| Plan Review Notes For Permit 08010510 |
| Permit Number |
08010510 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-13 07:28:51 | 1. BUILDING ADDRESS SHOULD HAVE BEEN NOTED ON THE | | | PLANS. | | | | | | 2. NEW FIRE PUMP INSTALLATION TO COMPLY WITH NFPA 20. | | | AFTER INSTALLATION, THE FIRE PUMP AND ALL APPURTENANT | | | EQUIPMENT SHALL BE TESTED TO ENSURE PROPER OPERATION. | | | WHEN THE PRE-TESTING HAS BEEN COMPLETED, ANOTHER TEST | | | IS TO BE PERFORMED WITH THE AUTHORITY HAVING | | | JURISDICTION WHICH IS THE BUREAU OF FIRE PREVENTION. | | | | | | 3. ALL NEW 21/2" X 2 1/2" X 4" FIRE DEPARTMENT | | | CONNECTIONS LOCATED ON THE SIXTH FLOOR LEVEL ON PAGE | | | FP2.60 SHALL BE PROPERLY RESTRAINED TO PREVENT VERTICAL | | | OR HORIZONTAL MOVEMENT. | | | | | | 4. ALL NEW STANDPIPE RISERS ILLUSTRATED ON THE DRAWINGS | | | SHALL ALSO BE PROPERLY RESTRAINED. | | | | | | 5. THE BUILDING IS TO REMAIN UNDER APPROVED FIRE WATCH | | | ACTIVITIES UNTIL SUCH TIME AS THE NEW FIRE PUMP | | | INSTALLATION IS INSPECTED, TESTED, AND APPROVED BY THE | | | BUREAU OF FIRE PREVENTION. | | | | | | 6. THE STANDPIPE SYSTEM SHALL COMPLY WITH NFPA 14. | | | | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|