| Plan Review Notes For Permit 08010571 |
| Permit Number |
08010571 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-31 17:48:12 | | | | | | | DENIED | | | | | | 1)DRAWINGS DO NOT DETAIL AREA THAT IS EXISTING | | | STRUCTURE AND AREA THAT IS NEW. 1ST SHEET IS | | | ENGINEERINGFOR STRUCTURE THAT ONLY CARRIES SCREEN | | | CLOTH, SHEET 2 SHOWS TIE IN TO INSULATED | | | ROOF(EXISTING?)AND WHAT MAY BE A NEW INSULATED ROOF | | | STRUCTURE BUT ENGINEERING DOES NOT HAVE DETAIL ON TIE | | | DOWN OF THIS STRUCTURE TO FOUNDATION OR MAXIMUM SPANS | | | OF BEAMS OR COLUMN LENGTHS. PLEASE CLARIFY WHAT IS IN | | | SCOPE OF WORK. | | | | | | 2)IF NEW ROOF PANELS ARE TO BE USED SUBMIT FLORIDA | | | PRODUCT APPROVALS | | | | | | 3)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | 4)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE | | | PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR | | | SETBACKS | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|