2008-02-25 12:51:31BUILDING PLAN REVIEW
 PERMIT: 08010504
 ADD: 3501 ELECTRONICS WAY
 CONT: UNITED GENERAL CONTRACTORS
 TEL: (561)422-0755
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 2-25-08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2)DUE TO THE FACT THAT THE MASTER PERMIT IS NOT
 ISSUED AT THIS TIME, THESE DRAWINGS SHALL BE REVIEWED
 AND BY THE DESIGN TEAM OF THE BASE BUILDING. THE PLANS
 SHALL CONTAIN AN APPROVED REVIEW STAMP BY THE DESIGNERS
 OF THE BASE BUILDING.
  
 3)PROVIDE THE LIFE SAFETY PLAN WHICH SHALL INCLUDE
 EXIT ACCESS / EXIT / EXIT DISCHARGE / HORIZONTAL EXITS
 / EXIT PASSAGEWAYS.
  
 4)FBC 1004.1.1 THE DESIGN OCCUPANT LOAD SHALL BE
 INDICATED ON THE DRAWINGS IN DETERMINING MEANS OF
 EGRESS REQUIREMENTS. THE NUMBER OF OCCUPANTS FOR WHOM
 MEANS OF EGRESS FACILITIES SHALL BE PROVIDED SHALL BE
 ESTABLISHED BY THE LARGEST NUMBER COMPUTED IN
 ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH 1004.1.3.
  
 5)WPB AMENDMENTS 106.1.3 BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]