Plan Review Notes
Plan Review Notes For Permit 08010437
Permit Number 08010437
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-29 17:27:12** DENIED REVIEW **
  
  
 1) NOTE: PLANS ONLY SUBMITTED FOR PLAN REVIEW AND NOT
 FOR PERMIT. PLEASE BE AWARE WHEN PLANS ARE CODE
 COMPLIANT AND READY FOR ISSUANCE THE REVIEW WILL REMAIN
 IN FAILED STATUS UNTIL SUCH TIME PERMIT APPLICATION HAS
 BEEN MADE.
  
 2) NOTE: PLEASE VERIFY LICENSING OF FIRM AS LISTED ON
 SPECIFICATION BOOKS AND PLANS. PLEASE SEE FOR EXAMPLE:
 BOOKS CONTAIN *MORSE, ZEHNTER ASSOCIATES* HOWEVER PLANS
 CONTAIN MORSE AND ASSOCIATES.
 PLEASE ALSO SEE THE PLANS STATE A FIRM LICENSE NUMBER
 OF AR001209. PLEASE KNOW THE AR IS FOR REGISTERED
 ARCHITECT AND THE LICENSE NUMBER AS LISTED ABOVE IS NOT
 THAT AS LISTED ON THE STATE OF FLORIDA DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION WEBSITE. PLEASE
 SEE ATTACHED PRINT OUT FROM DPBR WHICH SHOWS THE
 CURRENT NAME AND LICENSURE INFORMATION.
 PLEASE SEE FAC 61G1-16.004, AND FS 481.219 FOR
 INFORMATION REQUIRED TO COORDINATE.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES FOR REVIEW.
  
 3) NOTE: PLEASE SEE THE SPECIFICATION BOOK HAS A METHOD
 *A* SUBMITTED FOR ENERGY CALCULATIONS WHICH DOES NOT
 SEEM POSSIBLE. PLEASE SEE COMMENTS FROM MECHANICAL
 REVIEW.
 PLEASE KNOW THIS IS NOT A WHOLE BUILDING WITH ALL NEW
 COMPONENTS.
 PLEASE SEE THIS ALSO DOES NOT FALL UNDER RENOVATIONS.
 PLEASE SEE ENERGY CALCULATIONS ARE BEING SHOWN WITH ALL
 NEW LIGHTING YET THE SCOPE OF WORK AND PLANS SUBMITTED
 DO NOT COORDINATE WITH ANY OF THIS.
  
 PLEASE SEE FBC CHAPTER 13, 13-101.1 (ALL), 13-415.2 AND
 OTHER SECTIONS WHICH MAY BE REFLECTED UNDER MECHANICAL
 REVIEW.
  
 4) NOTE: PLEASE SEE ALL GROUNDING ON THE SECONDARY
 SIDES OF TRANSFORMERS SHALL BE CONNECTED TO AN
 EFFECTIVE GROUNDING ELECTRODE SOURCE. THE COLD WATER
 PIPE AS THE SOLE CONNECTION IS NOT ACCEPTABLE DUE TO
 SEVERAL INTERRUPTIONS IN A COLD WATER PIPE WHICH WILL
 AFFECT AN EFFECTIVE BOND. PLEASE KNOW FOR EXAMPLE: PVC
 INTERCONNECTION POINTS, UNION FITTINGS ETC.
 PLEASE SEE 250.30, 250.50, 250.53, 250.58 ETC. THIS
 COMMENT IS FOR NEW AS WELL AS EXISTING 225K UNIT WHICH
 ONLY NOTES CWP FOR CONNECTION.
  
 5) NOTE: PLEASE KNOW ANY CONNECTIONS OF SYSTEMS,
 PANELS, LOADS, CONDUCTORS ETC TO THE EXISTING SERVICE
 WILL REQUIRE THE SERVICE AS SHOWN(MAIN SWITCH GEAR)
 TO BE BROUGHT UP TO CODE.THE SERVICE AS SHOWN DOES
 NOT MEET CURRENT CODE FOR MANY ITEMS AND ANY CHANGE IN
 SERVICE OR SYSTEMS OF SERVICE WILL REQUIRE THIS TO BE
 BROUGHT UP TO CURRENT CODE.
 THIS WAS CONFIRMED ALL OTHER ELECTRICAL PLAN REVIEW
 STAFF AS WELL AS THE CHIEF ELECTRICAL INSPECTOR OVER
 INSPECTIONS. THE SERVICE AS SHOWN WHICH EXISTS DOES NOT
 COMPLY WITH THE CURRENT CODE OR CODES GOING BACK FOR
 DECADES. THERE ARE SEVERAL SAFETY ISSUES ON THIS
 SERVICE FROM PROTECTION OF CONDUCTORS, EFFECTIVE
 GROUNDING, TAPPED CONDUCTORS, OVER LOADING ETC. PLEASE
 SEE THE MAIN SWITCH BOARD DOES NOT SHOW ANY SEPARATION
 OF SYSTEMS BASED ON PLANS SUBMITTED. PLEASE SEE THE
 MAIN SWITCH BOARD DOES NOT INDICATE ALL POSSIBLE
 MAINS.
 PLEASE SEE THE MAIN SWITCH BOARD WHICH IS SHOWN FEEDING
 OUT TO THE 225K TRANSFORMER SHOWS THESE CONDUCTORS
 COMING BACK INTO A MLO 800A BUS WITH NO TERMINATION
 INTO A SINGLE MEANS OF OVER CURRENT PROTECTION OF ANY
 KIND.
 PLEASE SEE THE TAPPED CONDUCTORS ON THE SECONDARY SIDE
 OF THIS SAME 225K TRANSFORMER ARE NOT RATED FOR
 800AMPS.
 PLEASE SEE THE FEEDERS ON SCHEDULE SHOULD COORDINATE
 WITH RISER. FOR EXAMPLE: PLEASE SEE PANEL *C*. PLEASE
 SEE 240.4, 310.16, 230.70, 230.71, 230.2, 240.21,
 240.13, ETC
 THERE ARE TOO MANY SECTIONS TO LIST.
  
 * PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH MAY
 CHANGE, THERE MAY VERY WELL BE NEW COMMENTS ON THE NEXT
 REVIEW.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]