2008-02-13 19:20:15REVIEW #: 1ST *PLAN CHECK ONLY*
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. INDEX PAGE, SHEET METAL DUCT INSTALLATION NOTES,
 NOTE #7: THIS NOTE INDICATES THAT THE EXCEPTION LISTED
 IN THE NOTE APPLIES TO DUCT PENETRATIONS IN RATED WALLS
 AND PARTITIONS. THIS IS NOT ACCURATE AS THE EXCEPTION
 MAY ONLY BE UTILIZED IN FIRE PARTITIONS AND IS NOT
 APPLICABLE IN FIRE BARRIERS OR FIRE WALLS. SEE FBC, M
 607.5 AND FBC 702 FOR DEFINITIONS. ALSO, THERE IS NO
 INDICATION ON DUCT FLOOR PLANS, PAGES M-103 THROUGH
 M-111, OF THE LOCATIONS OF RATED ASSEMBLIES WHERE
 OPENING PROTECTIVES WILL BE REQUIRED. A GENERAL NOTE
 CALLING FOR PROTECTION OF PENETRATIONS IN RATED WALLS
 IS NOT SUFFICIENT TO DEMONSTRATE CODE COMPLIANCE. THE
 SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH FIRE
 DOOR, FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER
 SHALL BE SHOWN AND PROPERLY IDENTIFIED ON THE BUILDING
 PLANS BY THE DESIGNER IN ACCORDANCE WITH FBC, M 607.8.
 PLEASE INDICATE ON THE PLANS THE LOCATION OF ANY RATED
 WALL OR CEILING ASSEMBLIES AS WELL AS THE OPENING
 PROTECTIVE METHODS DEPLOYED AT ALL PENETRATIONS OF
 THESE ASSEMBLIES TO DEMONSTRATE COMPLIANCE WITH THIS
 SECTION.
  
 2. INDEX PAGE, GENERAL SCOPE OF WORK, NOTE #7 CALLS FOR
 ALL EXISTING ATTIC INSULATION TO BE REMOVED WITH NEW
 R-19 INSULATION TO BE INSTALLED. DETAIL #1 ON PG M-502
 SHOWS INSULATION BEING INSTALLED ABOVE A HARD CEILING.
 HOWEVER, GENERAL HVAC NOTE #21 STATES THAT GYPSUM
 CEILING AREAS ARE LIMITED WHICH INDICATES THAT MOST
 CEILING AREAS CONSIST OF LAY-IN TILE TYPE CEILINGS. HOW
 WILL THE NEW INSULATION BE INSTALLED IN THESE GRID
 CEILING AREAS? ROOF INSULATION SHALL NOT BE INSTALLED
 ON A SUSPENDED CEILING WITH REMOVABLE CEILING PANELS IN
 ACCORDANCE WITH FBC 13-404.1.ABC.1. SHOW HOW NEW
 INSULATION IS TO BE INSTALLED IN THESE AREAS IN
 ACCORDANCE WITH THIS SECTION.
  
 3. ENERGY CALCULATIONS: METHOD A CALCULATIONS ARE NOT
 APPROPRIATE FOR THIS PROPOSED PROJECT. EXISTING
 BUILDINGS NOT MEETING THE DEFINITION OF A RENOVATION
 (SEE 13-202) IN WHICH NEW HEATING, COOLING, WATER
 HEATING, ELECTRICAL OR LIGHTING SYSTEMS ARE INSTALLED
 SHALL MEET THE BASIC PRESCRIPTIVE MINIMUM EFFICIENCIES
 LISTED IN THIS CODE FOR THE SYSTEM(S) BEING CHANGED IN
 ACCORDANCE WITH FBC 13-400.0.C.4. ALL NEW MECHANICAL
 COMPONENTS SHOWN ON PLANS ARE SHOWN TO MEET THE
 PRESCRIPTIVE MINIMUM EFFICIENCIES. NO COMPLIANCE FORM
 IS NEEDED TO DEMONSTRATE COMPLIANCE WITH THE MECHANICAL
 PORTIONS OF FBC CHAPTER 13. METHOD A CALCULATIONS SHALL
 ONLY BE USED UNDER THE CONDITIONS AS STATED IN FBC
 13-101.4.2. ENERGY CALCULATIONS WHICH HAVE BEEN
 SUBMITTED WILL NOT BE REVIEWED FOR MECHANICAL AS THEY
 ARE NOT NEEDED.
  
 4. PG M-501: DETAIL #3, CONDENSATE NOTE INDICATES
 CONDENSATE MAY DISCHARGE INTO A FLOOR/SANITARY DRAIN.
 AIR CONDITIONING CONDENSATE SHALL NOT DISCHARGE INTO
 THE SANITARY SEWER SYSTEM IN ACCORDANCE WITH CITY OF
 WPB MUNICIPAL CODE 31-62(5). ALSO, PLEASE SHOW MEANS
 AND LOCATION OF CONDENSATE FOR AHU-7 AND NEW MINI-SPLIT
 SYSTEM IN ACCORDANCE WITH FBC, M 307.2.1.
  
 5. PG M-501: DETAIL #6 PROVIDES A DETAIL FOR FIRE
 DAMPER INSTALLATION. FIRE DAMPERS, SMOKE DAMPERS,
 COMBINATION FIRE/SMOKE DAMPERS AND CEILING DAMPERS
 LOCATED WITHIN AIR DISTRIBUTION AND SMOKE CONTROL
 SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 REQUIREMENTS OF THIS SECTION, AND THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS AND LISTING PER FBC, M 607.2.
 THE PROVIDED DETAIL MAY BE IN CONFLICT WITH
 MANUFACTURER?S INSTRUCTIONS.
 6. PG M-502: DETAIL #7, DOWNDRAFT RTUS SHALL HAVE
 AUXILIARY DRAIN PROTECTION IN ACCORDANCE WITH FBC, M
 307.2.3. THIS MAY BE ACCOMPLISHED WITH THE INSTALLATION
 OF A WATER LEVEL DETECTION DEVICE INSIDE THE UNIT ON
 THE PRIMARY DRAIN PAN. IF THE PRIMARY DRAIN WERE TO
 OVERFLOW, IT IS LIKELY IT WOULD DRAIN INTO THE BUILDING
 IN VIOLATION OF THIS SECTION.
  
 7. PG M-701 AND M-702: WIND LOAD CALCULATIONS FOR
 OUTDOOR UNITS ARE SUBJECT TO BUILDING PLAN REVIEW. IN
 ADDITION, EQUIPMENT AND APPLIANCES THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING PER FBC, M 301.13. PROVIDE DOCUMENTATION
 SHOWING SPECIFIED EQUIPMENT HAS BEEN TESTED TO
 WITHSTAND ANTICIPATED WIND PRESSURES IN ACCORDANCE WITH
 THIS SECTION.
  
 8. PLEASE SEE ELECTRICAL REVIEW COMMENT #2 REGARDING
 DESIGN PROFESSIONAL LICENSURE REQUIREMENTS.
  
 NOTE: THIS PLAN HAS BEEN SUBMITTED FOR PLAN REVIEW ONLY
 AND NOT FOR PERMIT. ONCE PERMIT HAS BEEN APPLIED FOR,
 PLANS WILL BE REQUIRED TO COMPLY WITH THE CODE VERSION
 IN EFFECT AT THE TIME OF APPLICATION. ONCE ALL COMMENTS
 ARE ADDRESSED, REVIEW WILL REMAIN IN FAILED STATUS
 UNTIL TIME OF APPLICATION AND VERIFICATION THAT THE
 PLANS HAVE BEEN REVIEWED UNDER THE CORRECT CODE CYCLE.
  
 PLEASE RESPOND TO ALL REVIEW COMMENTS IN WRITING WITH
 INFORMATION ON HOW COMMENTS HAVE BEEN ADDRESSED AND
 WHERE THE REQUESTED INFORMATION CAN BE FOUND IN ORDER
 TO SPEED THE REVIEW PROCESS. ADDITIONALLY, PLEASE
 RETURN ONE SET OF OLD PLANS FOR REFERENCE.
  