2008-01-23 18:00:57BUILDING PLAN REVIEW
 PERMIT: 08010506
 ADD: 700 S ROSEMARY AVE # 118
 CONT: SOUTHEAST CONTRACTING
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.NOTE PLEASE CONTACT THE THRESHOLD
 INSPECTOR MANAGER, THIS IS A 5 STORY BUILDING NOT A 2
 STORY BUILDING. THE PARKING GARAGE IS PART OF THE SAME
 BUILDING. CONTACT MR. PISKURA TO SEE IF 3 SETS OF PLANS
 WILLL BE REQUIRED, AND IF THRESHOLD INSPECTION REPORT
 AND INSPECTOR WILL BE REQUIRED FORTHIS JOB.(561)
 805-6711.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) PLANS DO NOT INDICATEWORK BEING COMPLETED UNDER
 THE 2004 EXISTING BUILDING CODE, PLEASE ADD TO THE
 DESIGN CRITERIA, LEVEL I ALTERATION SEE 507.3 EXISTING
 BUILDING CODE. REFERS YOU BACK TO CHAPTER 16 FOR WIND
 AND LARGE MISSLIE REQUIREMENTS FOR REPLACEMENT OF
 WINDOWS AND DOORS. 1609.1.4 PROTECTION OF
 OPENINGS IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING
 THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET
 (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS
 AND THE BALANCE OF GLAZED OPENINGS IN THE REST OF THE
 BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 ANDASTM E 1996, OR MIAMI-DADE TAS 201, 202 AND
 203 REFERENCED THEREIN AS FOLLOWS: 1. GLAZED OPENINGS
 LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST. 2.GLAZED
 OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) ABOVE GRADE
 SHALL MEET THE PROVISIONS OF THE SMALL MISSILE TEST.
  
 3)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 A) STOREFRONT FIXED WINDOWS
 B) STOREFRONT AUTOMATIC BYPASS DOORS
  
 4)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6)SHEET A601 INDICATES THE NEW FRONT DOORS ARE
 AUTOMATIC SLIDING GLASS DOORS, PROVIDE PRODUCT
 INFORMATION FOR BREAK AWAY DOORS SHOW COMPLIANCE WITH
 1008.1.3.3.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 THRESHOLD INSPECTION PLANFL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURALINSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTOR:
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6711 FOR FURTHER INFORMATION
 BEFORE
 THE PERMIT MAY BE ISSUED.
  
 THRESHOLD BLDG,REQUIRED STATEMENT:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.