| Plan Review Notes For Permit 08010437 |
| Permit Number |
08010437 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-19 14:50:20 | ***DENIED*** | | | | | | THIS PLAN HAS BEEN SUBMITTED FOR PLAN REVIEW ONLY AND | | | NOT FOR PERMIT AT THIS TIME. | | | | | | 1) HOW WILL THIS WORK IMPACT EXISTING BUILDING FIRE | | | PROTECTION EQUIPMENT? (FIRE SPRINKLER, FIRE ALARM | | | ETC.) | | | | | | 2) REQUIRED MEANS OF EGRESS AND EXITS SHALL BE | | | MAINTAINED AT ALL TIMES. | | | | | | 3) THE SITE SHALL BE CLEANED DAILY OF EXCESS | | | CONSTRUCTION DEBRIS. | | | | | | 4) NEW FIRE DAMPERS TO BE TESTED FOR CLOSURE AND SHALL | | | COMPLY WITH WITH UL 555 STANDARDS PRIOR TO FINAL | | | INSPECTION. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | |
|