| Date |
Text |
| 2008-01-29 20:06:53 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE KNOW PLANS HAVE ONLY BEEN SUBMITTED FOR |
| | *PLAN REVIEW * ONLY AND HAVE NOT BEEN SUBMITTED FOR |
| | PERMIT AT THIS TIME. |
| | PLEASE KNOW EVEN ONCE PLANS ARE CODE COMPLIANT MEETING |
| | COMMENTS FROM REVIEWER(S), PLANS WILL NOT BE STAMPED |
| | AND REVIEW WILL REMAIN IN A FAILED STATUS UNTIL PERMIT |
| | APPLICATION HAS BEEN MADE. |
| | |
| | 2) NOTE: PLEASE KNOW THE ADDRESSING FOR UNIT/SUIT IS |
| | YET TO BE DETERMINED. PLEASE KNOW AS THIS IS AN |
| | EXTENSION TO AN EXISTING TENANT PLEASE OBTAIN EXISTING |
| | SUITE/UNIT NUMBER AND CONFIRM WITH THIS OFFICE AND |
| | ADDRESSING REVIEWER. PLEASE KNOW THE INFORMATION WAS |
| | SENT TO THE ADDRESSING REVIEWER AS OF THIS REVIEW. |
| | PLEASE BE SURE ALL TITLE BLOCKS CONTAIN THE ADJUSTED |
| | SUITE/UNIT LOCATION ONCE DETERMINED. |
| | PLEASE SEE LOCATION FOR EAST OR WEST TOWER LOCATION |
| | ALSO NEEDS TO BEAPPLIED. |
| | FBC 106.5, 106.1.2 ADMIN SECTION. |
| | FAC 61G15-23.002, 61G1-16.002 |
| | |
| | 3) NOTE: PLEASE SEE THE COLOR CODING AS STATED ON PLANS |
| | FOR 277/480V SYSTEMS SHALL BE BROWN, PURPLE, YELLOW. |
| | THE *ORANGE* COLOR AS SPECIFIED ON THE PLANS IS FOR A |
| | DELTA HIGH-LEG SYSTEM WHICH THIS IS NOT. |
| | THIS WAS A LOCAL AMENDMENT FOR THIS AND OTHER LOCAL |
| | JURISDICTIONS AND WIRING METHOD IN THIS AND OTHER |
| | EXISTING BUILDING CONTAIN THE COLOR CODING AS MENTIONED |
| | ABOVE. |
| | THIS REMAINS A REQUIREMENT PER 90.4 DUE TO EXISTING |
| | WIRING METHODS FOR SAFETY. |
| | |
| | 4) NOTE: PLEASE SEE THE METHOD *B* ENERGY CALCULATIONS |
| | SUBMITTED DO NOT CONTAIN THE INPUT DATA REPORT(S) IN |
| | ANY OF THE THREE COPIES SUBMITTED. |
| | PLEASE SEE SHEET #2 OF THE SUMMARY AS THIS SPECIFICALLY |
| | STATES THE INPUT DATA REPORT MUST ACCOMPANY |
| | CALCULATIONS. |
| | PLEASE KNOW AS THERE WERE NOT SUBMITTED NO REVIEW OF |
| | THE ITEMS ON THE IDR CAN BE DONE AND COORDINATED WITH |
| | THE SUBMITTED PLANS AND FIXTURE LEGEND. |
| | PLEASE SEE THE CERTIFICATION SHEET IS REQUIRED TO BE |
| | SEALED BY THE DESIGN PROFESSIONAL OF RECORD. THE SHEET |
| | WAS SIGNED, AND DATED HOWEVER DID NOT GET SEALED. |
| | PLEASE ALSO SEE THE OWNER AGENT SIGNATURE IS MISSING ON |
| | THIS SAME SHEET. |
| | 13-415.1.B, 13-415.2, 13-103.1, 13-103.1.1, |
| | 13-103.1.1.1 |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER REVIEW TRADES. |
| | |
| | 5) NOTE: PLEASE STATE MAXIMUM TIMES ON ALL OCCUPANCY |
| | SENSOR TYPE DEVICES PER 13-415.1.ABC.1.1, .1.2. |
| | |
| | 6) NOTE: PLEASE SEE NOTE ON E.02 MENTIONS RELOCATION OF |
| | THE TRANSFORMER. PLEASE SHOW AND INDICATE THE GROUNDING |
| | ELECTRODE CONDUCTOR WHICH WILL MOST LIKELY BE REQUIRED |
| | TO BE NEW DUE TO RELOCATION. |
| | PLEASE SEE 250.66, 250.50, 250.30, 250.50 |
| | |
| | |
| | |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |