| Plan Review Notes For Permit 08010505 |
| Permit Number |
08010505 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-25 15:17:04 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2.PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | | ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE. | | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3, | | | PROVIDE CALCULATIONS AND PROVIDE INFORMATION REGARDING | | | THE EXISTING DOOR (AMOUNT OF GLAZING). | | | | | | 2.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | | FAC9B72, WWW.FLORIDABUILDING.ORG.A REPORT WAS | | | PROVIDED BUT THE FLORIDA STATE PRODUCT APPROVAL WAS NOT | | | INCLUDED. | | | | | | 3.DECLARE GOVERNING CODE AND WIND DESIGN CRITERIA FBC | | | R 301. | | | | | | 4.PROVIDE A STRUCTURAL DETAIL FOR THE WINDOW INFILL. | | | THE DETAIL PROVIDED IS NOT CLEAR.EXISTING CONDITIONS | | | NOT SHOWN, TAPCONS SPECIFIED EVERY 12" BUT THERE ARE | | | NUMEROUS LINES SHOWN WHICH ARE CLOSER THAN 12", WHAT IS | | | THIS?THE DETAIL IS MARKED "WINDOW FRAMING DETAIL". | | | NO WINDOWS REFERENCED ON THE APPLICATION; DO YOU MEAN | | | WINDOW INFILL DETAIL? | | | | | | | | | |
|