| 2008-01-29 17:27:12 | ** DENIED REVIEW ** |
| | |
| | |
| | 1) NOTE: PLANS ONLY SUBMITTED FOR PLAN REVIEW AND NOT |
| | FOR PERMIT. PLEASE BE AWARE WHEN PLANS ARE CODE |
| | COMPLIANT AND READY FOR ISSUANCE THE REVIEW WILL REMAIN |
| | IN FAILED STATUS UNTIL SUCH TIME PERMIT APPLICATION HAS |
| | BEEN MADE. |
| | |
| | 2) NOTE: PLEASE VERIFY LICENSING OF FIRM AS LISTED ON |
| | SPECIFICATION BOOKS AND PLANS. PLEASE SEE FOR EXAMPLE: |
| | BOOKS CONTAIN *MORSE, ZEHNTER ASSOCIATES* HOWEVER PLANS |
| | CONTAIN MORSE AND ASSOCIATES. |
| | PLEASE ALSO SEE THE PLANS STATE A FIRM LICENSE NUMBER |
| | OF AR001209. PLEASE KNOW THE AR IS FOR REGISTERED |
| | ARCHITECT AND THE LICENSE NUMBER AS LISTED ABOVE IS NOT |
| | THAT AS LISTED ON THE STATE OF FLORIDA DEPARTMENT OF |
| | BUSINESS AND PROFESSIONAL REGULATION WEBSITE. PLEASE |
| | SEE ATTACHED PRINT OUT FROM DPBR WHICH SHOWS THE |
| | CURRENT NAME AND LICENSURE INFORMATION. |
| | PLEASE SEE FAC 61G1-16.004, AND FS 481.219 FOR |
| | INFORMATION REQUIRED TO COORDINATE. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES FOR REVIEW. |
| | |
| | 3) NOTE: PLEASE SEE THE SPECIFICATION BOOK HAS A METHOD |
| | *A* SUBMITTED FOR ENERGY CALCULATIONS WHICH DOES NOT |
| | SEEM POSSIBLE. PLEASE SEE COMMENTS FROM MECHANICAL |
| | REVIEW. |
| | PLEASE KNOW THIS IS NOT A WHOLE BUILDING WITH ALL NEW |
| | COMPONENTS. |
| | PLEASE SEE THIS ALSO DOES NOT FALL UNDER RENOVATIONS. |
| | PLEASE SEE ENERGY CALCULATIONS ARE BEING SHOWN WITH ALL |
| | NEW LIGHTING YET THE SCOPE OF WORK AND PLANS SUBMITTED |
| | DO NOT COORDINATE WITH ANY OF THIS. |
| | |
| | PLEASE SEE FBC CHAPTER 13, 13-101.1 (ALL), 13-415.2 AND |
| | OTHER SECTIONS WHICH MAY BE REFLECTED UNDER MECHANICAL |
| | REVIEW. |
| | |
| | 4) NOTE: PLEASE SEE ALL GROUNDING ON THE SECONDARY |
| | SIDES OF TRANSFORMERS SHALL BE CONNECTED TO AN |
| | EFFECTIVE GROUNDING ELECTRODE SOURCE. THE COLD WATER |
| | PIPE AS THE SOLE CONNECTION IS NOT ACCEPTABLE DUE TO |
| | SEVERAL INTERRUPTIONS IN A COLD WATER PIPE WHICH WILL |
| | AFFECT AN EFFECTIVE BOND. PLEASE KNOW FOR EXAMPLE: PVC |
| | INTERCONNECTION POINTS, UNION FITTINGS ETC. |
| | PLEASE SEE 250.30, 250.50, 250.53, 250.58 ETC. THIS |
| | COMMENT IS FOR NEW AS WELL AS EXISTING 225K UNIT WHICH |
| | ONLY NOTES CWP FOR CONNECTION. |
| | |
| | 5) NOTE: PLEASE KNOW ANY CONNECTIONS OF SYSTEMS, |
| | PANELS, LOADS, CONDUCTORS ETC TO THE EXISTING SERVICE |
| | WILL REQUIRE THE SERVICE AS SHOWN(MAIN SWITCH GEAR) |
| | TO BE BROUGHT UP TO CODE.THE SERVICE AS SHOWN DOES |
| | NOT MEET CURRENT CODE FOR MANY ITEMS AND ANY CHANGE IN |
| | SERVICE OR SYSTEMS OF SERVICE WILL REQUIRE THIS TO BE |
| | BROUGHT UP TO CURRENT CODE. |
| | THIS WAS CONFIRMED ALL OTHER ELECTRICAL PLAN REVIEW |
| | STAFF AS WELL AS THE CHIEF ELECTRICAL INSPECTOR OVER |
| | INSPECTIONS. THE SERVICE AS SHOWN WHICH EXISTS DOES NOT |
| | COMPLY WITH THE CURRENT CODE OR CODES GOING BACK FOR |
| | DECADES. THERE ARE SEVERAL SAFETY ISSUES ON THIS |
| | SERVICE FROM PROTECTION OF CONDUCTORS, EFFECTIVE |
| | GROUNDING, TAPPED CONDUCTORS, OVER LOADING ETC. PLEASE |
| | SEE THE MAIN SWITCH BOARD DOES NOT SHOW ANY SEPARATION |
| | OF SYSTEMS BASED ON PLANS SUBMITTED. PLEASE SEE THE |
| | MAIN SWITCH BOARD DOES NOT INDICATE ALL POSSIBLE |
| | MAINS. |
| | PLEASE SEE THE MAIN SWITCH BOARD WHICH IS SHOWN FEEDING |
| | OUT TO THE 225K TRANSFORMER SHOWS THESE CONDUCTORS |
| | COMING BACK INTO A MLO 800A BUS WITH NO TERMINATION |
| | INTO A SINGLE MEANS OF OVER CURRENT PROTECTION OF ANY |
| | KIND. |
| | PLEASE SEE THE TAPPED CONDUCTORS ON THE SECONDARY SIDE |
| | OF THIS SAME 225K TRANSFORMER ARE NOT RATED FOR |
| | 800AMPS. |
| | PLEASE SEE THE FEEDERS ON SCHEDULE SHOULD COORDINATE |
| | WITH RISER. FOR EXAMPLE: PLEASE SEE PANEL *C*. PLEASE |
| | SEE 240.4, 310.16, 230.70, 230.71, 230.2, 240.21, |
| | 240.13, ETC |
| | THERE ARE TOO MANY SECTIONS TO LIST. |
| | |
| | * PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH MAY |
| | CHANGE, THERE MAY VERY WELL BE NEW COMMENTS ON THE NEXT |
| | REVIEW. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |