Plan Review Notes
Plan Review Notes For Permit 08010591
Permit Number 08010591
Review Stop M
Sequence Number 1
Notes
Date Text
2008-03-11 09:38:35PLAN DENIED
 1)PLEASE PROVIDE DUCT SIZES ON ALL DUCTS AND GRILLS
 ON PLANS .
 2)PLEASE PROVIDE BATH EXHAUST AND TERMINATION OF
 EXHAUEST DUCT ON PLANS .SECTION 402.3.1 2004 FBC (M).
 3)PLEASE SUBMIT A COPY OF MANUFACTURERS INSTALLATION
 INSRUCTIONS ON THE AIR CONDITIONING EQUIPNENT WITH THE
 PLANS .
 4)PLEASE SUBMIT ENERGY CALCULATIONS WITH THE
 PLANS.SECTION 13-400.0.A
 5)PLEASE REFER TO MUNICIPAL CODE ARTICLE 3 SECTION
 90-125 PROHIBITIONS AND LIMITATIONS OF DISCHARGE ( B)
 (5). (CAN NOT TIE A/C CONDENSATE IN A FLOOR DRAIN) 6)
 PLAESE EXPLAIN WHAT DUCT IS 32 X16 AND 18 X16 WITH
 INSULATION IS. PAGE M1 ON MECHANICAL PLANS.
 7) PAGE M4 MECHANICAL SPECIFICATIONS NOTE # 9
 FIBERGLASS DUCT CAN NOT BE PAINTED SECTION 604.3 FBC
 (M) 2004