| 2008-02-27 11:07:01 | ***DENIED*** |
| | |
| | 1) THE FLOW TEST DATE OF 12/5/06 IS NOT COMPLIANT WITH |
| | THE ONE YEAR DATA REQUIREMENT. IF FLOW DATE HAS BEEN |
| | UPDATED, PLEASE INCLUDE INFORMATION. |
| | |
| | 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR |
| | INSTALLATION OR REMODEL OF FIRE SPRINKLER SYSTEM. |
| | |
| | 3) PLANS ILLUSTRATE A NEW CHAIN LINK FENCE AND GATE. |
| | FIRE PROTECTION EQUIPMENT INCLUDING THE FIRE DEPARTMENT |
| | CONNECTION SHALL NOT BE OBSTRUCTED AND MAINTAIN PROPER |
| | CLEARANCES. PLEASE SHOW HOW FDC WILL BE ACCESSED BY |
| | FIRE APPARATUS. |
| | |
| | 4) SHEET FP-1 SHOWS BOTH FDC BREAK OFF CAPS AND KNOX |
| | LOCKING CAPS. NEW INSTALLATIONS ARE REQUIRED TO BE |
| | SECURED WITH KNOX LOCKING CAPS. AN APPLICATION CAN BE |
| | OBTAINED FROM BUREAU OF FIRE PREVENTION. (561) |
| | 804-4724 |
| | |
| | 5) PLANS SHOW PHASING OF PROJECT ON ELECTRICAL SHEETS. |
| | PLEASE INDICATE ALL REQUIRED MEANS OF EGRESS. |
| | |
| | 6) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. |
| | |
| | 7) NEW FIRE HYDRANTS TO BE FULLY OPERATIONAL PRIOR TO, |
| | DURING AND AFTER CONSTRUCTION. |
| | |
| | 8) APPLICATION INDICATES IN-RACK FIRE SPRINKLER SYSTEM. |
| | PLANS SEEM TO SHOW A NEW FIRE SPRINKLER SYSTEM FOR |
| | BUILDING. PLEASE CLARIFY AND AS A NOTE, MONITORING OF |
| | NEW FIRE SPRINKLER SYSTEMS SHALL BE UL CERTIFIED FOR |
| | CENTRAL STATION SERVICE PRIOR TO FINAL INSPECTION. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |