Plan Review Notes
Plan Review Notes For Permit 08010591
Permit Number 08010591
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-17 13:46:00*****DENIED*****
  
  
 1.THE ADDRESS FOR THE SCOPE OF WORK LOCATION SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.PROVIDE THE OCCUPANCY TYPE AND OCCUPANT LOAD FOR
 THE NEW ONE STORY MULTI-PURPOSE ROOM AND THE NEW ONE
 STORY DINING ROOM.
  
 4.SPECIFY THE INTERIOR WALL AND CEILING FINISH FOR
 THE NEW AND RENOVATED AREAS IN TERMS OF CLASS A, CLASS
 B, OR CLASS C.
  
 5.SPECIFY THE INTERIOR FLOOR FINISH FOR THE NEW AREAS
 IN TERMS OF CLASS I OR CLASS II.
  
 6.PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCES
 TO THE EXITS.
  
 7.SHOW THE LOCATIONS OF THE 2A:10BC RATED FIRE
 EXTINGUISHERS WHICH SATISFIY THE 75' TRAVEL DISTANCE.
  
 8.PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM FOR THE
 PROPOSED SCOPE OF WORK.PLEASE BE ADVISED THAT
 SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE FIRE
 ALARM/FIRE SPRINKLER REMODEL OR INSTALLATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE APPROPIATE PLAN SHEET)
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722