| 2008-02-27 07:51:46 | PERMIT: 08010506 |
| | ADD: 700 S ROSEMARY AVE # 118 |
| | CONT: SOUTHEAST CONTRACTING |
| | TEL: (561)856-6655 |
| | FEB. 27,2007 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE.NOTE PLEASE CONTACT THE THRESHOLD |
| | INSPECTOR MANAGER, THIS IS A 5 STORY BUILDING NOT A 2 |
| | STORY BUILDING. THE PARKING GARAGE IS PART OF THE SAME |
| | BUILDING. CONTACT MR. PISKURA TO SEE IF 3 SETS OF PLANS |
| | WILLL BE REQUIRED, AND IF THRESHOLD INSPECTION REPORT |
| | AND INSPECTOR WILL BE REQUIRED FORTHIS JOB.(561) |
| | 805-6711. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. SHOP DRAWINGS |
| | INDICATE THE USE OF "WHITE OUT" IN MANY AREAS OF THE |
| | PLANS. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE2007 SUPPLEMENTS. |
| | |
| | 2) 2ND REQUEST, THE PLANS ARE SUPPOSE TO GIVE THE |
| | DESIGN CRITERIA THAT THEY WERE DESIGN UNDER AND HOW |
| | THEY WILL BE REVIEWED TO THAT SAME CRITERIA.THE TYPE |
| | OF CONSTRUCTION TABLE 503 AND TABLE 601. IF FIRE |
| | SPRINKERED, EDITION OF CODE THE RENOVATION WAS DESIGNED |
| | TOO, UNDER THE 2004 EXISTING BUILDING CODE THE |
| | REPLACEMENT OF THE WINDOW WALL SYSTEM IS A LEVEL I |
| | ALTERATION. NOTE THIS PERMIT IS ONLY FOR THE STOREFRONT |
| | NOT THE RENOVATION OF THE TENANT SPACE. THE OTHER |
| | PERMIT THAT IS SUBMITTED FOR THE TENANT RENOVATION IS A |
| | LEVEL II ALTERATION. THE PLANS NEED TO NOTE THE ABOVE |
| | INFORMATION ON THE PLANS AS STATED BELOW. ONCE THE |
| | PERMIT IS ISSUED THE NOTES USED FOR PLAN REVIEW AND THE |
| | DESIGN TEAMS RESPONCES ARE DESTROYED, THEY ARE NOT |
| | SCANNED IN FOR RECORD KEEPING PURPOSES. |
| | PLANS DO NOT INDICATEWORK BEING COMPLETED UNDER THE |
| | 2004 EXISTING BUILDING CODE, PLEASE ADD TO THE DESIGN |
| | CRITERIA, LEVEL I ALTERATION SEE 507.3 EXISTING |
| | BUILDING CODE. REFERS YOU BACK TO CHAPTER 16 FOR WIND |
| | AND LARGE MISSLIE REQUIREMENTS FOR REPLACEMENT OF |
| | WINDOWS AND DOORS.1609.1.4 PROTECTION OF OPENINGS IN |
| | WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT |
| | RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3 |
| | M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE |
| | BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT |
| | RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR |
| | PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 ANDASTM E 1996, |
| | OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN |
| | AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET |
| | (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE |
| | LARGE MISSILE TEST. 2.GLAZED OPENINGS LOCATED MORE |
| | THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE |
| | PROVISIONS OF THE SMALL MISSILE TEST. |
| | |
| | 3) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS |
| | ARE AS FOLLOWS: |
| | A) STOREFRONT FIXED WINDOWS |
| | B) STOREFRONT AUTOMATIC BYPASS DOORS-WHITE OUT ON |
| | COVER SHEET |
| | |
| | ONLY 2 COPIES OF THE PRODUCT APPROVALS WERE SUBMITTED |
| | NOT THREE THAT ARE REQUIRED FOR A THRESHOLD BUILDING. |
| | NOTE 2 COPIES OF SHOP DRAWINGS WERE SUBMITTED NOT |
| | THREE |
| | NOTE WHITE OUT USED ON SHOP DRAWINGS- NOT ALLOWED |
| | NOTE THE DESIGN CRITERIA ON THE SHOP DRAWINGS INDICATES |
| | A MEAN ROOF HEIGHT OF 40 FEET NOT THE 66 FT SHOWN IN |
| | THE STRUCTURAL CALCULATIONS. |
| | THE SHOP DRAWINGS DO NOT INCLUDE THE 2007 SUPPLEMENTS |
| | TO THE 2004 FBC, THE 2007 SUPPLEMENTS DO HAVE WIND |
| | INFORMATION! |
| | |
| | 4)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 6)COMPLIED. |
| | |
| | |
| | 7) COMPLIED. THRESHOLD INSPECTION PLANFL S. S. |
| | 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURALINSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 8) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER |
| | INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 9) THRESHOLD BLDG,REQUIRED STATEMENT:W.P.B. |
| | AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |