Plan Review Notes
Plan Review Notes For Permit 08010504
Permit Number 08010504
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-02-27 11:07:01***DENIED***
  
 1) THE FLOW TEST DATE OF 12/5/06 IS NOT COMPLIANT WITH
 THE ONE YEAR DATA REQUIREMENT. IF FLOW DATE HAS BEEN
 UPDATED, PLEASE INCLUDE INFORMATION.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR
 INSTALLATION OR REMODEL OF FIRE SPRINKLER SYSTEM.
  
 3) PLANS ILLUSTRATE A NEW CHAIN LINK FENCE AND GATE.
 FIRE PROTECTION EQUIPMENT INCLUDING THE FIRE DEPARTMENT
 CONNECTION SHALL NOT BE OBSTRUCTED AND MAINTAIN PROPER
 CLEARANCES. PLEASE SHOW HOW FDC WILL BE ACCESSED BY
 FIRE APPARATUS.
  
 4) SHEET FP-1 SHOWS BOTH FDC BREAK OFF CAPS AND KNOX
 LOCKING CAPS. NEW INSTALLATIONS ARE REQUIRED TO BE
 SECURED WITH KNOX LOCKING CAPS. AN APPLICATION CAN BE
 OBTAINED FROM BUREAU OF FIRE PREVENTION. (561)
 804-4724
  
 5) PLANS SHOW PHASING OF PROJECT ON ELECTRICAL SHEETS.
 PLEASE INDICATE ALL REQUIRED MEANS OF EGRESS.
  
 6) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 7) NEW FIRE HYDRANTS TO BE FULLY OPERATIONAL PRIOR TO,
 DURING AND AFTER CONSTRUCTION.
  
 8) APPLICATION INDICATES IN-RACK FIRE SPRINKLER SYSTEM.
 PLANS SEEM TO SHOW A NEW FIRE SPRINKLER SYSTEM FOR
 BUILDING. PLEASE CLARIFY AND AS A NOTE, MONITORING OF
 NEW FIRE SPRINKLER SYSTEMS SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE PRIOR TO FINAL INSPECTION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756