Plan Review Notes For Permit 08010504
Permit Number 08010504
Review Stop E
Sequence Number 3
Notes
Date Text
2008-07-17 10:43:01** DENIEDRE-SUB **
  
 ** MOST OF THE SAME COMMENTS FROM PREVIOUS TWO REVIEWS
 ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE:PLEASE SEE PLANS CONTAIN A SIGNATURE WHICH IS
 COMPLETELY DIFFERENT THAN PREVIOUS SUBMITTED PLANS BY
 THE SAME ENGINEER. PLANS ARE NOW BEING RETAINED FOR
 POSSIBLE REVIEW BY THE FLORIDA BOARD OF ENGINEERS.
 PLEASE SEE FS 471.025 AS THE ENGINEER MAY BE THE ONLY
 PERSON TO SIGN, DATE AND SEAL PLANS. FAC61G15-23.002.
 AT THIS TIME THIS OFFICE HAS MULTIPLE RECORDS OF THE
 SAME PERSON. NEED TO SUBMIT A SIGNATURE VERIFICATION
 LETTER ALONG WITH PHOTO ID OR THE ENGINEER OF RECORD
 MAY APPEAR IN PERSON WITH ID TO SIGN, DATE AND SEAL
 PLANS.
 IF A LETTER IS SUBMITTED, THIS MUST STATE THE LEGAL
 SIGNATURE, BE SIGNED, DATED, SEALED AND BE PROPERLY
 NOTARIZED. PLEASE SEE FS 117.05 FOR NOTARY
 REQUIREMENTS.
  
 2) NOTE: PLEASE SEE PREVIOUS COMMENTS AS THE PLANS ARE
 REQUIRED TO GO BACK TO THE BASE BUILDING DESIGNER OF
 RECORD FOR *SHOP DRAWING REVIEW* AND STAMPING. THE
 ENGINEER OF RECORD IS NOT SIGNED OR STAMPED ON PLANS.
 THE BASE BUILDING DESIGNER STILL NEEDS TO STAMP PLANS.
 THIS PERSON IS RESPONSIBLE FOR THIS BUILDING UNTIL THAT
 SCOPE OF WORK IS COMPLETED.
 THIS IS REQUIRED ON EACH SHEET IN ALL SETS.
  
 3) NOTE:PLEASE KNOW THIS CONSTRUCTION WORK BEING
 APPLIED FOR IN THE BASE BUILDING IS BEING DONE AT THE
 SAME TIME THE BASE BUILDING IS BEING CONSTRUCTED BY A
 SEPARATE CONTRACTOR. THERE MUST BE A LETTER OF
 UNDERSTANDING BETWEEN THE TWO CONTRACTORS. THIS LETTER
 MUST BE ORIGINAL AND NOTARIZED WITH THE WORDING OF
 UNDERSTANDING FOR INSPECTIONS, WORK BEING DONE IN THE
 SAME AREAS ETC.
 IF THIS SCOPE OF WORK IS NOT ISSUED UNTIL AFTER THE
 BASE BUILDING OBTAINS C OF O/ FINAL THEN THIS WILL NOT
 BE REQUIRED.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.1, .1.2.
 PLEASE SEE THE PREVIOUS REVIEW REQUESTED THIS HOWEVER
 THE PLANS DO NOT SHOW ANY OF THE INFORMATION. PLEASE BE
 AWARE OF LIGHTING WHICH IS ALREADY IN PLACE UNDER THE
 BASE BUILDING. THIS LIGHTING WHICH IS PART OF THE BASE
 BUILDING MUST ALSO BE INCLUDED.
  
 5) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH ALSO
 REQUESTED COMPLIANCE FOR FBC CHAPTER 13 WITH RESPECT TO
 LIGHTING CONTROLS REQUIRED PER 13-415.1.ABC.1.1, .1.2,
 AND .1.3.
 PLEASE SUBMIT SCHEDULING AND ALL MAXIMUM TIMES ON OVER
 RIDES.
  
 6) NOTE: PLEASE PLACE NOTES ON PLANS PER
 13-413.1.ABC.2.1 AND .2.2.
  
 7) NOTE: PLEASE SUBMIT THE PHOTO-METRICS AS PREVIOUSLY
 REQUESTED IN ORDER TO COMPLY WITH THE MINIMUM LIGHTING
 LEVELS IN THE LIFE SAFETY CODE.
 PLEASE SEE 7.8, 7.9 AND 7.8.1.3, 7.9.2.2 FOR MINIMUM
 LEVELS.
 PLEASE ALSO SEE FAC 61G15-33.004
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION WITH PLANS.
  
 8) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW SHEET
 E-6 SHOWS A NEW PANEL WHICH IS NOW SHOWN AS HB HOWEVER
 THE INCREASED LOAD CALCULATIONS ON PANELS AND SERVICE
 WAS NOT SUBMITTED AS PREVIOUSLY REQUESTED.
 PLEASEBE SURE ALL ITEMS TO BE SUBMITTED COORDINATE
 WITH THE 2005 NFPA-70 210,220,230,215.5,240.4,310.16
 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PREVIOUS REVIEW GAVE NOTICE TO FLORIDA
 STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS
 FOR CODE COMPLIANCE.THIS IS THE THIRD REVIEW IN WHICH
 SEVERAL ITEMS ARE REPEATED FOR MINIMUM CODE COMPLIANCE
 ONCE AGAIN. THE FEE HAS NOW BEEN ASSESSED AND IS DUE
 BEFORE PLANS MAY BE RESUBMITTED.
 THE FEE OF $5,619.00 IS NOW DUE BEFORE PLANS MAY BE
 SUBMITTED BACK FOR THE FORTH REVIEW. TWO SETS OF
 ELECTRICAL PLANS HAVE NOW BEEN RETAINED BY THIS OFFICE
 FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD OF
 ENGINEERS.
 THE PREVIOUS REVIEW STATED IF THERE WERE QUESTIONS TO
 PLEASE CALL. TO DATE NO CONTACT HAS BEEN MADE TO THIS
 REVIEWER.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II