| Date |
Text |
| 2008-02-11 10:29:42 | ** DENIED REVIEW ** |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| | SUBMITTED FOR REVIEW OR IN DESIGN AS REQUIRED THERE MAY |
| | VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE POSSIBLY MADE AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING RELEVANT CODES ARE |
| | REQUIRED TO BE STATED ON PLANS INCLUSIVE OF ELECTRICAL |
| | AS WELL AS ARCHITECTURAL SHEETS. |
| | 2004 FBC W/2007 REVISIONS/SUPPLEMENTS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE LICENSE INFORMATION IN TITLE BLOCKS |
| | FOR ARCHITECTURAL/ENGINEER FIRM TRO/ JUNG/BRANNEN PER |
| | FLORIDA ADMINISTRATIVE CODES 61G1-16.004 (ARCH) AND |
| | 61G15-23.002 (ENG). PLEASE SEE MISSING LICENSES KNOWN |
| | AS CERTIFICATE OF AUTHORIZATION NUMBERS AS REQUIRED PER |
| | FLORIDA STATUTES 481.219 (ARCH) AND 471.023 (ENG). |
| | PLEASE SEE THIS COMMENT IS NOT FOR FORNEY ENGINEERING |
| | INC. ALTHOUGH INFORMATION IS STILL REQUIRED ON MEP |
| | SHEETS AS WELL DUE TO TITLE BLOCKS AS SUBMITTED. |
| | |
| | 3) NOTE: PLEASE SEE THAT IF BUILDING CONTAINS A FIRE |
| | ALARM SYSTEM, PLEASE INCLUDE LOCATIONS FOR ALL |
| | HORN/STROBE DEVICES AS REQUIRED PER FBC 11-4.28.1,.2 |
| | AND .3(4). PLEASE ALSO SEE NFPA-72 |
| | PLEASE INCLUDE NOT ONLY LOCATIONS BUT THE MINIMUM |
| | LEVELS FOR ADA COMPLIANCE AS GIVEN. |
| | ** BUILDING DOES APPEAR TO BE A BUILDING WHICH HAS A |
| | REQUIRED SYSTEM. |
| | |
| | 4) NOTE: PLEASE SEE MISSING LIGHTING CONTROLS FOR ALL |
| | NEW LIGHTING CONTROLS BEING INSTALLED PER 13-415.1.ABC |
| | .1.1, .1.2, .1.3 AND .1.4. |
| | PLEASE SEE .1.1-.1.3 FOR INTERIOR LIGHTING AND .1.4 FOR |
| | EXTERIOR. EXTERIOR LIGHTING REQUIRES ONE OF TWO TYPES |
| | OF CONTROL FOR MINIMUM COMPLIANCE. (MAY BE BOTH) PLEASE |
| | SEE THAT THE PLANS DO NOT SHOW AN ASTRONOMICAL TIME |
| | CLOCK WITH THE 10HR BATTERY BACK UP AS NEEDED. |
| | ** PLEASE BE SURE ALL DEVICES OR SYSTEM DEPENDING ON |
| | DESIGN CONTAINS ALL MAXIMUM TIMES ON DEVICES, OVER |
| | RIDES AND ANY TIMED SCHEDULING. |
| | ** AS NO SYSTEM OR DEVICES ARE SHOWN, NO REVIEW OF |
| | THESE CAN BE DONE. |
| | |
| | 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS AS REQUIRED PER 13-415.2. PLEASE BE SURE |
| | TO SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR EXTERIOR |
| | LIGHTING. |
| | PLEASE BE SURE TO COORDINATE ALL LIGHTING ON PLANS WITH |
| | THAT OF THE FIXTURE LEGEND AND THE CALCULATIONS TO BE |
| | SUBMITTED. |
| | PLEASE SEE 13-415.1.B, 13-415.1.C. |
| | |
| | 6) NOTE: PLEASE SEE KEYED NOTES ON RISER ARE NOT |
| | COMPLETE FOR NEW FEEDERS ON ALL CONDUITS. THIS CAN NOT |
| | BE ASSUMED. |
| | PLEASE COMPLETE. |
| | 240.4, 310.16 ETC |
| | FBC 106.3.5.1.2 |
| | |
| | 7) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS NOT |
| | ONLY FOR NEW ADDING TO EXISTING SERVICE AS REQUIRED PER |
| | 220.87 BUT ALSO FOR THE CONTINUOUS LOADS WHICH ARE |
| | REQUIRED TO BE SHOWN AT 125%. 215.3, 230.42 ETC. |
| | |
| | 8) NOTE: PLEASE SEE 210.8B2 FOR 15/20AMP 120VOLT |
| | RECEPTACLES IN KITCHEN AREAS WHETHER OR NOT THEY FEED |
| | COUNTER SPACE RECEPTACLES OR WHETHER OR NOT THEY ARE |
| | LOCATED WITHIN 6FT OF ANY SINKS. |
| | |
| | 9) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLACE |
| | NOTES ON PLANS ACCORDINLY. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW IF |
| | THERE ARE ANY QUESTIONS; PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |