| 2008-06-04 07:35:16 | BUILDING PLAN REVIEW |
| | PERMIT: 08010437 |
| | ADD: 1041 45TH ST |
| | CONT: ** PLAN REVIEW** |
| | TEL: (561)718-4140 JON VANDERBERG |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW"PLAN REVIEW" |
| | ACTION: DENIED |
| | |
| | 1A-C) COMPLIED |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) COMPLIED. |
| | |
| | 2)COMPLIED. |
| | |
| | 3) COMPLIED, NOTED.T |
| | |
| | 4)2ND REQUEST, PLANS DO NOT INDICATE THE CORRIDOR |
| | WALLS AS THE REQUIRED SMOKE PARTITIONS (407.3). THE |
| | PLANS WILL ALSO NEED TO INDICATE THE SMOKE BARRIER |
| | WALLS THAT ARE REQUIRED IN 407.3 AND ALSO INDICATE |
| | COMPLIANCE WITH 407.4.1 REFUGE AREA PER PATIENT WITHIN |
| | THE AGGREGATE AREA OF CORRIDORS, PATENIT ROOMS |
| | TREATMENT ROOMS LOUNGE OR DINING ROOMS AND OTHER LOW |
| | HAZARD AREAS ON EACH SIDE OF EACH SMOKE BARRIER. |
| | |
| | ON VARIOUS SHEETS WHERE THE DUCTS CROSS SMOKE BARRIERS |
| | FROM ONE CHAMBER TO ANOTHER THE DUCTS ARE MISSING SMOKE |
| | DAMPERS. PLEASE ILLUSTRATE CODE COMPLIANCE WITH 716.1.1 |
| | AND OR 712.3. AND 712.3.4. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | |
| | |
| | |