| 2008-09-04 08:30:07 | |
| | |
| | |
| | |
| | |
| | ** DENIED 4TH TIME REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE COMMENTS FROM THE PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE |
| | SIGNATURE OF THE ENGINEER OF RECORD. AS THIS OFFICE HAS |
| | SEEN MORE THAN ONE SIGNATURE AND THE ENGINEER HAS |
| | STATED THAT SOME PREVIOUS PLANS WERE SIGNED BY HIS |
| | SECRETARY THE PREVIOUS REVIEW STATED THAT A SIGNATURE |
| | VERIFICATION LETTER IS REQUIRED. AT THIS TIME THIS |
| | OFFICE DOES KNOW WHICH SIGNATURE IS CORRECT. PLEASE |
| | SUBMIT THE LETTER, PLEASE BE SURE THE LETTER IS |
| | ORIGINAL, SIGNED, DATED WITH RAISED SEAL AND CORRECTLY |
| | NOTARIZED. |
| | FS 471.025 |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH STATED THE |
| | BASE BUILDING DESIGNERS OF RECORD WERE REQUIRED TO |
| | *STAMP* PLANS AS SHOP DRAWING REVIEW AND SIGN EACH |
| | SHEET. THE ELECTRICAL SHEETS ARE NOT SIGNED BY THE |
| | *ENGINEER* OF RECORD FOR THIS PROJECT. |
| | FS 471.025 |
| | |
| | ** BASE/SHELL BUILDING DESIGNERS ARE RESPONSIBLE FOR |
| | ALL WORK IN THIS BUILDING UNTIL C OF O OR C OF C. |
| | |
| | 3) NOTE: PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS |
| | TABLE PROVIDED ONLY NOW FOR THE FIRST REVIEW IS STATING |
| | THE 2007 FLORIDA BUILDING CODE. PLEASE SEE FS 553.73 AS |
| | THE 2007 FBC HAS NOT BEEN ADOPTED BY THE STATE OF |
| | FLORIDA. THE CODE IN EFFECT ON ANY PROJECT IS BASED ON |
| | PERMIT APPLICATION DATE. THE 2007 FBC ADOPTION HAS BEEN |
| | PUSHED BACK UNTIL AT LEAST DECEMBER 31ST, 2008. AS |
| | PERMIT APPLICATION WAS MADE IN JANUARY OF 2008 THE CODE |
| | IN EFFECT AT TIME OF PERMIT APPLICATION IS 2004 FBC W/ |
| | 2007 REVISIONS. PLEASE CORRECT PLANS. |
| | |
| | 4) NOTE: PLEASE EXPLAIN WHY THE NORMAL LEVELS OF |
| | PHOTO-METRICS ARE NOT COMPLETE FOR STAIRS ON ALL |
| | LEVELS. IN FACT SOME LEVELS ARE MISSING THE STAIRS |
| | COMPLETELY AND SOME ARE MISSING ONE STAIR BUT NOT THE |
| | OTHER. |
| | THE LEVELS OF LIGHTING ARE REQUIRED ON THE SLOPE, NOT |
| | ONLY WHAT WOULD BE A FLAT SURFACE. |
| | NFPA-7.8.1.3 |
| | |
| | 5) NOTE: PLEASE PROVIDE THE LIGHTING FIXTURE PRODUCT |
| | DATA SHEET WHICH PROVIDES THE BALLAST POWER FACTOR. |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | NEC 110.3 |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |