Plan Review Notes
Plan Review Notes For Permit 08010504
Permit Number 08010504
Review Stop E
Sequence Number 4
Notes
Date Text
2008-09-04 08:30:07 
  
  
  
  
 ** DENIED 4TH TIME REVIEW **
  
 ** PLEASE SEE THERE ARE COMMENTS FROM THE PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE
 SIGNATURE OF THE ENGINEER OF RECORD. AS THIS OFFICE HAS
 SEEN MORE THAN ONE SIGNATURE AND THE ENGINEER HAS
 STATED THAT SOME PREVIOUS PLANS WERE SIGNED BY HIS
 SECRETARY THE PREVIOUS REVIEW STATED THAT A SIGNATURE
 VERIFICATION LETTER IS REQUIRED. AT THIS TIME THIS
 OFFICE DOES KNOW WHICH SIGNATURE IS CORRECT. PLEASE
 SUBMIT THE LETTER, PLEASE BE SURE THE LETTER IS
 ORIGINAL, SIGNED, DATED WITH RAISED SEAL AND CORRECTLY
 NOTARIZED.
 FS 471.025
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH STATED THE
 BASE BUILDING DESIGNERS OF RECORD WERE REQUIRED TO
 *STAMP* PLANS AS SHOP DRAWING REVIEW AND SIGN EACH
 SHEET. THE ELECTRICAL SHEETS ARE NOT SIGNED BY THE
 *ENGINEER* OF RECORD FOR THIS PROJECT.
 FS 471.025
  
 ** BASE/SHELL BUILDING DESIGNERS ARE RESPONSIBLE FOR
 ALL WORK IN THIS BUILDING UNTIL C OF O OR C OF C.
  
 3) NOTE: PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS
 TABLE PROVIDED ONLY NOW FOR THE FIRST REVIEW IS STATING
 THE 2007 FLORIDA BUILDING CODE. PLEASE SEE FS 553.73 AS
 THE 2007 FBC HAS NOT BEEN ADOPTED BY THE STATE OF
 FLORIDA. THE CODE IN EFFECT ON ANY PROJECT IS BASED ON
 PERMIT APPLICATION DATE. THE 2007 FBC ADOPTION HAS BEEN
 PUSHED BACK UNTIL AT LEAST DECEMBER 31ST, 2008. AS
 PERMIT APPLICATION WAS MADE IN JANUARY OF 2008 THE CODE
 IN EFFECT AT TIME OF PERMIT APPLICATION IS 2004 FBC W/
 2007 REVISIONS. PLEASE CORRECT PLANS.
  
 4) NOTE: PLEASE EXPLAIN WHY THE NORMAL LEVELS OF
 PHOTO-METRICS ARE NOT COMPLETE FOR STAIRS ON ALL
 LEVELS. IN FACT SOME LEVELS ARE MISSING THE STAIRS
 COMPLETELY AND SOME ARE MISSING ONE STAIR BUT NOT THE
 OTHER.
 THE LEVELS OF LIGHTING ARE REQUIRED ON THE SLOPE, NOT
 ONLY WHAT WOULD BE A FLAT SURFACE.
 NFPA-7.8.1.3
  
 5) NOTE: PLEASE PROVIDE THE LIGHTING FIXTURE PRODUCT
 DATA SHEET WHICH PROVIDES THE BALLAST POWER FACTOR.
 13-415.2, 13-415.2.ABC.1.1, .1.2.
 NEC 110.3
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  