| 2008-01-29 18:56:37 | ** PROVISO/REVISION NEEDED ** |
| | |
| | ** PLEASE SEE THE FOLLOWING ITEMS WERE REDLINED ON |
| | PLANS OR NEED TO BE UPDATED BEFORE FINAL ELECTRICAL |
| | INSPECTION. |
| | ** PLEASE KNOW ANY OTHER REVISIONS SHALL BE SUBMITTED |
| | BEFORE ROUGH ELECTRICAL INSPECTION. |
| | |
| | ** ALL REVISED PLANS FOR ROUGH OR FINAL ARE REQUIRED TO |
| | BE ON-SITE FOR ELECTRICAL INSPECTOR STAMPED AS REVIEWED |
| | BY PLAN REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE THE CODE SECTION NOTED FOR |
| | EMERGENCY LIGHTS AHEAD OF LOCAL BRANCH CIRCUITS ON |
| | SHEETS E-4 AND E-6 (NOTE #2) CHANGED IN THE 2005 NEC TO |
| | 700.12(F). |
| | |
| | 2) NOTE: PLEASE LIST MAXIMUM TIMES FOR OCCUPANCY SENSOR |
| | TYPE DEVICES PER 13-415.1.ABC.1.1 AND .1.2. MAXIMUM |
| | TIMES REDLINED ON PLANS AS 30MINS AFTER THE LAST |
| | SENSING OF AN OCCUPANT. |
| | |
| | 3) NOTE: PLEASE KNOW THE PANEL SCHEDULES FOR NEW |
| | CIRCUITING WILL BE REQUIRED TO BE REVISED TO SPECIFIC |
| | TO ROOMS AND AREAS IN WHICH THEY FEED.THIS SHOULD BE |
| | DONE BY ROOM NAME/NUMERICAL DESIGNATIONS AS LISTED ON |
| | PLANS. |
| | FOR EXAMPLE: ROOM 1824/PANTRY RECEPTS, ROOM 1822 |
| | LIBRARY RECEPTS, LIGHTS ROOM 1942/LIBRARY, ETC. THIS IS |
| | FOR JOB-SITE AS WELL AS FINAL RECORD PLANS FOR *NEW |
| | CIRCUITS* AND *RE-LOCATED* CIRCUITS WHICH MAY BE |
| | AFFECTED BY CONSTRUCTION SCOPE OF WORK. |
| | NEC 408.4 |
| | FBC ADMIN SECTION, 106.1.2, 106.3.5.1.2, 106.5 |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS |
| | OFFICE/REVIEW AT THE CONTACT INFORMATION BELOW. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |