2008-01-27 21:03:47BUILDING PLAN REVIEW
 PERMIT: 08010437
 ADD: 1041 45TH ST
 CONT: ** PLAN REVIEW**
 TEL: (561)###-####
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW"PLAN REVIEW"
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2)) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.UPDATE THE CODE COMPLIANCE TO INCLUDE THE 2007
 SUPPLEMENTS.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3. COMPLIED.
 C) THE TYPE OF CONSTRUCTION AS DEFINEDIN CHAPTER 6,
 TABLE 601. TAGLE 601 CONSTRUCTION TYPE IIIA OR IIIB? D)
 THE OCCUPANT LOAD, SEE 1004.COMPLIED.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED? F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED? (AREA
 INCREASES)
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .H) NUMBER OF FLOORS
 THE ABOVE MENTIONED REQUIREMENTS ARE NEEDED TO DO AN
 ACCURATE REVIEW UNDER THE CURRENT CODES.
  
 3) THE TECHNICAL SPECIFICATIONS INDICATE THE PRESENCE
 OF ASBESTOS. PLEASE SEE WPB ADMINISTRATIVE CODE
 105.3.6* ,553.79 FL SS & 455.302 FL SSFOR ASBESTOS
 REMOVAL. THIS ABATEMENTOF ASBESTOS MUST BE BY STATE
 LAW MUST BE ACCOMPLISHED BYLICENSED CONTRACTORS.
 BFORE ABATEMENT OF ASBESTOS
 REQUIREMENTS INCLUDE - ASBESTOS SURVEY AND SUBMISSION
 OF WRITTEN NOTIFICATION TO THE FLORIDA DEPARTMENT OF
 ENVIROMENTAL PROTECTION PRIOR TO MOST RENOVATION
 ACTIVITIES IN REGULATED STRUCTURES WHERE ASBESTOS IS
 DISTURBED OR REMOVED. FOR FURTHER INFORMATION IN PALM
 BEACH COUNTY, CONTACT THE DIVISION OF ENVIROMENTAL
 HEALTH & ENGINEERING HRS/ PALM BEACH COUNTY HEALTH
 UNIT.
 HAS THE WRITTEN PERMISSION FOR REMOVAL OF ASBESTOS BEEN
 OBTAINED FOR THE PB COUNTY HEALTH DEPARTMENT?
  
 4) ON VARIOUS SHEETS WHERE THE DUCTS CROSS SMOKE
 BARRIERS FROM ONE CHAMBER TO ANOTHER THE DUCTS ARE
 MISSING SMOKE DAMPERS. PLEASE ILLUSTRATE CODE
 COMPLIANCE WITH 716.1.1 AND OR 712.3. AND 712.3.4.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  