Plan Review Notes
Plan Review Notes For Permit 08010591
Permit Number 08010591
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-11 10:29:42** DENIED REVIEW **
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED FOR REVIEW OR IN DESIGN AS REQUIRED THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE POSSIBLY MADE AT THIS TIME.
  
 1) NOTE: PLEASE SEE THE FOLLOWING RELEVANT CODES ARE
 REQUIRED TO BE STATED ON PLANS INCLUSIVE OF ELECTRICAL
 AS WELL AS ARCHITECTURAL SHEETS.
 2004 FBC W/2007 REVISIONS/SUPPLEMENTS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE LICENSE INFORMATION IN TITLE BLOCKS
 FOR ARCHITECTURAL/ENGINEER FIRM TRO/ JUNG/BRANNEN PER
 FLORIDA ADMINISTRATIVE CODES 61G1-16.004 (ARCH) AND
 61G15-23.002 (ENG). PLEASE SEE MISSING LICENSES KNOWN
 AS CERTIFICATE OF AUTHORIZATION NUMBERS AS REQUIRED PER
 FLORIDA STATUTES 481.219 (ARCH) AND 471.023 (ENG).
 PLEASE SEE THIS COMMENT IS NOT FOR FORNEY ENGINEERING
 INC. ALTHOUGH INFORMATION IS STILL REQUIRED ON MEP
 SHEETS AS WELL DUE TO TITLE BLOCKS AS SUBMITTED.
  
 3) NOTE: PLEASE SEE THAT IF BUILDING CONTAINS A FIRE
 ALARM SYSTEM, PLEASE INCLUDE LOCATIONS FOR ALL
 HORN/STROBE DEVICES AS REQUIRED PER FBC 11-4.28.1,.2
 AND .3(4). PLEASE ALSO SEE NFPA-72
 PLEASE INCLUDE NOT ONLY LOCATIONS BUT THE MINIMUM
 LEVELS FOR ADA COMPLIANCE AS GIVEN.
 ** BUILDING DOES APPEAR TO BE A BUILDING WHICH HAS A
 REQUIRED SYSTEM.
  
 4) NOTE: PLEASE SEE MISSING LIGHTING CONTROLS FOR ALL
 NEW LIGHTING CONTROLS BEING INSTALLED PER 13-415.1.ABC
 .1.1, .1.2, .1.3 AND .1.4.
 PLEASE SEE .1.1-.1.3 FOR INTERIOR LIGHTING AND .1.4 FOR
 EXTERIOR. EXTERIOR LIGHTING REQUIRES ONE OF TWO TYPES
 OF CONTROL FOR MINIMUM COMPLIANCE. (MAY BE BOTH) PLEASE
 SEE THAT THE PLANS DO NOT SHOW AN ASTRONOMICAL TIME
 CLOCK WITH THE 10HR BATTERY BACK UP AS NEEDED.
 ** PLEASE BE SURE ALL DEVICES OR SYSTEM DEPENDING ON
 DESIGN CONTAINS ALL MAXIMUM TIMES ON DEVICES, OVER
 RIDES AND ANY TIMED SCHEDULING.
 ** AS NO SYSTEM OR DEVICES ARE SHOWN, NO REVIEW OF
 THESE CAN BE DONE.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS AS REQUIRED PER 13-415.2. PLEASE BE SURE
 TO SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR EXTERIOR
 LIGHTING.
 PLEASE BE SURE TO COORDINATE ALL LIGHTING ON PLANS WITH
 THAT OF THE FIXTURE LEGEND AND THE CALCULATIONS TO BE
 SUBMITTED.
 PLEASE SEE 13-415.1.B, 13-415.1.C.
  
 6) NOTE: PLEASE SEE KEYED NOTES ON RISER ARE NOT
 COMPLETE FOR NEW FEEDERS ON ALL CONDUITS. THIS CAN NOT
 BE ASSUMED.
 PLEASE COMPLETE.
 240.4, 310.16 ETC
 FBC 106.3.5.1.2
  
 7) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS NOT
 ONLY FOR NEW ADDING TO EXISTING SERVICE AS REQUIRED PER
 220.87 BUT ALSO FOR THE CONTINUOUS LOADS WHICH ARE
 REQUIRED TO BE SHOWN AT 125%. 215.3, 230.42 ETC.
  
 8) NOTE: PLEASE SEE 210.8B2 FOR 15/20AMP 120VOLT
 RECEPTACLES IN KITCHEN AREAS WHETHER OR NOT THEY FEED
 COUNTER SPACE RECEPTACLES OR WHETHER OR NOT THEY ARE
 LOCATED WITHIN 6FT OF ANY SINKS.
  
 9) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLACE
 NOTES ON PLANS ACCORDINLY.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW IF
 THERE ARE ANY QUESTIONS; PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]