Plan Review Notes
Plan Review Notes For Permit 08010504
Permit Number 08010504
Review Stop E
Sequence Number 2
Notes
Date Text
2008-04-24 10:15:48** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME OF THE EXACT SAME NOTES ARE IN NEED
 OF ADDRESSING. PLEASE ALSO SEE SOME NEW NOTES DUE TO
 THIS BEING THE SECOND REVIEW AND PROJECT WHICH IS NOT
 ISSUED FOR PERMIT AND NOT FINALE.
  
 1) NOTE: PLEASE SEE THE TITLE BLOCKS FOR THE ELECTRICAL
 PAGES ARE STILL MISSING THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER. THIS IS A FLORIDA STATUTE AS
 GIVEN ON PREVIOUS REVIEW WHICH REQUIRES THE FIRM TO BE
 LICENSED IN THE STATE OF FLORIDA AND THE FLORIDA
 ADMINISTRATIVE CODE REQUIRES THAT LICENSE NUMBER TO BE
 ON THE TITLE BLOCKS ON EACH SHEET FOR SAID FIRM. PLEASE
 SEE FS 471.023 AND FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE THE SEAL NOW ON SAID PLANS IS NOT
 CLEAR AND VISIBLE WITH ALL INFORMATION. PLEASE BE SURE
 ALL INFORMATION ON RAISED SEAL IS CLEAR AND VISIBLE. FS
 471.025
  
 3) NOTE: PLEASE KNOW AS THE PERMIT FOR THE BASE
 BUILDING HAS NOT YET BEEN ISSUED THIS PERMIT MAY NOT
 YET BE ISSUED. PLEASE ALSO KNOW THE BASE BUILDING IS
 ALREADY UNDER A RESPONSIBLE ENGINEERING FIRM. ANY WORK
 WHICH IS BEING PERFORMED IN THE BUILDING BEFORE THE
 BASE BUILDING HAS OBTAINED A CERTIFICATE OF OCCUPANCY
 IS STILL UNDER THE RESPONSIBILITY OF THE BASE BUILDING
 DESIGNER(S).
 PLEASE BE SURE THE PLANS CONTAIN STAMPS BY THE BASE
 BUILDING RESPONSIBLE DESIGN TEAM SUCH AS A *SHOP
 DRAWING* REVIEW STAMP.
 IF THIS SCOPE OF WORK IS NOT GOING TO BE PERMITTED
 UNTIL AFTER C OF O OF THE BASE BUILDING THEN THIS WILL
 NOT BE REQUIRED. IF THERE ARE ANY QUESTIONS ON THIS
 PLEASE CALL.
  
 4) NOTE: PLEASE KNOW THIS CONSTRUCTION WORK BEING
 APPLIED FOR IN THE BASE BUILDING IS BEING DONE AT THE
 SAME TIME THE BASE BUILDING IS BEING CONSTRUCTED BY A
 SEPARATE CONTRACTOR. THERE MUST BE A LETTER OF
 UNDERSTANDING BETWEEN THE TWO CONTRACTORS. THIS LETTER
 MUST BE ORIGINAL AND NOTARIZED WITH THE WORDING OF
 UNDERSTANDING FOR INSPECTIONS, WORK BEING DONE IN THE
 SAME AREAS ETC.
 IF THIS SCOPE OF WORK IS NOT ISSUED UNTIL AFTER THE
 BASE BUILDING OBTAINS C OF O/ FINAL THEN THIS WILL NOT
 BE REQUIRED.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.1, .1.2.
 PLEASE SEE THE PREVIOUS REVIEW REQUESTED THIS HOWEVER
 THE PLANS DO NOT SHOW ANY OF THE INFORMATION. PLEASE BE
 AWARE OF LIGHTING WHICH IS ALREADY IN PLACE UNDER THE
 BASE BUILDING. THIS LIGHTING WHICH IS PART OF THE BASE
 BUILDING MUST ALSO BE INCLUDED.
  
 6) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH ALSO
 REQUESTED COMPLIANCE FOR FBC CHAPTER 13 WITH RESPECT TO
 LIGHTING CONTROLS REQUIRED PER 13-415.1.ABC.1.1, .1.2,
 AND .1.3.
 PLEASE SUBMIT SCHEDULING AND ALL MAXIMUM TIMES ON OVER
 RIDES.
  
 7) NOTE: PLEASE PLACE NOTES ON PLANS PER
 13-413.1.ABC.2.1 AND .2.2.
  
 8) NOTE: PLEASE SUBMIT THE PHOTO-METRICS AS PREVIOUSLY
 REQUESTED IN ORDER TO COMPLY WITH THE MINIMUM LIGHTING
 LEVELS IN THE LIFE SAFETY CODE.
 PLEASE SEE 7.8, 7.9 AND 7.8.1.3, 7.9.2.2 FOR MINIMUM
 LEVELS.
 PLEASE ALSO SEE FAC 61G15-33.004
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION WITH PLANS.
  
 9) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW SHEET
 E-6 SHOWS A NEW PANEL LP, HOWEVER THISPANEL IS NOT ON
 THE BASE BUILDING PLANS. IF THIS IS GOING TO BE A NEW
 PANEL THEN PLEASE SUBMIT LOAD CALCULATIONS, RISER
 DIAGRAM ON HOW AND WHERE THIS PANEL IS BEING FED ETC.
 PLEASEBE SURE ALL ITEMS TO BE SUBMITTED COORDINATE
 WITH THE 2005 NFPA-70 210,220,230,215.5,240.4,310.16
 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 10) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE
 KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME. PLEASE
 ALSO KNOW THIS OFFICE IS NOW RETAINING PLANS DUE TO
 REPEAT COMMENTS.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-04-23 17:25:402008-04-23 17:25:40
  
 PLAN REVIEW WILL BE IN A FAILED STATUS, NOTES TO
 FOLLOW.