Plan Review Notes
Plan Review Notes For Permit 08010447
Permit Number 08010447
Review Stop B
Sequence Number 2
Notes
Date Text
2008-02-04 09:30:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 FROM PREVIOUS LIST:
  
 1.ADDRESSED.
  
 2.PROVIDE TWO COMPLETE COLLATED SETS OF DOCUMENTS FOR
 PERMIT ISSUANCE.
  
 DUE TO WORKLOAD, CONTRACTORS ARE REQUIRED TO PROVIDE
 TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS.ONLY
 ONE FLOOR PLAN WAS SUBMITTED.
  
 NEW COMMENT:
  
 3.THE INSTALLATION SCHEDULE IS INCOMPLETE.PLEASE
 INCLUDE EDGE DISTANCE AND SHUTTER MOUNTING CONNECTION
 TYPE.WITHOUT THIS INFORMATION, CODE COMPLIANCE CANNOT
 BE DETERMINED.
  
 SEE THE HIGHLIGHTED PRODUCT APPROVAL.PLEASE INDICATE
 WHICH OF THE FIVE ANCHORS YOU ARE USING.YOU'VE STATED
 "STAINLESS"; AREN'T THEY ALL STAINLESS?
  
 CONNECTION MOUNTING TYPE SHOULD CORRELATE WITH THE
 ANCHOR CHART ON SHEET 4; IN THIS CASE, THE CHOICES ARE
 C1 THROUGH C5.NOTE THAT NOT ALL ANCHORS ARE PERMITTED
 DEPENDING ON MOUNTING TYPE, ANCHOR TYPE, EDGE DISTANCE.
 FROM THE INFORMATION PROVIDED I CANNOT DETERMINE
 WHETHER OR NOT THE 6" AND 12" SPECIFIED ARE COMPLIANT.
  
  
  