| 2008-07-17 10:43:01 | ** DENIEDRE-SUB ** |
| | |
| | ** MOST OF THE SAME COMMENTS FROM PREVIOUS TWO REVIEWS |
| | ARE STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE:PLEASE SEE PLANS CONTAIN A SIGNATURE WHICH IS |
| | COMPLETELY DIFFERENT THAN PREVIOUS SUBMITTED PLANS BY |
| | THE SAME ENGINEER. PLANS ARE NOW BEING RETAINED FOR |
| | POSSIBLE REVIEW BY THE FLORIDA BOARD OF ENGINEERS. |
| | PLEASE SEE FS 471.025 AS THE ENGINEER MAY BE THE ONLY |
| | PERSON TO SIGN, DATE AND SEAL PLANS. FAC61G15-23.002. |
| | AT THIS TIME THIS OFFICE HAS MULTIPLE RECORDS OF THE |
| | SAME PERSON. NEED TO SUBMIT A SIGNATURE VERIFICATION |
| | LETTER ALONG WITH PHOTO ID OR THE ENGINEER OF RECORD |
| | MAY APPEAR IN PERSON WITH ID TO SIGN, DATE AND SEAL |
| | PLANS. |
| | IF A LETTER IS SUBMITTED, THIS MUST STATE THE LEGAL |
| | SIGNATURE, BE SIGNED, DATED, SEALED AND BE PROPERLY |
| | NOTARIZED. PLEASE SEE FS 117.05 FOR NOTARY |
| | REQUIREMENTS. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS COMMENTS AS THE PLANS ARE |
| | REQUIRED TO GO BACK TO THE BASE BUILDING DESIGNER OF |
| | RECORD FOR *SHOP DRAWING REVIEW* AND STAMPING. THE |
| | ENGINEER OF RECORD IS NOT SIGNED OR STAMPED ON PLANS. |
| | THE BASE BUILDING DESIGNER STILL NEEDS TO STAMP PLANS. |
| | THIS PERSON IS RESPONSIBLE FOR THIS BUILDING UNTIL THAT |
| | SCOPE OF WORK IS COMPLETED. |
| | THIS IS REQUIRED ON EACH SHEET IN ALL SETS. |
| | |
| | 3) NOTE:PLEASE KNOW THIS CONSTRUCTION WORK BEING |
| | APPLIED FOR IN THE BASE BUILDING IS BEING DONE AT THE |
| | SAME TIME THE BASE BUILDING IS BEING CONSTRUCTED BY A |
| | SEPARATE CONTRACTOR. THERE MUST BE A LETTER OF |
| | UNDERSTANDING BETWEEN THE TWO CONTRACTORS. THIS LETTER |
| | MUST BE ORIGINAL AND NOTARIZED WITH THE WORDING OF |
| | UNDERSTANDING FOR INSPECTIONS, WORK BEING DONE IN THE |
| | SAME AREAS ETC. |
| | IF THIS SCOPE OF WORK IS NOT ISSUED UNTIL AFTER THE |
| | BASE BUILDING OBTAINS C OF O/ FINAL THEN THIS WILL NOT |
| | BE REQUIRED. |
| | |
| | 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | PLEASE SEE THE PREVIOUS REVIEW REQUESTED THIS HOWEVER |
| | THE PLANS DO NOT SHOW ANY OF THE INFORMATION. PLEASE BE |
| | AWARE OF LIGHTING WHICH IS ALREADY IN PLACE UNDER THE |
| | BASE BUILDING. THIS LIGHTING WHICH IS PART OF THE BASE |
| | BUILDING MUST ALSO BE INCLUDED. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH ALSO |
| | REQUESTED COMPLIANCE FOR FBC CHAPTER 13 WITH RESPECT TO |
| | LIGHTING CONTROLS REQUIRED PER 13-415.1.ABC.1.1, .1.2, |
| | AND .1.3. |
| | PLEASE SUBMIT SCHEDULING AND ALL MAXIMUM TIMES ON OVER |
| | RIDES. |
| | |
| | 6) NOTE: PLEASE PLACE NOTES ON PLANS PER |
| | 13-413.1.ABC.2.1 AND .2.2. |
| | |
| | 7) NOTE: PLEASE SUBMIT THE PHOTO-METRICS AS PREVIOUSLY |
| | REQUESTED IN ORDER TO COMPLY WITH THE MINIMUM LIGHTING |
| | LEVELS IN THE LIFE SAFETY CODE. |
| | PLEASE SEE 7.8, 7.9 AND 7.8.1.3, 7.9.2.2 FOR MINIMUM |
| | LEVELS. |
| | PLEASE ALSO SEE FAC 61G15-33.004 |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION WITH PLANS. |
| | |
| | 8) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW SHEET |
| | E-6 SHOWS A NEW PANEL WHICH IS NOW SHOWN AS HB HOWEVER |
| | THE INCREASED LOAD CALCULATIONS ON PANELS AND SERVICE |
| | WAS NOT SUBMITTED AS PREVIOUSLY REQUESTED. |
| | PLEASEBE SURE ALL ITEMS TO BE SUBMITTED COORDINATE |
| | WITH THE 2005 NFPA-70 210,220,230,215.5,240.4,310.16 |
| | ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 9) NOTE: PREVIOUS REVIEW GAVE NOTICE TO FLORIDA |
| | STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS |
| | FOR CODE COMPLIANCE.THIS IS THE THIRD REVIEW IN WHICH |
| | SEVERAL ITEMS ARE REPEATED FOR MINIMUM CODE COMPLIANCE |
| | ONCE AGAIN. THE FEE HAS NOW BEEN ASSESSED AND IS DUE |
| | BEFORE PLANS MAY BE RESUBMITTED. |
| | THE FEE OF $5,619.00 IS NOW DUE BEFORE PLANS MAY BE |
| | SUBMITTED BACK FOR THE FORTH REVIEW. TWO SETS OF |
| | ELECTRICAL PLANS HAVE NOW BEEN RETAINED BY THIS OFFICE |
| | FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD OF |
| | ENGINEERS. |
| | THE PREVIOUS REVIEW STATED IF THERE WERE QUESTIONS TO |
| | PLEASE CALL. TO DATE NO CONTACT HAS BEEN MADE TO THIS |
| | REVIEWER. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |