| Date |
Text |
| 2008-04-01 12:01:50 | *****DENIED***** |
| | |
| | |
| | 01. THE COMPLETE ADDRESS SHALL BE IN THE TITLE BLOCK OF |
| | EACH SUBMITTED PLAN SHEET.BE ADVISED THAT THERE IS A |
| | DISTINCTION BETWEEN NORTH FLAGLER AND SOUTH FLAGLER |
| | DRIVE. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 04.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 05.BE ADVISED THAT THIS SCOPE OF WORK WILL REQUIRE A |
| | CONVERSION FROM THAT A OF RESIDENTIAL OCCUPANCY.LIST |
| | THE OCCUPANCY TYPE FOR THIS PROJECT ( NEW DAY-CARE, NEW |
| | RESIDENTIAL BOARD AND CARE - SMALL FACILITY, LARGE |
| | FACILITY, ETC.) AS PER NFPA 101 - 2003 EDITION. |
| | |
| | 06.IF THE OCCUPANCY IS OTHER THAN RESIDENTIAL, |
| | ADDRESS NUMBERS (AS PER WEST PALM BEACH CODE) SHALL BE |
| | NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN |
| | STROKE.DISPLAY/SHOW THE ADDRESS NUMBER ON THE |
| | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS NORTH |
| | FLAGLER DRIVE. |
| | |
| | 07.A SECONDARY MEANS OF ESCAPE SHALL BE REQUIRED IN |
| | SLEEPING ROOMS AND LIVING AREAS IN FACILITIES WITHOUT A |
| | SPRINKLER SYSTEM.AN OUTSIDE WINDOW OR DOOR PROVIDING |
| | A CLEAR OPENING OF NOT LESS THAN 5.7 SQ.FT. WITH THE |
| | WIDTH NOT LESS THAN 20" AND THE HEIGHT NOT LESS THAN |
| | 24".THE BOTTOM OF THE OPENING SHALL NOT BE MORE THAN |
| | 44" ABOVE THE FLOOR. |
| | |
| | 08.EVERY CLOSET DOOR LATCH SHALL BE READILY OPENED |
| | FROM THE INSIDE. |
| | |
| | 09.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | SPECIFY INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR |
| | CLASS II. |
| | |
| | 10.A MANUAL FIRE ALARM SYSTEM WITH OCCUPANT |
| | NOTIFICATION, SHALL BE PROVIDED AUTOMATICALLY WITHOUT |
| | DELAY, IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE ALARM |
| | CODE, 2002 EDITION. |
| | |
| | 11.IN CONVERSIONS, SPRINKLERS SHALL NOT BE REQUIRED |
| | IN SMALL BOARD AND CARE HOMES, SERVING EIGHT OR FEWER |
| | RESIDENTS, WHEN ALL OCCUPANTS HAVE THE ABILITY TO AS A |
| | GROUP TO MOVE RELIABLY TO A POINT OF SAFETY WITHIN 3 |
| | MINUTES.PLEASE ADVISE AS TO THE NUMBER OF RESIDENTS |
| | PROJECTED. |
| | |
| | 12.THE WALL BETWEEN THE GARAGE/LAUNDRY AREA (MORE |
| | HAZARDOUS AREA) WHICH ABUTS BEDROOM #3 SHALL HAVE A |
| | FIRE RESISITIVE RATING OF AT LEAST 1 HOUR. |
| | |
| | 13.THE SEPARATION WALLS OF THE SLEEPING ROOMS SHALL |
| | BE CAPABLE OF RESISTING FIRE FOR AT LEAST 1/2 HOUR. |
| | |
| | 14.SLEEPING ROOM DOORS SHALL BE SUBSTANTIAL DOORS, |
| | SUCH AS THOSE OF 1 3/4-IN THICK, SOLID BONDED WOOD CORE |
| | CONSTRUCTION OR OF OTHER CONSTRUCTION OF EQUAL OR |
| | GREATER STABILITY AND FIRE INTEGRITY. |
| | |
| | 15.DOORS SHALL MEET THE FOLLOWING REQUIREMENTS:(1) |
| | DOORS SHALL BE PROVIDED WITH LATCHES OR OTHER |
| | MECHANISMS SUITABLE FOR KEEPING THE DOORS CLOSED;(2) |
| | NO DOOR SHALL BE ARRANGED TO PREVENT THE OCCUPANT FROM |
| | CLOSING THE DOOR;(3) DOORS SHALL BE SELF-CLOSING OR |
| | AUTOMATIC-CLOSING UNLESS THE BUILDING IS PROTECTED |
| | THROUGHOUT BY AN APPROVED, AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | 16.APPROVED SMOKE ALARMS SHALL BE PROVIDED AND |
| | INSTALLED IN ALL LIVING AREAS, EACH SLEEPING ROOM, BUT |
| | EXCLUDING CRAWL SPACES AND UNFINISHED ATTICS. |
| | |
| | 17.NO STOVE OR COMBUSTION HEATER SHALL BE LOCATED TO |
| | BLOCK ESCAPE IN CASE OF FIRE CAUSED BY THE MALFUNCTION |
| | OF THE STOVE OR HEATER. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS |
| | ADDRESSED |
| | |
| | |