Plan Review Notes
Plan Review Notes For Permit 08010437
Permit Number 08010437
Review Stop E
Sequence Number 2
Notes
Date Text
2008-06-02 17:25:52** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE ONCE AGAIN PLANS ARE SUBMITTED
 WITHOUT BEING SUBMITTED BY A CONTRACTOR FOR PERMIT
 APPLICATION. PLEASE KNOW EVEN ONCE ALL CODE COMMENTS
 ARE ADDRESSED PLANS WILL STILL REMAIN IN A FAILED
 STATUS UNTIL PERMIT APPLICATION IS MADE. THERE ARE MANY
 ITEMS REVIEWED AND VERIFIED ONCE APPLICATION IS MADE
 AND NEED TO BE DONE AT THAT TIME.
  
 2) NOTE: PLEASE SEE ONCE AGAIN TITLE BLOCKS AND
 LICENSING INFORMATION HAS NOT BEEN CORRECTED. PLEASE
 SEE TITLE BLOCKS STILL SHOW *AR* INSTEAD OF AN *AA* OR
 *AAC* FOR ARCHITECTURAL BUSINESS. PLEASE SEE ONCE AGAIN
 THE LICENSING ON SOME SHEETS FOR MORSE ASSOCIATES IS
 NOT THE SAME ON ALL SHEETS. PLEASE KNOW THE LICENSING
 SHOWN ON ELECTRICAL SHEETS DOES NOT COME UP AS VALID
 WITH THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION.
 PLEASE SUPPLY INFORMATION ON WHICH ENGINEERS WORK FOR
 WHICH FIRM. AS DYANKI SHOWN ON TITLE BLOCKS IS THE ONLY
 FIRM LISTED WITH AN ENGINEERING BUSINESS LICENSE NUMBER
 IT IS UNCLEAR OF THE ARCHITECTURAL FIRM BEING LISTED.
 IT IS ALSO NOT CLEAR WHY THERE ARE STILL TWO SEPARATE
 LICENSE NUMBERS.
 LICENSING FOR NAME AND FIRMS LISTED HAS BEEN NOTED ON
 NUMEROUS REVIEWS BY THIS OFFICE ON MULTIPLE PROJECTS TO
 BE COORDINATED AND FINALIZED YET THIS STILL COMES BACK
 AS AN ISSUE.
 PLEASE SEE FLORIDA STATUTES 481.219, 471.023 AND
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004, 61G15-23.002
 FOR INFORMATION NEEDED AND REQUIRED.
  
 3) NOTE: PLEASE SEE ONCE AGAIN INCOMPLETE METHOD *A*
 CALCULATIONS ARE STILL BEING SUBMITTED. MAY NOT USE OR
 SUBMIT METHOD *A* CALCULATIONS UNLESS COMPLYING WITH
 THE CODE FOR WHOLE BUILDING AS VERSION STATES.
 PLEASE ALSO KNOW PER 13-400.A.3 VERSION 3.0 IS NOT
 ADOPTED BY THE STATE OF FLORIDA OR THE FLORIDA BUILDING
 CODE.
 CALCULATIONS SUBMITTED ARE NOT REVIEWED FOR ANY
 ELECTRICAL CODE COMPLIANCE. IF SCOPE OF WORK IS TO
 INCLUDE ALL ELECTRICAL AS INDICATED, THEN PLANS WILL BE
 REQUIRED TO MEET CHAPTER 13 UNDER THE 2004 W/2007
 REVISIONS.
  
 4) NOTE: PLEASE SEE THE REVISED ELECTRICAL RISER WHICH
 APPEARS TO NOW BE SHOWING THE EXISTING MAIN LUG ONLY
 ENCLOSURE BEING CONVERTED TO A JUNCTION BOX HOWEVER
 THIS COULD NOT BE DONE AS SHOW.
 THE PLANS STILL SHOW THE PANEL SCHEDULE FOR THE SWB
 WHICH WOULD ACTUALLY NO LONGER EXISTS.
 THIS WOULD NOW CONTAIN PROTECTED AND UN-PROTECTED (LINE
 AND LOAD) CONDUCTORS IN THE SAME ENCLOSURE WHICH IS NOT
 PERMITTED.
 PLEASE SEE THAT NO MORE THAN 8FT OF UNPROTECTED
 CONDUCTORS ARE PERMITTED INSIDE THE BUILDING.
 PLEASE SEE NEW PROPOSED MSD ALSO DOES NOT CONTAIN ANY
 MAIN YET THERE ARE MORE THAN 6 SPACES WHICH ARE NOT
 PERMITTED.
 PLEASE SEE THAT ONCE A MAIN IS INSTALLED GF PROTECTION
 WILL BE REQUIRED.
 NOTE # 2 TO GENERAL NOTES ON RISER MENTIONS THE
 ALTERNATIVE FOR SERVICE INTO VAULT. THIS WOULD NEED TO
 BE SHOWN AT THIS TIME.
  
 230.70, 230.71, 230.72, 240.13, 230.95.300.3B ETC
  
 ** AS NOTED ON PREVIOUS REVIEW AS SOME ITEMS ARE NOT
 CLEAR YET AND SOME INFORMATION IS NOT YET SHOWN PLEASE
 KNOW THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  