Plan Review Notes
Plan Review Notes For Permit 08010504
Permit Number 08010504
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-31 13:01:46** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE TITLE BLOCK FOR THE ENGINEERING
 FIRM IS MISSING THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE SEE FAC 61G15-23.002, FS 471.023
  
 2) NOTE: PLEASE BE SURE WHEN SEALING PLANS THE ENTIRE
 SEAL IS CLEAR AND VISIBLE WITH ALL INFORMATION ON SAID
 SEAL. FS 471.025
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER FBC CHAPTER 13, 13-415.2.
 PLEASE BE SURE ALL FIXTURES ON PLANS COORDINATE WITH A
 FIXTURE LEGEND TO BE SUBMITTED.
  
 4) NOTE: PLEASE SUBMIT TIMES ON SCHEDULING OF LIGHTING
 CONTROL PANEL AND MAXIMUM TIMES OF OVER RIDE DEVICES
 PER 13-415.1.ABC.1.1, .1.2.
  
 5) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER
 13-413.1.ABC.2.1, AND .2.2.
  
 6) NOTE: PLEASE PROVIDE VOLTAGE DROP INFORMATION PER
 13-413.1ABC.1
  
 7) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR MINIMUM
 LIGHTING LEVELS UNDER NORMAL CONDITIONS AS WELL AS
 MINIMUM LEVELS UNDER EMERGENCY CONDITIONS PER LS 7.8
 AND 7.9. PLEASE SEE SPECIFIC AREAS SUCH AS STAIRS ARE
 UNDER 7.8.1.3 AND 7.9.2.2.
 FAC 61G15-33.004
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 8) NOTE: PLEASE SEE SHEET E-6.0 SHOWS A NEW PANEL LP ,
 YET DOES NOT SHOW ANY INFORMATION WHERE THIS PANEL IS
 BEING FED FROM, LOAD CALCULATIONS ON EXISTING EQUIPMENT
 WHICH FEEDS THIS PANEL ETC.
 FEEDERS, GROUNDING, LOADS, OVER CURRENT PROTECTION
 ETC.
 PLEASE SEE 210, 220, 230, 215.5, 240.4, 310.16 ETC FBC
 106.3.5.1.2, 106.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED FOR REVIEW A COMPLETE REVIEW CAN NOT BE DONE
 AT THIS TIME.
 PLEASE ALSO KNOW THERE MAY VERY WELL BE NEW COMMENTS ON
 THE FOLLOWING REVIEW BASED ON INFORMATION WHICH WILL BE
 IN REVIEW FOR THE FIRST TIME.
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-01-30 20:05:44IN ELEC FOR REVIEW