODE.
  
 9) SHEET AN-2.1:
 9A) THIS SHEET INDICATES A DROP OFF OR LOADING ZONE AT
 THE FRONT CURB LINE. THIS SHEET NOR
 AN-1.2 INDICATE AACCESS AISLE 60 INCHES BY 20FEET,
 PLEASE SEE THE REQUIREMENTS
 OF 11-4.6.6. PLEASE SEE 11-4.29.5 DETECTABLE WARNINGS
 AT HAZARDOUS VEHICULAR AREAS.
  
 9B)PLEASE SEE STAIR#2 & STAIR#4, THEY BOTH DROP YOU
 OUTSIDE OF THE 2 HR RATED ENCLOSURE WHILE STILL WITHIN
 THE FOOTPRINT OF THE BUILDING. PLEASE SEE 403.13 AND
 1019.1.8.1. STAIRWELL# 4 ALSO DROPS YOU IN A TRAFFIC
 AREA WITH NO SIDEWALK OR WALKWAY.
  
 9C) THIS COMMENT WILL STAND FOR ALL EXIT ENCLOSURES 4
 STORIES OR MORE THAN HEIGHT, ALL DOORS THAT ARE
 DESIGNATED BY DOOR# 3 ARE TO BE 90 MINUTE OPENING
 PROTECTION SEE TABLE 715.3.
  
 9D) IN THE NORTHEAST CORNER OF THE GARAGE BY PARKING
 SPACE# 12 THERE IS A DOOR # 04 WHICH IS AN EXIT THAT
 ALSO LEADS DIRECTLY INTO THE TRAFFIC LANE WITH NO
 WALKWAYS LEADING TO THE PUBLIC WAY. SEE EXIT DISCHARGE&
 11-4.1.3(8)(A) &(B).
  
 9E) BOTH THE LAUNDRY ROOM AND TRASH ROOM ARE BOTH
 CONSIDERED TERMINATION ROOMS REQUIRING THE DOOR TO HAVE
 BE ? HR OPENING PROTECTION. SEE 707.13.4. THIS DOOR IS
 TO BE SELF-CLOSING OR AUTOMATIC CLOSING UPON THE
 DETECTION OF SMOKE.
  
 9F) DOORS THAT LEAD FROM THE LOBBY INTO THE PARKING
 GARAGE ARE LED INTO THE GARAGE BY DOOR# 14, PLEASE
 CORRECT THE DOOR SCHEDULE AND PROVIDE HR RATING SEE
 TABLE 302.3.2 AND TABLE 715.3.
  
 9G) THE RETAIL TENANT SPACE WITH 828 SQ FT IS INDICATED
 WITH THE TENANT SEPARATION WALLS AS NON-RATED WALLS,
 PLEASE SEE 708.3.& 302.2.
  
 9H) THE FIRE CONTROL ROOM IS TO BE SEPARATED BY A
 1-HOUR RATED WALL AND OPENING PROTECTIVES. SEE DOOR 15
 IS NOT PROVIDED IN HOURS THE FIRE RATING PLEASE
 CORRECT, TABLE 715.3.
  
 9I) MISSING WALL IDENTIFICATION TAG FOR THE WALL THAT
 SEPARATES THE LOBBY ANDBICYCLE STORAGE AREA.
  
 9J)RESTROOMS NEXT TO BICYCLE STORAGE NEED ACCESSIBLE
 RESTROOMS11-4.16. SHOWER ROOMS NEXT TO THE BICYCLE
 STORAGEPLEASE SEE 11-4.21.7. CURBS. 11-4.21.4 GRAB
 BARS. THE
 RESTROOMS ARE MISSING THE SINK IN THE STALL, SEE
 FLORIDA ACCESSIBILITY COMMON AREAS 11-4.22.4/
 11-4.17.3.& 11-4.13.7 DOORS IN SERIES.
  
 9K) FIRE PUMP ROOM IS INDICATED AS A LOUVER IN THE 2 HR
 RATED WALL AND NOTE TO SEE MECHANICAL PLAN MN-2.04 NO
 MENTION OF FIRE DAMPER IN THE RATED WALL. SEE TABLE
 716.3.1.
  
 9L) DOOR # 16 THE BACK OF THE RETAIL TENANT SPACES AND
 THE DOOR LEADING TO THE MEETING ROOM IS IDENTIFIED AS
 DOOR TYPE M A PAIR OF LOUVERED DOORS. PLEASE SEE TENANT
 SEPARATION REQUIREMENTS AND RATINGS.
  
 10) SHEET AN2.2:
 10A) PLEASE PROVIDE CALCULATIONS FOR WHAT AREA IS TO BE
 CONSIDERED A MEZZANINE. SEE 505.2
 THE AGGREGATE AREA OF A MEZZANINE WITHIN A ROOM SHALL
 NOT EXCEED ONE-THIRD OF THE AREA OF THAT ROOM OR SPACE
 IN WHICH THEY ARE LOCATED. IT APPEARS THIS IS A SECOND
 FLOOR.
  
 10B) DOOR # 14 IS THE REFUSE CHUTE ACCESS ROOM
 REQUIRING A ? HR OPENING PROTECTIVE. PLEASE CORRECT
 DOOR SCHEDULE DOOR CLASSIFICATION AND RATING 707.13.3.
  
 10C) THE REFUSE SHAFT WALL IS NOT TAGGED ON THIS SHEET.
 707.4.
  
 10D)STAIR# 4 THE MEZZANINE LEVEL IT APPEARS THAT
 WITHIN THE STAIRWELL THERE IS A WALL NOT RATED, THIS
 WALL APPEARS TO BE THE EXIT PASSAGE WAY ON THE FIRST
 FLOOR LEVEL AND PART OF THE EXIT ENCLOSURE. PLEASE TURN
 TO PN-2.05 IT APPEARS THAT WITHIN THE ENCLOSURE THERE
 ALSO RUNS A 3? SANITARY STACK AND AIR ADMITTANCE
 DEVICE. 707.7.1 & 1019.1.2.
  
 10E) PLEASE SEE STAIRWELL# 3 AND 3 INCH STACK IN
 STAIRWELL, 707.7.1 & 1019.1.2.
  
 10F)STAIRWELL# 1THE MEZZANINE LEVEL APPEARS AGAIN
 TO HAVE A LARGE VOID SPACE FROM THE FIRST FLOOR, PLEASE
 SEE PN-2.06 WHERE BOTH A 3? AND 4? RISER DROP BELOW THE
 2ND FLOOR SLAB AND ARE PICKED UP IN THE MEZZANINE LEVEL
 STAIRWELL, MEZZANINE LEVEL VOID. SEE 707.7.1 &
 1019.1.2.
  
 11) SHEET AN-2.3:
 11A) THIS COMMENT WILL STAND FOR THE 2ND THROUGH THE
 8TH FLOORS, MISSING THE REQUIRED ELEVATOR LOBBY:
 707.14.1ELEVATOR LOBBY. ELEVATORS OPENING INTO A
 FIRE-RESISTANCE-RATED CORRIDOR AS REQUIRED BY SECTION
 1016.1 SHALL BE PROVIDED WITH AN ELEVATOR LOBBY AT EACH
 FLOOR CONTAINING SUCH A CORRIDOR. THE LOBBY SHALL
 SEPARATE THE ELEVATORS FROM THE CORRIDOR BY FIRE
 PARTITIONS AND THE REQUIRED OPENING PROTECTION.
 ELEVATOR LOBBIES SHALL HAVE AT LEAST ONE MEANS OF
 EGRESS COMPLYING WITH CHAPTER 10 AND OTHER PROVISIONS
 WITHIN THIS CODE.
 SEE ALSO CODE COMMENTARY.
  
 11B) THIS COMMENT WILL STAND FOR THE 2ND THROUGH THE
 8TH FLOORS,VARIOUS CONDO UNITS DO NOT PROVIDE WALL
 TAGS IDENTIFYING THE WALLS BETWEEN UNITS AND OR UNITS
 AND ASSOCIATED ROOMS SUCH AS THE MEETING ROOMS AND OR
 BUSINESS CENTER.
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC ) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 11C) THIS COMMENT WILL STAND FOR THE 2ND THROUGH THE
 8TH FLOORS. PROVIDE INFORMATION AS TO HOW CODE
 COMPLIANCE WILL BE ACHIEVED FOR : 1207.3
 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 11D) EAST END OFTHE BUILDING TENANT STORAGE UNIT AND
 DOOR#18 ARE TO RESIST THE PASSAGE OF SMOKE PLEASE
 PROVIDE SEE 302.1.1.1 AND 710.5.2.
  
 11E) EAST END OF THE BUILDING THE MAIN ELECTRIC ROOM
 WALL COMMON TO CONDO UNIT IS INDICATED TO BE A ?P-2?
 TYPE PARTITION, PLEASE PROVIDE THE STC RATING FOR THIS
 WALL 1207.2
 AIR-BORNE SOUND.
  
 12)SHEET AN-2.4:
 12A) GRID LINE O-4 THERE IS A ROOM THAT IS NOT
 IDENTIFIED THE MECHANICAL PLAN INDICATES A MECHANICAL
 ELECTRICAL ROOM. 106.1.2. ADDITIONAL INFORMATION
 REQUIRED.
  
 12B) JUST ADJACENT THERE APPEARS TO BE A SPACE OR VOID
 AREA THAT APPEARS TO BE A SHAFT, ADDITIONAL INFORMATION
 REQUIRED, 106.1.2.THIS COMMENT WILL SERVE FOR ALL
 FLOORS.
  
 12C) THE LINEN ACCESS ROOM AND REFUSE ACCESS ROOMS ARE
 NOT IDENTIFIED NOR WALL TAGS PROVIDED WITH WALL
 RATINGS, PLEASE IDENTIFY.707.13.3.
  
 12D) GRID LINE G1 BETWEEN 15& 16 THERE IS A VOID SPACE
 ON THIS PLAN PLEASE IDENTIFY THIS SPACE IT APPEARS THIS
 MAY BE A SHAFT REQUIRING 2 HR CONSTRUCTION. 707.4. THIS
 AREA DOES APPEAR TO BE CONSISTENT ON ALL FLOORS .THIS
 COMMENT WILL SERVE FOR ALL FLOORS.
  
 12E) GRID LINE G BETWEEN 3 & 4 APPEAR TO HAVE THE SAME
 VOID AREA IS SHAFT WALL CONSTRUCTION REQUIRED TO BE 2
 HR. 707.4. THIS COMMENT WILL SERVE FOR ALL FLOORS.
  
 12F) GRID LINE N & 15.1 IT APPEARS TO BE A VOID SPACE
 IS THIS SHAFT WALL CONSTRUCTION REQUIRED TO BE 2 HR
 707.4. THIS COMMENT WILL SERVE FOR ALL FLOORS.
  
 13) SHEET AN-2.8ROOF DECK:
 13A)NOTE THERE ARE TWO AREAS OF THE ROOF THAT HAVE ROOF
 DRAINS BUT NO OVERFLOW EMERGENCY SCUPPERS:
 13A) (1) ON GRID LINE E2 JUST TO THE RIGHT OF
 ELEVATOR# 5.
 13A)(2) NORTH OF GRID LINE M AND EAST OF GRID LINE
 13,
 IN BOTH CASES THE SURROUNDING OVERFLOW SIZE HAS STAYED
 THE SAME BUT THE VOLUME THAT WOULD HAVE BEEN DOUBLED
 ISN?T INDICATED WITH LARGER OVERFLOW SCUPPERS? 1503.4.
  
 13B) ELEVATOR# 5 INDICATES AN ELEVATOR EQUIPMENT ROOM
 WITH NO WALL RATINGS, PLEASE SEE
 3006.4.
  
 13C) POOL DECK SHEET AN-6.2 INDICATES THE ELEVATOR AND
 POOL DECK, WITH A STORAGE ROOM
 WHAT HAPPENS TO THE ELEVATOR HOIST WAY TO THE WEST SIDE
 DOES IT ALSO BECOME A SINGLE ELEVATOR TO THIS FLOOR
 LEVEL?
  
 13D)FOR THE METAL STAIRS AND GRANDSTAND PLEASE
 PROVIDE THE MINIMUM LIVE LOADS THESE AREAS ARE TO BE
 DESIGNED TO. ONCE THESE FACTORS ARE KNOWN SHOP DRAWINGS
 TO FOLLOW AFTER PERMITTING. TABLE 1607.1.
 13E) THE 48? HIGH POOL GATE SEPARATING THE SKY CINEMA
 AND POOL DECK IS MISSING THE 18?
 ON THE LATCH SIDE. SEE A117.1 98 TABLE 404.2.4.1 FIGURE
 404.2.4.1(A).
  
 13F) SHEET AN-7.5 THE RESTROOMS ARE MISSING THE SINK IN
 THE STALL, SEE FLORIDA ACCESSIBILITY COMMON AREAS
 11-4.22.4/ 11-4.17.3.
  
 14) STAIR IDENTIFICATION:
 14A) PLEASE SEE 1019.1.6 FOR REQUIREMENTS FOR AN
 APPROVED BARRIER AT THE LEVEL OF EXIT DISCHARGE TO
 PREVENT PERSONS FROM UNINTENTIONALLY CONTINUING INTO
 THE LEVELS BELOW.
 THIS COMMENT WILL HOLD FOR ALL STAIRS THAT LEAD BELOW
 GRADE.
  
 14B) STAIR FLOOR NUMBERING SIGNAGE REQUIRED PLEASE SEE
 1019.1.7 FOR REQUIRED SIGNAGE, FLOOR LEVEL, THE
 TERMINUS OF THE TOP AND BOTTOM OF THE STAIR ENCLOSURE
 AND THE IDENTIFICATION OF THE STAIR AND AVAILABILITY OF
 ROOF ACCESS. THIS STATEMENT WILL SERVE FOR ALL
 STAIRWELLS AFFECTED.
  
 14C) 1019.1.8 PLEASE SEE 1019.1.8 SMOKE PROOF
 ENCLOSURES. PLEASE PROVIDE CODE COMPLIANCE FOR SMOKE
 PROOF ENCLOSURES OR PRESSURIZED STAIRWAY IN ACCORDANCE
 WITH 909.20.
  
 15) SHEET AN-6.9
 15A) DETAIL# 8 INDICATES THE USE OF 3/4INCH CDX PLYWOOD
 SHEATHING. PLEASE SEE TABLE 601 FOOTNOTE ?(2). PLEASE
 PROVIDE WHAT TYPE OF SHEATHING WILL BE USED SINCE THE
 CDX PLYWOOD WILL NOT MEET THE REQUIREMENT F FOOTNOTE
 ?C?
  
 15B) PLEASE NOTE THAT ANY FABRIC CANOPIES SHOWN ON THE
 PLANS WILL REQUIRE A SEPARATE PERMIT AND ASSOCIATED
 FEES. 108.3.
  
 16) SHEET AN-6.13:
 16A) THE PLANS INDICATE THE USE OF 4X10, 4X12 CYPRESS
 WOOD BEAMS AND T& G SHEATHING.
 PLEASE SEE THE REQUIREMENTS FOR USING FIRE RETARDANT
 TREATED WOOD IN TYPE I-A BUILDINGS
 SEE TABLE 601 FOOTNOTE( C )(2) (III) .
  
 16B) NOTE THAT AS DETAILED THE ROOFING NAILS WILL
 PENETRATE THE T&G SHEATHING AND WILL BE VISIBLE. SEE
 1507.3.6THE FASTENER SHALL PENETRATE THE DECK A
 MINIMUM OF 0.75 INCHES OR
 THROUGH THE THICKNESS OF THE DECK, WHICHEVER IS LESS.
  
  
 17) AN-6.16:
 17A) THE PLANS SHOW SEVERAL CUT DETAILS SECTION G SHEET
 A9.1 THIS SHEET IS MISSING FROM THE PLANS, IT IS SHOWN
 ON THE INDEX SHEET.
  
 17B) THE MISSING SHEET A9.1 SECTION G & K DOES NEED TO
 SHOW COMPLIANCE WITH FLASHINGS SEE 1405.3. SEE SILLS,
 PROJECTING TRIM AND COPINGS.
  
 17C)DETAIL G SHEET A9.2 IS A TYPICAL SLIDING GLASS
 DOOR DETAIL, PLEASE SEE COMMENT ABOVE ABOUT FLASHINGS.
 THE REAL ISSUE IS HOW YOU INTEND TO COMPLY WITH FAIR
 HOUSING,
 SLIDING SECONDARY DOORS AT CONCRETE LANDINGS. FROM THE
 INTERIOR FINISH FLOOR TO THE TOP OF THE TRACK THE
 HEIGHT CHANGE IS TO BE I/4? IT CAN BE ?? IF A FILLER
 WITH A 1:2 SLOPE IS APPLIED.
 THEN THE MAX DROP OF 4? TO THE FINISHED CONCRETE
 BALCONY DECK BELOW. SEE ATTACHMENT.
 THE FAIR HOUSING ACT MADE IT LAW A NATIONAL STANDARD
 FOR BUILDINGS AND FACILITIES PROVIDING ACCESSIBILITY
 AND USABILITY FOR PHYSICALLY HANDICAPPED PEOPLE. THE
 GUIDELINES ARE NOT MANDATORY BUT INTENDED TO PROVIDE A
 SAFE HARBOR FOR COMPLIANCE WITH THE ACCESSIBILITY
 REQUIREMENTS OF THE FAIR HOUSING ACT.
  
 ATTACHED IS ONE OTHER METHOD OF MEETING THESE
 REQUIREMENTS. IT HAS BEEN REVIEWED BY THE CITY?S
 ATTORNEYS AS WELL AS REVIEW BY FAIR HOUSING, NOTE THIS
 DOCUMENT DOES HAVE TO BE RECORDED BY THE COUNTY CLERK.
  
 18) SHEET AN-9.4, DETAILS FOR EXPANSION JOINT
 MATERIALS, PLEASE PROVIDE MANUFACTURERS SPEC FOR FIRE
 RATING OF SLABS TABLE 601. 3HR FLOOR CONSTRUCTION, 1 HR
 REDUCTION FOR FIRE SPRINKLERS.
  
 19)SHEET AN-2.21: THIS COMMENT WILL BE FOR ALL
 FLOORS.
 19A) THIS SHEET DOES NOT IDENTIFY THE SECONDARY SLIDING
 GLASS DOORS LEADING TO THE UNIT BALCONIES. 106.1.2
 ADDITIONAL INFORMATION REQUIRED. PLEASE SEE DOOR
 SCHEDULE LOCATED ON SHEET AN-8.0.SLIDING GLASS DOORS
 NUMBERED 9 & 10 WILL REQUIRE A CLEAR MEASUREMENT OF 32?
 FAIR HOUSING ANSI A117.1-1998 404.2.3. CLEAR WIDTH.
  
 19B) PLEASE ALSO INDICATE COMPLIANCE WITH ANSI
 A117.1-98 SECTION 404.2.7 COMPLIANCE WITH DOOR HARDWARE
 FOR SLIDING GLASS DOORS.
  
 20) SHEET AN-2.23- AN-2.30 THE DOORS TO THE INTERIOR
 OF THE UNITS ARE NOT IDENTIFIED PER THE DOOR SCHEDULE.
 ADDITIONAL INFORMATION REQUIRED, 106.1.2.FAIR HOUSING
 CHAPTER # 4.
  
 21) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 22) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
  
 A) FIXED GLASS
 B) STOREFRONT
 C) CASEMENT WINDOWS
  
  
 D) MULLIONS- IF NOT PART OF THE PRODUCT APPROVAL
 1714.5.5.2 LOAD TRANSFER. MULLIONS SHALL BE
 DESIGNED TO TRANSFER THE DESIGN PRESSURE
 LOADS APPLIED BY THE WINDOW AND DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBSTRATE.
  
 1714.5.5.4 STRUCTURAL SAFETY FACTOR.
 MULLIONS SHALL BE CAPABLE OF RESISTING A LOAD OF
 ONE-AND-ONE-HALF TIMES THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR
 ASSEMBLIES TO BE SUPPORTED WITHOUT
 EXCEEDING THE APPROPRIATE MATERIAL STRESS LEVELS.
 IF TESTED BY AN APPROVED LABORATORY,
 THE ONE AND ONE-HALF TIMES THE DESIGN PRESSURE
 LOAD SHALL BE SUSTAINED FOR 10
 SECONDS, AND THE PERMANENT DEFORMATION SHALL NOT
 EXCEED 0.4 PERCENT OF THE MULLION
 SPAN AFTER THE ONE-AND-ONE-HALF TIMES DESIGN
 PRESSURE LOAD IS REMOVED.
  
 E) WALL LOUVERS
 F) GLAZED DOORS
 G) GLAZED DOORS WITH SIDELIGHTS
 H) SLIDING GLASS DOORS
 22I) EXTERIOR SWING METAL DOORS
 EXTERIOR DOOR ASSEMBLIES NOT COVERED BY SECTION
 1715.4.2 OR SECTION 1714.5.3.1
 SHALL BE TESTED FOR STRUCTURAL INTEGRITY IN
 ACCORDANCE WITH ASTM E 330 PROCEDURE A,
 AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN
 PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED
 FOR 10 SECONDS WITH NO PERMANENT DEFORMATION OF
 ANY MAIN FRAME OR PANEL MEMBER
 IN EXCESS OF 0.4 PERCENT OF ITS SPAN AFTER THE
 LOAD IS REMOVED. HIGH-VELOCITY HURRICANE
 ZONES SHALL COMPLY WITH TAS 202. AFTER EACH
 SPECIFIED LOADING, THERE SHALL BE NO
 GLASS BREAKAGE, PERMANENT DAMAGE TO FASTENERS,
 HARDWARE PARTS, OR ANY OTHER
 DAMAGE WHICH CAUSES THE DOOR TO BE INOPERABLE.
 THE MINIMUM TEST SIZES AND MINIMUM DESIGN
 PRESSURES SHALL BE AS INDICATED IN
 TABLE 1714.5.3 .
 22J) EXTERIOR ROLL UP DOORS
 22K) ROOFING ASSEMBLIES:
 1) FLAT ROOFING SYSTEMS
 2)ROOFING TILE & UNDERLAYMENT?S
 PLEASE SUBMIT INFORMATION ON HOW THE
 RIDGE TILE ARE GOING TO BE SECURED TO THE
 ROOFING SYSTEM.1507.3.7 ATTACHMENT.
 CLAY AND CONCRETE ROOF TILES SHALL BE
 FASTENED IN ACCORDANCE WITH SECTION
 1609 OR IN ACCORDANCE WITH FRSA/RTI
 INSTALLATION MANUAL. 1507.3.8
 APPLICATION. TILE SHALL BE APPLIED ACCORDING TO THE
 MANUFACTURER?S INSTALLATION
 INSTRUCTIONS OR RECOMMENDATIONS OF THE
 FRSA/RTI 07320- 04.
 3) ROOFING FASTENERS- SPRAYED OR MECHANICAL
 4) PRE-ENGINEERED A/C STANDS
  
 23)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 24) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 25) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  