Plan Review Notes
Plan Review Notes For Permit 08010588
Permit Number 08010588
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-24 10:16:20 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE COMPLIANCE WITH NFPA-72, 2002 FOR SMOKE
 ALARMS.
  
 2} INDICATE EMERGENCY LIGHTING LOCATIONS PER 700.12,
 700.15, 700.16 AND 700.17, 2005 NEC.
  
 3} LOCATE EGRESS LIGHTING PER 210.70(A).
  
 4} PROVIDE AN ELECTRICAL FLOOR PLAN FOR REVIEW.106.1
 FBC AS AMENDED.
  
 5} } PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS
 PER 106.3.5.4 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718