| 2008-01-31 13:01:46 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE TITLE BLOCK FOR THE ENGINEERING |
| | FIRM IS MISSING THE REQUIRED CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | PLEASE SEE FAC 61G15-23.002, FS 471.023 |
| | |
| | 2) NOTE: PLEASE BE SURE WHEN SEALING PLANS THE ENTIRE |
| | SEAL IS CLEAR AND VISIBLE WITH ALL INFORMATION ON SAID |
| | SEAL. FS 471.025 |
| | |
| | 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS PER FBC CHAPTER 13, 13-415.2. |
| | PLEASE BE SURE ALL FIXTURES ON PLANS COORDINATE WITH A |
| | FIXTURE LEGEND TO BE SUBMITTED. |
| | |
| | 4) NOTE: PLEASE SUBMIT TIMES ON SCHEDULING OF LIGHTING |
| | CONTROL PANEL AND MAXIMUM TIMES OF OVER RIDE DEVICES |
| | PER 13-415.1.ABC.1.1, .1.2. |
| | |
| | 5) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER |
| | 13-413.1.ABC.2.1, AND .2.2. |
| | |
| | 6) NOTE: PLEASE PROVIDE VOLTAGE DROP INFORMATION PER |
| | 13-413.1ABC.1 |
| | |
| | 7) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR MINIMUM |
| | LIGHTING LEVELS UNDER NORMAL CONDITIONS AS WELL AS |
| | MINIMUM LEVELS UNDER EMERGENCY CONDITIONS PER LS 7.8 |
| | AND 7.9. PLEASE SEE SPECIFIC AREAS SUCH AS STAIRS ARE |
| | UNDER 7.8.1.3 AND 7.9.2.2. |
| | FAC 61G15-33.004 |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION. |
| | |
| | 8) NOTE: PLEASE SEE SHEET E-6.0 SHOWS A NEW PANEL LP , |
| | YET DOES NOT SHOW ANY INFORMATION WHERE THIS PANEL IS |
| | BEING FED FROM, LOAD CALCULATIONS ON EXISTING EQUIPMENT |
| | WHICH FEEDS THIS PANEL ETC. |
| | FEEDERS, GROUNDING, LOADS, OVER CURRENT PROTECTION |
| | ETC. |
| | PLEASE SEE 210, 220, 230, 215.5, 240.4, 310.16 ETC FBC |
| | 106.3.5.1.2, 106.1.2 ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION. |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| | SUBMITTED FOR REVIEW A COMPLETE REVIEW CAN NOT BE DONE |
| | AT THIS TIME. |
| | PLEASE ALSO KNOW THERE MAY VERY WELL BE NEW COMMENTS ON |
| | THE FOLLOWING REVIEW BASED ON INFORMATION WHICH WILL BE |
| | IN REVIEW FOR THE FIRST TIME. |
| | |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-01-30 20:05:44 | IN ELEC FOR REVIEW |