Plan Review Notes
Plan Review Notes For Permit 08010591
Permit Number 08010591
Review Stop P
Sequence Number 1
Notes
Date Text
2008-02-26 18:57:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH ARCHITECT TRO JUNG BRANNEN TITLE
 BLOCK. THE BUSINESS LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), AND THE DATE THE PLANS ARE PREPARED ARE
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.004(2)(4) AND FS 481.219, 481.2055.
  
 2. PLANS SHOW DEMOLITION OF EXISTING FLOOR PLANS, (1ST
 & 2ND) AND A NEW PORTE COCHERE. THIS IS NOT INDICATED
 ON THE PERMIT APPLICATION WHICH STATES "DESCRIBE
 PROJECT IN DETAIL". PLEASE INDICATE ALL WORK ON THE
 APPLICATION THAT WILL BE PERMITTED AT THIS TIME. ALSO
 INDICATE THE SQUARE FOOTAGE OF THE ADDITIONS. (SEE
 INFORMATION REQUIRED ON APPLICATION.
  
 3. IN THE INSTALLATION OR REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SECTION
 704.5. ON SHT P2 THERE APPEAR TO BE DEAD ENDS STILL IN
 THE SANITARY SYSTEM.
  
 4. THE STAFF TOILET SHALL BE ACCESSIBLE PER SECTION
 11-4.1.3(11). SUBMIT A DETAIL FOR ALL TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
  
 5. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE THE LOCATION OF THE REQUIRED DRINKING
 FOUNTAIN.
  
 6. SHT P2 DETAILS P1 & P2 THE GREASE TRAP IS NOT
 APPROVED. PER ARTICLE III SECTION 90-124(7)(B) GREASE
 INTERCEPTORS ARE TO BE INSTALL OUTSIDE WITH THE
 DISHWASHER DISCHARGING VIA A SEPARATE LINE. THE GREASE
 INTERCEPTOR SHALL BE CONSTRUCTED OF STEEL REINFORCED
 CONCRETE PER ARTICLE III SECTION 90-124(7)(F). THE
 GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY DEPT.
 INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT RODNEY COMPO (561) 644-1821 OR BY FAX
 (561) 822-2287 OR BY E-MAIL [email protected].
  
 7. SHT P2 INDICATE WHAT WILL BE DRAINING INTO THE FD-B
 IN THE MECHANICAL ROOMS. A TRAP SEAL SHALL BE INSTALLED
 WHERE THE TRAP IS SUBJECT TO EVAPORATION. CONDENSATE
 SHALL NOT DRAIN INTO THE SANITARY SYSTEM. ARTICLE III
 SECTION 90-125(5).
  
 8. SHT P2 A VENT IS REQUIRED FOR THE FD-B IN MECHANICAL
 ROOM 115.
  
 9. ROUTE PLANS TO THE PALM BEACH COUNTY HEALTY UNIT
 DIVISION OF ENVIRONMENTAL HEALTH, 901 EVERNIA STREET
 WEST PALM BEACH FOR REVIEW PRIOR TO RESUBMITTING FOR
 REVIEW AT THE CITY WPB.SECTION 102.2.1. PLANS SHALL
 BE STAMPED FOR REVIEW BY THE HEALTH DEPT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved