| Plan Review Notes For Permit 08010526 |
| Permit Number |
08010526 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-06 16:22:21 | *****DENIED***** | | | | | | | | | 1.THE SUITE NUMBER SHALL BE INCLUDED WITH THE | | | NUMERICAL ADDRESS LOCATED IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. ALSO INDICATE EAST OR WEST | | | TOWER. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | | COMMENT TO SHEET AD1.09 | | | | | | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 4.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALL | | | AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 5.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL | | | DISTANCE. | | | | | | 6.INDICATE AS TO WHETHER THERE HAS BEEN ANY | | | ALTERATION TO FIRE ALARM DEVICES SHOWN ON SHEET E.02 IN | | | THE POWER & MISC. SYSTEMS PLAN.BE ADVISED THAT | | | SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE FIRE | | | ALARM REMODEL, | | | | | | 7.NFPA 13, STANDARD FO THE INSTALLATION OF SPRINKLER | | | SYSTEMS, 2002 EDITION SHALL BE REFERENCED.AMEND NOTE | | | #12 ON SHEET FP.01 | | | | | | 8.FLORIDA FIRE PREVENTION CODE 2004 EDITION SHALL BE | | | REFERENCED.AMEND NOTE #13 ON SHEET FP.01 | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|