| Plan Review Notes For Permit 08010591 |
| Permit Number |
08010591 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-11 09:38:35 | PLAN DENIED | | | 1)PLEASE PROVIDE DUCT SIZES ON ALL DUCTS AND GRILLS | | | ON PLANS . | | | 2)PLEASE PROVIDE BATH EXHAUST AND TERMINATION OF | | | EXHAUEST DUCT ON PLANS .SECTION 402.3.1 2004 FBC (M). | | | 3)PLEASE SUBMIT A COPY OF MANUFACTURERS INSTALLATION | | | INSRUCTIONS ON THE AIR CONDITIONING EQUIPNENT WITH THE | | | PLANS . | | | 4)PLEASE SUBMIT ENERGY CALCULATIONS WITH THE | | | PLANS.SECTION 13-400.0.A | | | 5)PLEASE REFER TO MUNICIPAL CODE ARTICLE 3 SECTION | | | 90-125 PROHIBITIONS AND LIMITATIONS OF DISCHARGE ( B) | | | (5). (CAN NOT TIE A/C CONDENSATE IN A FLOOR DRAIN) 6) | | | PLAESE EXPLAIN WHAT DUCT IS 32 X16 AND 18 X16 WITH | | | INSULATION IS. PAGE M1 ON MECHANICAL PLANS. | | | 7) PAGE M4 MECHANICAL SPECIFICATIONS NOTE # 9 | | | FIBERGLASS DUCT CAN NOT BE PAINTED SECTION 604.3 FBC | | | (M) 2004 |
|