Plan Review Notes
Plan Review Notes For Permit 08010585
Permit Number 08010585
Review Stop E
Sequence Number 2
Notes
Date Text
2008-04-10 16:39:58 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} PROVIDE A RISER DIAGRAM INDICATING COMPLIANCE WITH
 230.70(A)(1). DISCONNECT IS REQUIRED IF THE PANEL IS
 NOT BACK TO BACK WITH THE METER. SHOW ALL SERVICE
 EQUIPMENT ON THE RISER AND SUBMIT A SITE OR FLOOR PLAN
 PHYSICALLY LOCATING ALL PANELS, DISCONNECTS AND THE
 METER.
  
 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718