| 2008-06-02 17:25:52 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE: PLEASE SEE ONCE AGAIN PLANS ARE SUBMITTED |
| | WITHOUT BEING SUBMITTED BY A CONTRACTOR FOR PERMIT |
| | APPLICATION. PLEASE KNOW EVEN ONCE ALL CODE COMMENTS |
| | ARE ADDRESSED PLANS WILL STILL REMAIN IN A FAILED |
| | STATUS UNTIL PERMIT APPLICATION IS MADE. THERE ARE MANY |
| | ITEMS REVIEWED AND VERIFIED ONCE APPLICATION IS MADE |
| | AND NEED TO BE DONE AT THAT TIME. |
| | |
| | 2) NOTE: PLEASE SEE ONCE AGAIN TITLE BLOCKS AND |
| | LICENSING INFORMATION HAS NOT BEEN CORRECTED. PLEASE |
| | SEE TITLE BLOCKS STILL SHOW *AR* INSTEAD OF AN *AA* OR |
| | *AAC* FOR ARCHITECTURAL BUSINESS. PLEASE SEE ONCE AGAIN |
| | THE LICENSING ON SOME SHEETS FOR MORSE ASSOCIATES IS |
| | NOT THE SAME ON ALL SHEETS. PLEASE KNOW THE LICENSING |
| | SHOWN ON ELECTRICAL SHEETS DOES NOT COME UP AS VALID |
| | WITH THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION. |
| | PLEASE SUPPLY INFORMATION ON WHICH ENGINEERS WORK FOR |
| | WHICH FIRM. AS DYANKI SHOWN ON TITLE BLOCKS IS THE ONLY |
| | FIRM LISTED WITH AN ENGINEERING BUSINESS LICENSE NUMBER |
| | IT IS UNCLEAR OF THE ARCHITECTURAL FIRM BEING LISTED. |
| | IT IS ALSO NOT CLEAR WHY THERE ARE STILL TWO SEPARATE |
| | LICENSE NUMBERS. |
| | LICENSING FOR NAME AND FIRMS LISTED HAS BEEN NOTED ON |
| | NUMEROUS REVIEWS BY THIS OFFICE ON MULTIPLE PROJECTS TO |
| | BE COORDINATED AND FINALIZED YET THIS STILL COMES BACK |
| | AS AN ISSUE. |
| | PLEASE SEE FLORIDA STATUTES 481.219, 471.023 AND |
| | FLORIDA ADMINISTRATIVE CODE 61G1-16.004, 61G15-23.002 |
| | FOR INFORMATION NEEDED AND REQUIRED. |
| | |
| | 3) NOTE: PLEASE SEE ONCE AGAIN INCOMPLETE METHOD *A* |
| | CALCULATIONS ARE STILL BEING SUBMITTED. MAY NOT USE OR |
| | SUBMIT METHOD *A* CALCULATIONS UNLESS COMPLYING WITH |
| | THE CODE FOR WHOLE BUILDING AS VERSION STATES. |
| | PLEASE ALSO KNOW PER 13-400.A.3 VERSION 3.0 IS NOT |
| | ADOPTED BY THE STATE OF FLORIDA OR THE FLORIDA BUILDING |
| | CODE. |
| | CALCULATIONS SUBMITTED ARE NOT REVIEWED FOR ANY |
| | ELECTRICAL CODE COMPLIANCE. IF SCOPE OF WORK IS TO |
| | INCLUDE ALL ELECTRICAL AS INDICATED, THEN PLANS WILL BE |
| | REQUIRED TO MEET CHAPTER 13 UNDER THE 2004 W/2007 |
| | REVISIONS. |
| | |
| | 4) NOTE: PLEASE SEE THE REVISED ELECTRICAL RISER WHICH |
| | APPEARS TO NOW BE SHOWING THE EXISTING MAIN LUG ONLY |
| | ENCLOSURE BEING CONVERTED TO A JUNCTION BOX HOWEVER |
| | THIS COULD NOT BE DONE AS SHOW. |
| | THE PLANS STILL SHOW THE PANEL SCHEDULE FOR THE SWB |
| | WHICH WOULD ACTUALLY NO LONGER EXISTS. |
| | THIS WOULD NOW CONTAIN PROTECTED AND UN-PROTECTED (LINE |
| | AND LOAD) CONDUCTORS IN THE SAME ENCLOSURE WHICH IS NOT |
| | PERMITTED. |
| | PLEASE SEE THAT NO MORE THAN 8FT OF UNPROTECTED |
| | CONDUCTORS ARE PERMITTED INSIDE THE BUILDING. |
| | PLEASE SEE NEW PROPOSED MSD ALSO DOES NOT CONTAIN ANY |
| | MAIN YET THERE ARE MORE THAN 6 SPACES WHICH ARE NOT |
| | PERMITTED. |
| | PLEASE SEE THAT ONCE A MAIN IS INSTALLED GF PROTECTION |
| | WILL BE REQUIRED. |
| | NOTE # 2 TO GENERAL NOTES ON RISER MENTIONS THE |
| | ALTERNATIVE FOR SERVICE INTO VAULT. THIS WOULD NEED TO |
| | BE SHOWN AT THIS TIME. |
| | |
| | 230.70, 230.71, 230.72, 240.13, 230.95.300.3B ETC |
| | |
| | ** AS NOTED ON PREVIOUS REVIEW AS SOME ITEMS ARE NOT |
| | CLEAR YET AND SOME INFORMATION IS NOT YET SHOWN PLEASE |
| | KNOW THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW |
| | WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |