Plan Review Notes
Plan Review Notes For Permit 08010526
Permit Number 08010526
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-29 20:06:53** DENIED REVIEW **
  
 1) NOTE: PLEASE KNOW PLANS HAVE ONLY BEEN SUBMITTED FOR
 *PLAN REVIEW * ONLY AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT AT THIS TIME.
 PLEASE KNOW EVEN ONCE PLANS ARE CODE COMPLIANT MEETING
 COMMENTS FROM REVIEWER(S), PLANS WILL NOT BE STAMPED
 AND REVIEW WILL REMAIN IN A FAILED STATUS UNTIL PERMIT
 APPLICATION HAS BEEN MADE.
  
 2) NOTE: PLEASE KNOW THE ADDRESSING FOR UNIT/SUIT IS
 YET TO BE DETERMINED. PLEASE KNOW AS THIS IS AN
 EXTENSION TO AN EXISTING TENANT PLEASE OBTAIN EXISTING
 SUITE/UNIT NUMBER AND CONFIRM WITH THIS OFFICE AND
 ADDRESSING REVIEWER. PLEASE KNOW THE INFORMATION WAS
 SENT TO THE ADDRESSING REVIEWER AS OF THIS REVIEW.
 PLEASE BE SURE ALL TITLE BLOCKS CONTAIN THE ADJUSTED
 SUITE/UNIT LOCATION ONCE DETERMINED.
 PLEASE SEE LOCATION FOR EAST OR WEST TOWER LOCATION
 ALSO NEEDS TO BEAPPLIED.
 FBC 106.5, 106.1.2 ADMIN SECTION.
 FAC 61G15-23.002, 61G1-16.002
  
 3) NOTE: PLEASE SEE THE COLOR CODING AS STATED ON PLANS
 FOR 277/480V SYSTEMS SHALL BE BROWN, PURPLE, YELLOW.
 THE *ORANGE* COLOR AS SPECIFIED ON THE PLANS IS FOR A
 DELTA HIGH-LEG SYSTEM WHICH THIS IS NOT.
 THIS WAS A LOCAL AMENDMENT FOR THIS AND OTHER LOCAL
 JURISDICTIONS AND WIRING METHOD IN THIS AND OTHER
 EXISTING BUILDING CONTAIN THE COLOR CODING AS MENTIONED
 ABOVE.
 THIS REMAINS A REQUIREMENT PER 90.4 DUE TO EXISTING
 WIRING METHODS FOR SAFETY.
  
 4) NOTE: PLEASE SEE THE METHOD *B* ENERGY CALCULATIONS
 SUBMITTED DO NOT CONTAIN THE INPUT DATA REPORT(S) IN
 ANY OF THE THREE COPIES SUBMITTED.
 PLEASE SEE SHEET #2 OF THE SUMMARY AS THIS SPECIFICALLY
 STATES THE INPUT DATA REPORT MUST ACCOMPANY
 CALCULATIONS.
 PLEASE KNOW AS THERE WERE NOT SUBMITTED NO REVIEW OF
 THE ITEMS ON THE IDR CAN BE DONE AND COORDINATED WITH
 THE SUBMITTED PLANS AND FIXTURE LEGEND.
 PLEASE SEE THE CERTIFICATION SHEET IS REQUIRED TO BE
 SEALED BY THE DESIGN PROFESSIONAL OF RECORD. THE SHEET
 WAS SIGNED, AND DATED HOWEVER DID NOT GET SEALED.
 PLEASE ALSO SEE THE OWNER AGENT SIGNATURE IS MISSING ON
 THIS SAME SHEET.
 13-415.1.B, 13-415.2, 13-103.1, 13-103.1.1,
 13-103.1.1.1
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEW TRADES.
  
 5) NOTE: PLEASE STATE MAXIMUM TIMES ON ALL OCCUPANCY
 SENSOR TYPE DEVICES PER 13-415.1.ABC.1.1, .1.2.
  
 6) NOTE: PLEASE SEE NOTE ON E.02 MENTIONS RELOCATION OF
 THE TRANSFORMER. PLEASE SHOW AND INDICATE THE GROUNDING
 ELECTRODE CONDUCTOR WHICH WILL MOST LIKELY BE REQUIRED
 TO BE NEW DUE TO RELOCATION.
 PLEASE SEE 250.66, 250.50, 250.30, 250.50
  
  
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved