| Date |
Text |
| 2008-02-22 16:49:52 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| | 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE |
| | PERMIT APPLICATION. |
| | |
| | 2.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN |
| | FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA |
| | (INSPECTION SERVICES MANAGER - TEL: |
| | 561 805 6711), A MEETING INVOLVING THE OWNER, SPECIAL |
| | INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS |
| | MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL |
| | SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING AND |
| | FOR ALL SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6. |
| | |
| | 3.)THRESHOLD INSPECTION PLAN REQUIRED, FBC*1009.3.6. |
| | |
| | 4.)SEE FBC*109.3.6.4.4 AND INCLUDE THE STATEMENT |
| | ATTESTING TO COMPLIANCE. |
| | |
| | 5.)SEPARATE PERMITS WILL BE REQUIRED FOR THE |
| | AWNINGS. |
| | |
| | 6.)CERTIFICATE OF AUTHORIZATION REQUIRED TO PRACTICE |
| | ARCHITECTURE THROUGH A COMPANY, FS481.219(2).A |
| | LICENSE NUMBER WAS PRINTED ON THE COVER SHEET BUT I WAS |
| | UNABLE TO LOCATE THIS NUMBER ON THE WEBSITE |
| | WWW.MYFLORIDALICENSE.COM (AA-C000288).I?VE PUT IN AN |
| | INQUIRY TO THE STATE; THIS COMMENT WILL BE REMOVED WHEN |
| | THE NUMBER IS CONFIRMED. |
| | |
| | 7.)THE CERTIFICATE OF AUTHORIZATION FOR THE |
| | ARCHITECTURE FIRM IS TO BE PRINTED ON EACH SHEET, |
| | FAC61G16-23.002, 003. |
| | |
| | 8.)CERTIFICATE OF AUTHORIZATION REQUIRED TO PRACTICE |
| | ENGINEERING THROUGH A COMPANY, FS471.023 (COMMENT |
| | APPLIES TO TRO JUNG BRANNEN). |
| | |
| | 9.)THE CERTIFICATE OF AUTHORIZATION FOR THE |
| | ENGINEERING FIRM IS TO BE PRINTED ON EACH SHEET, |
| | FAC6G15-23.002. |
| | |
| | 10.)IN DECLARING GOVERNING CODE, PLEASE REVISE TO |
| | INCLUDE 2007 REVISIONS WHICH BECAME EFFECTIVE JULY 1, |
| | 2007. |
| | |
| | 11.)A100, PROVIDE AREA INCREASE CALCULATIONS ON THE |
| | PLAN.THE PLANS STATE TOTAL SQUARE FOOT AREA, BUT |
| | COMPLIANCE WITH FBC TABLE 503 IS REQUIRED.STATE TOTAL |
| | EXISTING SQUARE FOOT AREA FOR EACH FLOOR, TOTAL |
| | PROPOSED, NEW TOTALS. |
| | |
| | 12.)I2 HAS BEEN DECLARED AS OCCUPANCY CLASSIFICATION. |
| | SEE FBC302.1.THIS BUILDING APPEARS TO BE A MIXED |
| | OCCUPANCY DUE TO THE ASSEMBLY AND BUSINESS AREAS.NOTE |
| | SEPARATE OCCUPANCIES ON THE PLAN, SQUARE FOOT AREA PER |
| | FLOOR FOR EACH OCCUPANCY, AND SHOW COMPLIANCE WITH FBC |
| | TABLE 503. |
| | |
| | 13.)CLARIFY FIRE RATED WALLS AND OCCUPANCY |
| | SEPARATIONS.FOR INSTANCE, SEE A201A.A TWO HOUR WALL |
| | IS SHOWN, BUT THE FOOD STAGING AND DISH WASH AREAS IN |
| | THE SAME FIRE AREA AS OFFICE AND STAFF LOCKERS.NO |
| | RATED WALL SHOWN AT THE CORRIDOR OR BETWEEN FOOD |
| | STAGING, CORRIDOR AND I2 AREAS.OCCUPANCY SEPARATIONS |
| | SHOULD SEPARATE THE DIFFERENT OCCUPANCIES UNLESS A NON |
| | SEPARATED USE.PLEASE SEE FBC302 AND CLARIFY |
| | REQUIREMENTS.THIS IS USUALLY INCLUDED ON A LIFE |
| | SAFETY PLAN.REQUIRED OCCUPANCY SEPARATIONS ARE NOT |
| | CLEAR. |
| | |
| | 14.)PLEASE PROVIDE A LIFE SAFETY PLAN, FBC CHAPTER |
| | 10. |
| | |
| | 15.)ACCESSIBLE PARKING SPACE, A100, IS TO INCLUDE THE |
| | FINE, FBC11-4.6.4. |
| | |
| | 16.)STAFF TOILET ROOM 125, TO BE ACCESSIBLE.SEE |
| | FBC11-4.1.3(11). |
| | |
| | 17.)THE ROOM MARKED CUST 133 APPEARS TO BE A WORK |
| | AREA.WORK AREAS ARE TO BE DESIGNED SO THAT |
| | INDIVIDUALS WITH DISABILITIES CAN APPROACH, ENTER, AND |
| | EXIT THE AREA, FBC11-4.1.1(3). |
| | |
| | 18.)SHOW MANEUVERING CLEARANCE, PULL SIDE, FOR THE |
| | FOLLOWING DOORS: |
| | |
| | PASS 121 TO CORRIDOR 120. |
| | DIRECTORS OFFICE 126 |
| | MULTIPURPOSE ROOM 116 |
| | |
| | 19.)A201R, 1 HOUR FIRE RESISTANCE RATING NOTED FOR |
| | THE ROOF.ON THE PLAN, SHOW ALL REQUIRED FIRE |
| | RESISTANCE FBC TABLE 601. |
| | |
| | 20.)PRODUCT APPROVALS REQUIRED: |
| | |
| | MODIFIED ROOF |
| | DURALOC METAL ROOF |
| | HARDISOFFIT |